Schneider Electric

Schneider Electric LC1D40AJD IEC contactor, TeSys Deca, nonreversing, 40A, 30HP at 480VAC, up to 100kA SCCR, 3 phase, 3 NO, 12VDC coil, open style

(No reviews yet) Write a Review
SKU:
LC1D40AJD
MPN:
LC1D40AJD
Condition:
New
Sustainable Offer Status:
Green Premium product
Time Constant:
34 ms
Environmental Disclosure:
ENVPEP1503009EN
[Ith] Conventional Free Air Thermal Current:
10 A (at 60°C) for Signaling circuit || 60 A (at 60°C) for power circuit
Device Short Name:
LC1D
[Ie] Rated Operational Current:
60 A (at <60°C) at <= 440 V AC AC-1 for power circuit || 40 A (at <60°C) at <= 440 V AC AC-3 for power circuit || 40 A (at <60°C) at <= 440 V AC AC-3e for power circuit
Mechanical Robustness:
vibrations contactor open 2 Gn, 5...300 Hz) || vibrations contactor closed 4 Gn, 5...300 Hz) || shocks contactor closed 15 Gn for 11 ms) || shocks contactor open 10 Gn for 11 ms)
Rated Breaking Capacity:
800 A at 440 V for power circuit conforming to IEC 60947
China Rohs Regulation:
Pro-active China RoHS declaration (out of China RoHS legal scope)
Net Weight:
0.925 kg
Overvoltage Category:
III
Pole Contact Composition:
3 NO
Auxiliary Contact Composition:
1 NO + 1 NC
Hold-In Power Consumption In W:
7.4-7.4 W 20°C
Climatic Withstand:
IACS E10 exposure to damp heat || IEC 60947-1 Annex Q category D exposure to damp heat
Fire Resistance:
850°C IEC 60695-2-1
Auxiliary Contacts Type:
mechanically linked 1 NO + 1 NC IEC 60947-5-1 || mirror contact 1 NC IEC 60947-4-1
Operating Altitude:
0...9842.52 ft (0...3000 m)
[Icw] Rated Short-Time Withstand Current:
320 A 40°C - 10 s for power circuit || 720 A 40°C - 1 s for power circuit || 72 A 40°C - 10 min for power circuit || 165 A 40°C - 1 min for power circuit || 100 A - 1 s for Signaling circuit || 120 A - 500 ms for Signaling circuit || 140 A - 100 ms f
Power Dissipation Per Pole:
2.4 W AC-3 || 5.4 W AC-1 || 2.4 W AC-3e
Poles Description:
3P
Warranty:
18 months
Minimum Switching Current:
5 mA for Signaling circuit
Control Circuit Type:
DC standard
Motor Power Kw:
18.5 kW at 380...400 V AC 50/60 Hz (AC-3) || 11 kW at 220...230 V AC 50/60 Hz (AC-3) || 22 kW at 415...440 V AC 50/60 Hz (AC-3) || 22 kW at 500 V AC 50/60 Hz (AC-3) || 30 kW at 660...690 V AC 50/60 Hz (AC-3) || 9 kW at 400 V AC 50/60 Hz (AC-4) || 18.
[Uc] Control Circuit Voltage:
12 V DC
Product Certifications:
CCC || UL || CB Scheme || CSA || CE || UKCA || Marine || EAC
Connections - Terminals:
control circuit: screw clamp terminals 2 1-2.5 mm² - cable stiffness: flexible with cable end || control circuit: screw clamp terminals 1 1-4 mm² - cable stiffness: flexible without cable end || control circuit: screw clamp terminals 2 1-4 mm² - c
Product Or Component Type:
contactor
Coil Technology:
built-in bidirectional peak limiting diode suppressor
Pollution Degree:
3
Rohs Exemption Information:
Yes
[Ue] Rated Operational Voltage:
power circuit <= 690 V AC 25...400 Hz || power circuit <= 300 V DC
Width:
55 mm
Electrical Durability:
0.7 Mcycles 60 A AC-1 <= 440 V || 1.5 Mcycles 40 A AC-3 <= 440 V || 1.5 Mcycles 40 A AC-3e <= 440 V
Eu Rohs Directive:
Compliant
Contactor Application:
motor control || resistive load
Range:
TeSys || TeSys Deca
Mercury Free:
Yes
Average Impedance:
1.5 mOhm - Ith 60 A 50 Hz for power circuit
Utilisation Category:
AC-4 || AC-1 || AC-3 || AC-3e
Safety Reliability Level:
B10d = 1369863 cycles contactor with nominal load EN/ISO 13849-1 || B10d = 20000000 cycles contactor with mechanical load EN/ISO 13849-1
Maximum Horse Power Rating:
5 hp at 230/240 V AC 50/60 Hz for 1 phase motors || 10 hp at 230/240 V AC 50/60 Hz for 3 phase motors || 30 hp at 575/600 V AC 50/60 Hz for 3 phase motors || 10 hp at 200/208 V AC 50/60 Hz for 3 phase motors || 3 hp at 115 V AC 50/60 Hz for 1 phase m
Maximum Operating Rate:
3600 cyc/h 60°C
Country of Origin:
France
Tightening Torque:
control circuit 1.7 N.m screw clamp terminals flat Ø 6 mm || control circuit 1.7 N.m screw clamp terminals Philips No 2 || power circuit 8 N.m EverLink BTR screw connectors 25-35 mm² hexagonal 4 mm || power circuit 5 N.m EverLink BTR screw connecto
Weight:
0.925 kg
$275.00

Description

TeSys D contactors have been designed for perfect integration into control systems. They can be used to create motor starters for almost any type of application. TeSys D contactors are available in 13 contactor ratings for inductive motor applications up to 150 full-load amps and resistive loads up to 200 amps. This 40A inductive 3 pole IEC contactor can be mounted on DIN rail or mounted directly to a panel. Contactors have both Horsepower and Kw motor rating for international acceptance. Contactor is rated for 10HP at 200 to 208VAC, 10HP at 240VAC, 30HP at 480VAC and 30HP at 600VAC three phase. Contactor is also rated for 3HP at 115VAC and 5HP at 240VAC single phase. When used with a 480VAC up to 110A circuit breaker, this contactor can have a SCCR up to 100kA. When used with up to a 600VAC 90A Class J or CC fuse, this contactor can have a SCCR up to 100kA. Contactor is supplied with a 12 VDC coil with transient suppressor module. Contactor has one normally open and one normally closed auxiliary contact built-in as standard. The NC contact is mirror certified. Screw clamp terminals are used for load and auxiliary connections. An extensive line of accessories makes it easy to meet the requirements of most applications. The contactor is 4.80 inches tall, 2.17 inches wide and 4.72 inches deep. It weighs 1.87 lbs. Contactor is certified to UL, CSA, IEC, CCC, EAC and Marine standards. Contactor also meets the requirements of RoHS/REACh making it a Green Premium product.
View AllClose