Schneider Electric LC1D40A6BBE IEC contactor, TeSys Deca, nonreversing, 40A, 30HP at 480VAC, 3 phase, 3 pole, 3 NO, 24VDC coil, open style
Schneider Electric
$330.00
TeSys D Green contactors have been designed for perfect integration into control systems. They can be used to create motor starters for almost any type of application. TeSys D contactors are available in 13 contactor ratings for inductive motor applications up to 150 full-load amps and resistive loads up to 200 amps. This 40A inductive 3 pole IEC contactor can be mounted on DIN rail or mounted directly to a panel. Contactors have both Horsepower and Kw motor rating for international acceptance. Contactor is rated for 10HP at 200 to 208VAC, 10HP at 240VAC, 30HP at 480VAC and 30HP at 600VAC three phase. Contactor is also rated for 3HP at 115VAC and 5HP at 240VAC single phase. Equipped with an electronic 24V DC coil, low consumption, for a direct control by a PLC output 24V DC / 500mA. Contactor has one normally open and one normally closed auxiliary contact built-in as standard. The NC contact is mirror certified. Ring-lug screw terminals are used for load and auxiliary connections. An extensive line of accessories makes it easy to meet the requirements of most applications. The contactor is 4.80 inches tall, 2.17 inches wide and 4.72 inches deep. It weighs 2.19 lbs. Contactor is certified to UL, CSA, IEC, CCC, EAC and Marine standards. Contactor also meets the requirements of RoHS/REACh making it a Green Premium product.
- Control Circuit Voltage Limits:
- <= 0.1 Uc -40-70°C drop-out DC || 0.8...1.2 Uc -40-60°C operational DC || 1...1.2 Uc 60-70°C operational DC
- Flame Retardance:
- V1 conforming to UL 94
- Inrush Power In W:
- 11-11 W 20°C)
- [Ui] Rated Insulation Voltage:
- power circuit 690 V IEC 60947-4-1 || Signaling circuit 690 V IEC 60947-1
- Climatic Withstand:
- IACS E10 exposure to damp heat || IEC 60947-1 Annex Q category D exposure to damp heat
- Tightening Torque:
- control circuit 1.7 N.m lugs-ring terminals flat Ø 6 mm M3.5 || control circuit 1.7 N.m lugs-ring terminals Philips No 2 M3.5 || power circuit 6 N.m lugs-ring terminals hexagonal 10 mm M6 || power circuit 6 N.m lugs-ring terminals pozidriv No 2 M4 |
- Maximum Horse Power Rating:
- 3 hp at 115 V AC 60 Hz for 1 phase motors || 5 hp at 230/240 V AC 60 Hz for 1 phase motors || 10 hp at 200/208 V AC 60 Hz for 3 phase motors || 10 hp at 230/240 V AC 60 Hz for 3 phase motors || 30 hp at 460/480 V AC 60 Hz for 3 phase motors || 30 hp
- Mechanical Durability:
- 6 Mcycles
- Utilisation Category:
- AC-1 || AC-3 || AC-3e
- Hold-In Power Consumption In W:
- 0.5-0.5 W 20°C
- Product Certifications:
- CCC || CSA || EAC || UL || KC || DNV-GL || LROS (Lloyds register of shipping) || UKCA
- Range Of Product:
- TeSys Deca
- Safety Reliability Level:
- B10d = 1369863 cycles contactor with nominal load EN/ISO 13849-1 || B10d = 20000000 cycles contactor with mechanical load EN/ISO 13849-1
- Irms Rated Making Capacity:
- 800 A at 440 V for power circuit conforming to IEC 60947 || 140 A AC for Signaling circuit conforming to IEC 60947-5-1 || 250 A DC for Signaling circuit conforming to IEC 60947-5-1
- Power Dissipation Per Pole:
- 5.4 W AC-1 || 2.4 W AC-3 || 2.4 W AC-3e
- Poles Description:
- 3P
- Depth:
- 120 mm
- Operating Altitude:
- 0...9842.52 ft (0...3000 m)
- Non-Overlap Time:
- 1.5 ms on de-energisation between NC and NO contact || 1.5 ms on energisation between NC and NO contact
- Range:
- TeSys || TeSys Deca
- Protective Cover:
- with
- [Ie] Rated Operational Current:
- 60 A (at <60°C) at <= 440 V AC-1 for power circuit || 40 A (at <60°C) at <= 440 V AC-3 for power circuit || 40 A (at <60°C) at <= 440 V AC-3e for power circuit
- Rohs Exemption Information:
- Yes
- Compatibility Code:
- LC1D
- Pollution Degree:
- 3
- Permissible Ambient Air Temperature Around The Device:
- -40-60°C || 60-70°C with derating
- Signaling Circuit Frequency:
- 25...400 Hz
- Country of Origin:
- France
- Auxiliary Contact Composition:
- 1 NO + 1 NC
- Device Short Name:
- LC1D
- Minimum Switching Current:
- 5 mA for Signaling circuit
- Insulation Resistance:
- > 10 MOhm for Signaling circuit
- [Icw] Rated Short-Time Withstand Current:
- 72 A 40°C - 10 min for power circuit || 165 A 40°C - 1 min for power circuit || 320 A 40°C - 10 s for power circuit || 720 A 40°C - 1 s for power circuit || 100 A - 1 s for Signaling circuit || 120 A - 500 ms for Signaling circuit || 140 A - 100 ms f
- Net Weight:
- 0.992 kg
- Product Or Component Type:
- contactor
- Mercury Free:
- Yes
- Environmental Disclosure:
- ENVPEP1607010EN
- Connections - Terminals:
- power circuit: lugs-ring terminals - external diameter: 16.5 mm || control circuit: lugs-ring terminals - external diameter: 8 mm
- Fire Resistance:
- 850°C IEC 60695-2-1
- [Uimp] Rated Impulse Withstand Voltage:
- 6 kV IEC 60947
- Weight:
- 0.992 kg
- Overvoltage Category:
- III
- Standards:
- EN/IEC 60947-4-1 || EN/IEC 60947-5-1 || UL 60947-4-1 || CSA C22.2 No 60947-4-1 || IEC 60335-1
- Eu Rohs Directive:
- Compliant with Exemptions
- Minimum Switching Voltage:
- 17 V for Signaling circuit
- Maximum Operating Rate:
- 3600 cyc/h 60°C