Schneider Electric

Schneider Electric LC1D50AB7 IEC contactor, TeSys Deca, nonreversing, 50A, 40HP at 480VAC, up to 100kA SCCR, 3 phase, 3 NO, 24VAC 50/60Hz coil, open

(No reviews yet) Write a Review
SKU:
LC1D50AB7
MPN:
LC1D50AB7
Condition:
New
Insulation Resistance:
> 10 MOhm for Signaling circuit
Height:
122 mm
Product Or Component Type:
contactor
Operating Altitude:
0...9842.52 ft (0...3000 m)
[Ue] Rated Operational Voltage:
power circuit <= 690 V AC 25...400 Hz || power circuit <= 300 V DC
Hold-In Power Consumption In Va:
13-13 VA 60 Hz cos phi 0.3 (at 20°C) || 15-15 VA 50 Hz cos phi 0.3 (at 20°C)
Maximum Operating Rate:
3600 cyc/h 60°C
Pvc Free:
Yes
Control Circuit Type:
AC 50/60 Hz standard
Circularity Profile:
ENVEOLI1503009EN
Coil Technology:
without built-in suppressor module
Mechanical Robustness:
vibrations contactor open 2 Gn, 5...300 Hz) || vibrations contactor closed 4 Gn, 5...300 Hz) || shocks contactor closed 15 Gn for 11 ms) || shocks contactor open 10 Gn for 11 ms)
Sustainable Offer Status:
Green Premium product
Associated Fuse Rating:
10 A gG for Signaling circuit conforming to IEC 60947-5-1 || 100 A gG at <= 690 V coordination type 1 for power circuit || 100 A gG at <= 690 V coordination type 2 for power circuit
Protective Cover:
with
Pole Contact Composition:
3 NO
Minimum Switching Voltage:
17 V for Signaling circuit
Reach Regulation:
Free of Substances of Very High Concern above the threshold
Reach Free Of Svhc:
Yes
Net Weight:
0.855 kg
Eu Rohs Directive:
Compliant
Rated Breaking Capacity:
900 A at 440 V for power circuit conforming to IEC 60947
Utilisation Category:
AC-4 || AC-1 || AC-3 || AC-3e
Compatibility Code:
LC1D
Poles Description:
3P
Protective Treatment:
THIEC 60068-2-30
Signaling Circuit Frequency:
25...400 Hz
[Uimp] Rated Impulse Withstand Voltage:
6 kV IEC 60947
Maximum Horse Power Rating:
3 hp at 115 V AC 50/60 Hz for 1 phase motors || 7.5 hp at 230/240 V AC 50/60 Hz for 1 phase motors || 15 hp at 200/208 V AC 50/60 Hz for 3 phase motors || 15 hp at 230/240 V AC 50/60 Hz for 3 phase motors || 40 hp at 460/480 V AC 50/60 Hz for 3 phase
Average Impedance:
1.5 mOhm - Ith 80 A 50 Hz for power circuit
Heat Dissipation:
4-5 W at 50/60 Hz
Minimum Switching Current:
5 mA for Signaling circuit
Country of Origin:
Singapore
Mounting Support:
plate || rail
[Icw] Rated Short-Time Withstand Current:
400 A 40°C - 10 s for power circuit || 810 A 40°C - 1 s for power circuit || 84 A 40°C - 10 min for power circuit || 208 A 40°C - 1 min for power circuit || 100 A - 1 s for Signaling circuit || 120 A - 500 ms for Signaling circuit || 140 A - 100 ms f
Range:
TeSys || TeSys Deca
Power Dissipation Per Pole:
3.7 W AC-3 || 9.6 W AC-1 || 3.7 W AC-3e
Ip Degree Of Protection:
IP20 front face IEC 60529
Electrical Durability:
1.45 Mcycles 50 A AC-3 <= 440 V || 1.1 Mcycles 80 A AC-1 <= 440 V || 1.45 Mcycles 50 A AC-3e <= 440 V
Warranty:
18 months
Motor Power Kw:
15 kW at 220...230 V AC 50/60 Hz (AC-3) || 22 kW at 380...400 V AC 50/60 Hz (AC-3) || 30 kW at 500 V AC 50/60 Hz (AC-3) || 33 kW at 660...690 V AC 50/60 Hz (AC-3) || 25 kW at 415 V AC 50/60 Hz (AC-3) || 30 kW at 440 V AC 50/60 Hz (AC-3) || 11 kW at 4
Safety Reliability Level:
B10d = 1369863 cycles contactor with nominal load EN/ISO 13849-1 || B10d = 20000000 cycles contactor with mechanical load EN/ISO 13849-1
Mercury Free:
Yes
Range Of Product:
TeSys Deca
Product Certifications:
CCC || UL || CB Scheme || CSA || CE || UKCA || Marine || EAC
Flame Retardance:
V1 conforming to UL 94
Weight:
0.855 kg
Device Short Name:
LC1D
Permissible Ambient Air Temperature Around The Device:
-40-60°C || 60-70°C with derating
China Rohs Regulation:
Pro-active China RoHS declaration (out of China RoHS legal scope)
$295.20

Description

TeSys D contactors have been designed for perfect integration into control systems. They can be used to create motor starters for almost any type of application. TeSys D contactors are available in 13 contactor ratings for inductive motor applications up to 150 full-load amps and resistive loads up to 200 amps. This 50A inductive 3 pole IEC contactor can be mounted on DIN rail or mounted directly to a panel. Contactors have both Horsepower and Kw motor rating for international acceptance. Contactor is rated for 15HP at 200 to 208VAC, 15HP at 240VAC, 40HP at 480VAC and 40HP at 600VAC three phase. Contactor is also rated for 3HP at 115VAC and 7.5HP at 240VAC single phase. When used with a 480VAC up to 110A circuit breaker, this contactor can have a SCCR up to 100kA. When used with up to a 600VAC 110A Class J or CC fuse, this contactor can have a SCCR up to 100kA. Contactor is supplied with a 24 VAC 50/60 Hz coil. Contactor has one normally open and one normally closed auxiliary contact built-in as standard. The NC contact is mirror certified. Screw clamp terminals are used for load and auxiliary connections. An extensive line of accessories makes it easy to meet the requirements of most applications. The contactor is 4.80 inches tall, 2.17 inches wide and 4.72 inches deep. It weighs 1.87 lbs. Contactor is certified to UL, CSA, IEC, CCC, EAC and Marine standards. Contactor also meets the requirements of RoHS/REACh making it a Green Premium product.
View AllClose