TeSys D contactors have been designed for perfect integration into control systems. They can be used to create motor starters for almost any type of application. TeSys D contactors are available in 13 contactor ratings for inductive motor applications up to 150 full-load amps and resistive loads up to 200 amps. This 40A inductive 3 pole IEC contactor can be mounted on DIN rail or mounted directly to a panel. Contactors have both Horsepower and Kw motor rating for international acceptance. Contactor is rated for 10HP at 200 to 208VAC, 10HP at 240VAC, 30HP at 480VAC and 30HP at 600VAC three phase. Contactor is also rated for 3HP at 115VAC and 5HP at 240VAC single phase. When used with a 480VAC up to 110A circuit breaker, this contactor can have a SCCR up to 100kA. When used with up to a 600VAC 90A Class J or CC fuse, this contactor can have a SCCR up to 100kA. Contactor is supplied with a 120 VAC 60 Hz coil. Contactor has one normally open and one normally closed auxiliary contact built-in as standard. The NC contact is mirror certified. Screw clamp terminals are used for load and auxiliary connections. An extensive line of accessories makes it easy to meet the requirements of most applications. The contactor is 4.80 inches tall, 2.17 inches wide and 4.72 inches deep. It weighs 1.87 lbs. Contactor is certified to UL, CSA, IEC, CCC, EAC and Marine standards. Contactor also meets the requirements of RoHS/REACh making it a Green Premium product.
- Insulation Resistance:
- > 10 MOhm for control circuit
- Mounting Support:
- rail || plate
- Poles Description:
- 3P
- Climatic Withstand:
- IACS E10 exposure to damp heat
- Product Or Component Type:
- contactor
- Maximum Operating Rate:
- 3600 cyc/h 60°C
- Width:
- 75 mm
- Non-Overlap Time:
- 1.5 ms on de-energisation between NC and NO contacts || 1.5 ms on energisation between NC and NO contacts
- Safety Reliability Level:
- B10d = 1369863 cycles contactor with nominal load EN/ISO 13849-1 || B10d = 20000000 cycles contactor with mechanical load EN/ISO 13849-1
- Inrush Power In Va:
- 140-140 VA cos phi 0.75 (at 20°C) || 160-160 VA cos phi 0.75 (at 20°C)
- Auxiliary Contacts Type:
- mirror contact 1 NC IEC 60947-4-1 || mechanically linked 1 NO + 1 NC IEC 60947-5-1
- China Rohs Regulation:
- Pro-active China RoHS declaration (out of China RoHS legal scope)
- Auxiliary Contact Composition:
- 1 NO + 1 NC
- [Ue] Rated Operational Voltage:
- power circuit <= 690 V AC 25...400 Hz
- [Ith] Conventional Free Air Thermal Current:
- 10 A (at 60°C) for control circuit || 60 A (at 60°C) for power circuit
- [Ui] Rated Insulation Voltage:
- control circuit 600 V CSA || control circuit 600 V UL || power circuit 600 V CSA || power circuit 600 V UL || control circuit 690 V IEC 60947-1 || power circuit 690 V IEC 60947-1
- Net Weight:
- 1.4 kg
- Standards:
- EN 60947-5-1 || IEC 60947-4-1 || UL 508 || CSA C22.2 No 14 || EN 60947-4-1 || IEC 60947-5-1
- Power Dissipation Per Pole:
- 5.4 W AC-1 || 2.4 W AC-3 || 2.4 W AC-3e
- Rated Breaking Capacity:
- 800 A at 440 V for power circuit conforming to IEC 60947
- Device Short Name:
- LC1D
- [Ie] Rated Operational Current:
- 60 A (at <60°C) at <= 440 V AC AC-1 for power circuit || 40 A (at <60°C) at <= 440 V AC AC-3 for power circuit || 40 A (at <60°C) at <= 440 V AC AC-3e for power circuit
- Contactor Application:
- resistive load || motor control
- Mechanical Robustness:
- shocks contactor opened 10 Gn for 11 ms) || shocks contactor closed 15 Gn for 11 ms) || vibrations contactor opened 2 Gn, 5...300 Hz) || vibrations contactor closed 4 Gn, 5...300 Hz)
- Range Of Product:
- TeSys Deca
- Eu Rohs Directive:
- Compliant
- Minimum Switching Current:
- 5 mA for control circuit
- Associated Fuse Rating:
- 10 A gG for control circuit conforming to IEC 60947-5-1 || 80 A gG at <= 690 V coordination type 1 for power circuit || 80 A gG at <= 690 V coordination type 2 for power circuit
- Pvc Free:
- Yes
- Mercury Free:
- Yes
- Warranty:
- 18 months
- Environmental Disclosure:
- ENVPEP110205EN
- Circularity Profile:
- N/A
- Motor Power Kw:
- 18.5 kW at 380...400 V AC 50/60 Hz || 22 kW at 500 V AC 50/60 Hz || 30 kW at 660...690 V AC 50/60 Hz || 11 kW at 220...230 V AC 50/60 Hz || 22 kW at 1000 V AC 50/60 Hz || 22 kW at 415 V AC 50/60 Hz || 22 kW at 440 V AC 50/60 Hz
- Permissible Ambient Air Temperature Around The Device:
- -5-60°C || -40-70°C at Uc
- Protective Cover:
- with
- Ip Degree Of Protection:
- IP2X IEC 60529 || IP2X VDE 0106
- Height:
- 127 mm
- Control Circuit Voltage Limits:
- 0.85...1.1 Uc 60-60°C operational AC 60 Hz || 0.3...0.6 Uc 60-60°C drop-out AC 60 Hz
- Product Certifications:
- GL || BV || DNV || LROS (Lloyds register of shipping) || RINA || UL || CCC || CSA || GOST || UKCA || CB
- Fire Resistance:
- 850°C IEC 60695-2-1
- Operating Altitude:
- 9842.52 ft (3000 m) without derating
- Tightening Torque:
- control circuit 1.7 N.m screw clamp terminal flat Ø 6 mm || control circuit 1.7 N.m screw clamp terminal Philips No 2 || power circuit 5 N.m screw clamp terminal flat Ø 6 mm || power circuit 5 N.m screw clamp terminal flat Ø 8 mm || control circui
- Connections - Terminals:
- control circuit: screw clamp terminal 1 1-4 mm² - cable stiffness: solid without cable end || control circuit: screw clamp terminal 2 1-4 mm² - cable stiffness: solid without cable end || control circuit: screw clamp terminal 1 1-2.5 mm² - cable s
- Utilisation Category:
- AC-2 || AC-1 || AC-3 || AC-4 || AC-3e
- Weee:
- The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins.
- Sustainable Offer Status:
- Green Premium product
- Rohs Exemption Information:
- Yes
- Weight:
- 1.4 kg
- Depth:
- 119 mm