Schneider Electric

Schneider Electric LC1D40ABBE IEC contactor, TeSys Deca Green, nonreversing, 40A, 30HP at 480VAC, up to 100kA SCCR, 3 phase, 3 NO, 24VDC coil, open style

(No reviews yet) Write a Review
SKU:
LC1D40ABBE
MPN:
LC1D40ABBE
Condition:
New
[Ie] Rated Operational Current:
60 A (at <60°C) at <= 440 V AC-1 for power circuit || 40 A (at <60°C) at <= 440 V AC-3 for power circuit || 40 A (at <60°C) at <= 440 V AC-3e for power circuit
[Uc] Control Circuit Voltage:
24 V DC
Safety Reliability Level:
B10d = 1369863 cycles contactor with nominal load EN/ISO 13849-1 || B10d = 20000000 cycles contactor with mechanical load EN/ISO 13849-1
Country of Origin:
France
Eu Rohs Directive:
Compliant with Exemptions
Coil Technology:
built-in bidirectional peak limiting
Heat Dissipation:
0.5-0.5 W
Maximum Horse Power Rating:
3 hp at 115 V AC 60 Hz for 1 phase motors || 5 hp at 230/240 V AC 60 Hz for 1 phase motors || 10 hp at 200/208 V AC 60 Hz for 3 phase motors || 10 hp at 230/240 V AC 60 Hz for 3 phase motors || 30 hp at 460/480 V AC 60 Hz for 3 phase motors || 30 hp
Minimum Switching Voltage:
17 V for Signaling circuit
Control Circuit Voltage Limits:
<= 0.1 Uc -40-70°C drop-out DC || 0.8...1.2 Uc -40-60°C operational DC || 1...1.2 Uc 60-70°C operational DC
Sustainable Offer Status:
Green Premium product
Mercury Free:
Yes
Fire Resistance:
850°C IEC 60695-2-1
Product Or Component Type:
contactor
[Icw] Rated Short-Time Withstand Current:
72 A 40°C - 10 min for power circuit || 165 A 40°C - 1 min for power circuit || 320 A 40°C - 10 s for power circuit || 720 A 40°C - 1 s for power circuit || 100 A - 1 s for Signaling circuit || 120 A - 500 ms for Signaling circuit || 140 A - 100 ms f
Control Circuit Type:
DC DC low consumption
[Uimp] Rated Impulse Withstand Voltage:
6 kV IEC 60947
Rated Breaking Capacity:
800 A at 440 V for power circuit conforming to IEC 60947
Overvoltage Category:
III
Permissible Ambient Air Temperature Around The Device:
-40-60°C || 60-70°C with derating
Inrush Power In W:
11-11 W 20°C)
Weight:
0.992 kg
Weee:
The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins.
Rohs Exemption Information:
Yes
Maximum Operating Rate:
3600 cyc/h 60°C
China Rohs Regulation:
Product out of China RoHS scope. Substance declaration for your information.
Flame Retardance:
V1 conforming to UL 94
Signaling Circuit Frequency:
25...400 Hz
[Ith] Conventional Free Air Thermal Current:
60 A (at 60°C) for power circuit || 10 A (at 60°C) for Signaling circuit
Halogen Content Performance:
Halogen free plastic parts & cables product
Connections - Terminals:
power circuit: EverLink BTR screw connectors 1 1-35 mm² - cable stiffness: solid || power circuit: EverLink BTR screw connectors 2 1-25 mm² - cable stiffness: solid || power circuit: EverLink BTR screw connectors 1 1-35 mm² - cable stiffness: flex
Non-Overlap Time:
1.5 ms on de-energisation between NC and NO contact || 1.5 ms on energisation between NC and NO contact
Tightening Torque:
control circuit 1.7 N.m screw clamp terminals flat Ø 6 mm || control circuit 1.7 N.m screw clamp terminals Philips No 2 || power circuit 8 N.m EverLink BTR screw connectors 25-35 mm² hexagonal 4 mm || power circuit 5 N.m EverLink BTR screw connecto
Mechanical Durability:
6 Mcycles
Pollution Degree:
3
Compatibility Code:
LC1D
Irms Rated Making Capacity:
800 A at 440 V for power circuit conforming to IEC 60947 || 140 A AC for Signaling circuit conforming to IEC 60947-5-1 || 250 A DC for Signaling circuit conforming to IEC 60947-5-1
Electrical Durability:
2 Mcycles 35 A AC-3 <= 440 V || 0.7 Mcycles 60 A AC-1 <= 440 V || 2 Mcycles 35 A AC-3e <= 440 V
Operating Altitude:
0...9842.52 ft (0...3000 m)
Environmental Disclosure:
ENVPEP1607010EN
Product Certifications:
CCC || CSA || EAC || UL || KC || DNV-GL || LROS (Lloyds register of shipping) || UKCA
[Ue] Rated Operational Voltage:
power circuit <= 690 V AC 25...400 Hz
Auxiliary Contacts Type:
mechanically linked 1 NO + 1 NC IEC 60947-5-1 || mirror contact 1 NC IEC 60947-4-1
Pole Contact Composition:
3 NO
Warranty:
18 months
Reach Regulation:
Reference contains Substances of Very High Concern above the threshold
Standards:
EN/IEC 60947-4-1 || EN/IEC 60947-5-1 || UL 60947-4-1 || CSA C22.2 No 60947-4-1 || IEC 60335-1
Insulation Resistance:
> 10 MOhm for Signaling circuit
$111.00

Description

TeSys D Green contactors have been designed for perfect integration into control systems. They can be used to create motor starters for almost any type of application. TeSys D contactors are available in 13 contactor ratings for inductive motor applications up to 150 full-load amps and resistive loads up to 200 amps. This 40A inductive 3 pole IEC contactor can be mounted on DIN rail or mounted directly to a panel. Contactors have both Horsepower and Kw motor rating for international acceptance. Contactor is rated for 10HP at 200 to 208VAC, 10HP at 240VAC, 30HP at 480VAC and 30HP at 600VAC three phase. Contactor is also rated for 3HP at 115VAC and 5HP at 240VAC single phase. When used with a 480VAC up to 110A circuit breaker, this contactor can have a SCCR up to 100kA. When used with up to a 600VAC 90A Class J or CC fuse, this contactor can have a SCCR up to 100kA. Equipped with an electronic 24V DC coil, low consumption, for a direct control by a PLC output 24V DC / 500mA. Contactor has one normally open and one normally closed auxiliary contact built-in as standard. The NC contact is mirror certified. Screw clamp terminals are used for load and auxiliary connections. An extensive line of accessories makes it easy to meet the requirements of most applications. The contactor is 4.80 inches tall, 2.17 inches wide and 4.72 inches deep. It weighs 2.19 lbs. Contactor is certified to UL, CSA, IEC, CCC, EAC and Marine standards. Contactor also meets the requirements of RoHS/REACh making it a Green Premium product.
View AllClose