Schneider Electric

Schneider Electric LC1D40A6M7 IEC contactor, TeSys Deca, nonreversing, 40A, 30HP at 480VAC, 3 phase, 3 pole, 3 NO, 220VAC 50/60Hz coil, open style

(No reviews yet) Write a Review
SKU:
LC1D40A6M7
MPN:
LC1D40A6M7
Condition:
New
Circularity Profile:
ENVEOLI1503009EN
Heat Dissipation:
4-5 W at 50/60 Hz
Non-Overlap Time:
1.5 ms on de-energisation between NC and NO contact || 1.5 ms on energisation between NC and NO contact
Operating Altitude:
0...9842.52 ft (0...3000 m)
Product Or Component Type:
contactor
Mechanical Durability:
6 Mcycles
Toxic Heavy Metal Free:
Yes
China Rohs Regulation:
Pro-active China RoHS declaration (out of China RoHS legal scope)
Operating Time:
4...19 ms opening || 12...26 ms closing
Fire Resistance:
850°C IEC 60695-2-1
Depth:
120 mm
Safety Reliability Level:
B10d = 1369863 cycles contactor with nominal load EN/ISO 13849-1 || B10d = 20000000 cycles contactor with mechanical load EN/ISO 13849-1
Ip Degree Of Protection:
IP20 front face IEC 60529
Overvoltage Category:
III
Hold-In Power Consumption In Va:
13-13 VA 60 Hz cos phi 0.3 (at 20°C) || 15-15 VA 50 Hz cos phi 0.3 (at 20°C)
Tightening Torque:
control circuit 1.7 N.m lugs-ring terminals flat Ø 6 mm M3.5 || control circuit 1.7 N.m lugs-ring terminals Philips No 2 M3.5 || power circuit 6 N.m lugs-ring terminals hexagonal 10 mm M6 || control circuit 1.7 N.m screw clamp terminals pozidriv No
Product Certifications:
CCC || UL || CB Scheme || CSA || CE || UKCA || Marine || EAC
[Uc] Control Circuit Voltage:
220 V AC 50/60 Hz
Control Circuit Voltage Limits:
0.3...0.6 Uc -40-70°C drop-out AC 50/60 Hz || 0.8...1.1 Uc -40-60°C operational AC 50 Hz || 0.85...1.1 Uc -40-60°C operational AC 60 Hz || 1...1.1 Uc 60-70°C operational AC 50/60 Hz
Auxiliary Contacts Type:
mechanically linked 1 NO + 1 NC IEC 60947-5-1 || mirror contact 1 NC IEC 60947-4-1
Control Circuit Type:
AC 50/60 Hz
Auxiliary Contact Composition:
1 NO + 1 NC
Protective Cover:
with
[Ie] Rated Operational Current:
60 A (at <60°C) at <= 440 V AC AC-1 for power circuit || 40 A (at <60°C) at <= 440 V AC AC-3 for power circuit || 40 A (at <60°C) at <= 440 V AC AC-3e for power circuit
Pole Contact Composition:
3 NO
Standards:
EN 60947-4-1 || EN 60947-5-1 || IEC 60947-4-1 || IEC 60947-5-1 || CSA C22.2 No 14 || UL 60947-4-1 || IEC 60335-2-40:Annex JJ || UL 60335-2-40:Annex JJ || IEC 60335-1:Clause 30.2
Flame Retardance:
V1 conforming to UL 94
Average Impedance:
1.5 mOhm - Ith 60 A 50 Hz for power circuit
Minimum Switching Current:
5 mA for Signaling circuit
Irms Rated Making Capacity:
140 A AC for Signaling circuit conforming to IEC 60947-5-1 || 250 A DC for Signaling circuit conforming to IEC 60947-5-1 || 800 A at 440 V for power circuit conforming to IEC 60947
Electrical Durability:
1.4 Mcycles 60 A AC-1 <= 440 V || 1.5 Mcycles 40 A AC-3 <= 440 V || 1.5 Mcycles 40 A AC-3e <= 440 V
Mounting Support:
plate || rail
Country of Origin:
Indonesia
Environmental Disclosure:
ENVPEP1503009EN
Maximum Horse Power Rating:
5 hp at 230/240 V AC 50/60 Hz for 1 phase motors || 10 hp at 230/240 V AC 50/60 Hz for 3 phase motors || 30 hp at 575/600 V AC 50/60 Hz for 3 phase motors || 10 hp at 200/208 V AC 50/60 Hz for 3 phase motors || 3 hp at 115 V AC 50/60 Hz for 1 phase m
Associated Fuse Rating:
10 A gG for Signaling circuit conforming to IEC 60947-5-1 || 80 A gG at <= 690 V coordination type 1 for power circuit || 80 A gG at <= 690 V coordination type 2 for power circuit
Eu Rohs Directive:
Compliant
Power Dissipation Per Pole:
2.4 W AC-3 || 5.4 W AC-1 || 2.4 W AC-3e
Reach Free Of Svhc:
Yes
Motor Power Kw:
18.5 kW at 380...400 V AC 50/60 Hz (AC-3) || 11 kW at 220...230 V AC 50/60 Hz (AC-3) || 22 kW at 415...440 V AC 50/60 Hz (AC-3) || 22 kW at 500 V AC 50/60 Hz (AC-3) || 30 kW at 660...690 V AC 50/60 Hz (AC-3) || 9 kW at 400 V AC 50/60 Hz (AC-4) || 18.
Net Weight:
0.85 kg
Protective Treatment:
THIEC 60068-2-30
Range:
TeSys || TeSys Deca
Sustainable Offer Status:
Green Premium product
Contactor Application:
resistive load || motor control
$261.60

Description

TeSys D contactors have been designed for perfect integration into control systems. They can be used to create motor starters for almost any type of application. TeSys D contactors are available in 13 contactor ratings for inductive motor applications up to 150 full-load amps and resistive loads up to 200 amps. This 40A inductive 3 pole IEC contactor can be mounted on DIN rail or mounted directly to a panel. Contactors have both Horsepower and Kw motor rating for international acceptance. Contactor is rated for 10HP at 200 to 208VAC, 10HP at 240VAC, 30HP at 480VAC and 30HP at 600VAC three phase. Contactor is also rated for 3HP at 115VAC and 5HP at 240VAC single phase. Contactor is supplied with a 220 VAC 50/60 Hz coil. Contactor has one normally open and one normally closed auxiliary contact built-in as standard. The NC contact is mirror certified. Ring-lug screw terminals are used for load and auxiliary connections. An extensive line of accessories makes it easy to meet the requirements of most applications. The contactor is 4.80 inches tall, 2.17 inches wide and 4.72 inches deep. It weighs 1.87 lbs. Contactor is certified to UL, CSA, IEC, CCC, EAC and Marine standards. Contactor also meets the requirements of RoHS/REACh making it a Green Premium product.