Schneider Electric

Schneider Electric LC1D50AFD IEC contactor, TeSys Deca, nonreversing, 50A, 40HP at 480VAC, up to 100kA SCCR, 3 phase, 3 NO, 110VDC coil, open style

(No reviews yet) Write a Review
SKU:
LC1D50AFD
MPN:
LC1D50AFD
Condition:
New
Reach Regulation:
Free of Substances of Very High Concern above the threshold
Mechanical Durability:
10 Mcycles
Associated Fuse Rating:
10 A gG for Signaling circuit conforming to IEC 60947-5-1 || 100 A gG at <= 690 V coordination type 1 for power circuit || 100 A gG at <= 690 V coordination type 2 for power circuit
Mechanical Robustness:
vibrations contactor open 2 Gn, 5...300 Hz) || vibrations contactor closed 4 Gn, 5...300 Hz) || shocks contactor closed 15 Gn for 11 ms) || shocks contactor open 10 Gn for 11 ms)
Control Circuit Type:
DC standard
Utilisation Category:
AC-4 || AC-1 || AC-3 || AC-3e
Time Constant:
34 ms
Weee:
The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins.
Irms Rated Making Capacity:
140 A AC for Signaling circuit conforming to IEC 60947-5-1 || 250 A DC for Signaling circuit conforming to IEC 60947-5-1 || 900 A at 440 V for power circuit conforming to IEC 60947
Signaling Circuit Frequency:
25...400 Hz
Protective Cover:
with
Mounting Support:
rail || plate
[Ui] Rated Insulation Voltage:
power circuit 600 V CSA || power circuit 600 V UL || Signaling circuit 690 V IEC 60947-1 || Signaling circuit 600 V CSA || Signaling circuit 600 V UL || power circuit 690 V IEC 60947-4-1
Hold-In Power Consumption In W:
7.4-7.4 W 20°C
Sustainable Packaging:
Yes
Coil Technology:
built-in bidirectional peak limiting diode suppressor
Tightening Torque:
control circuit 1.7 N.m EverLink BTR screw connectors flat Ø 6 mm || control circuit 1.7 N.m EverLink BTR screw connectors Philips No 2 || power circuit 8 N.m EverLink BTR screw connectors 25-35 mm² hexagonal 4 mm || power circuit 5 N.m EverLink BT
Compatibility Code:
LC1D
Maximum Horse Power Rating:
3 hp at 115 V AC 50/60 Hz for 1 phase motors || 7.5 hp at 230/240 V AC 50/60 Hz for 1 phase motors || 15 hp at 200/208 V AC 50/60 Hz for 3 phase motors || 15 hp at 230/240 V AC 50/60 Hz for 3 phase motors || 40 hp at 460/480 V AC 50/60 Hz for 3 phase
Circularity Profile:
ENVEOLI1503009EN
Sustainable Offer Status:
Green Premium product
Net Weight:
0.93 kg
Operating Altitude:
0...9842.52 ft (0...3000 m)
Auxiliary Contacts Type:
mechanically linked 1 NO + 1 NC IEC 60947-5-1 || mirror contact 1 NC IEC 60947-4-1
Reach Free Of Svhc:
Yes
Standards:
EN 60947-4-1 || EN 60947-5-1 || IEC 60947-4-1 || IEC 60947-5-1 || CSA C22.2 No 14 || UL 60947-4-1 || IEC 60335-2-40:Annex JJ || UL 60335-2-40:Annex JJ || IEC 60335-1:Clause 30.2
Inrush Power In W:
19-19 W 20°C)
Operating Time:
50±15 % ms closing || 16...24 ms opening
Overvoltage Category:
III
Poles Description:
3P
Product Certifications:
CCC || UL || CB Scheme || CSA || CE || UKCA || Marine || EAC
Power Dissipation Per Pole:
3.7 W AC-3 || 9.6 W AC-1 || 3.7 W AC-3e
[Ie] Rated Operational Current:
50 A (at <60°C) at <= 440 V AC AC-3 for power circuit || 80 A (at <60°C) at <= 440 V AC AC-1 for power circuit || 50 A (at <60°C) at <= 440 V AC AC-3e for power circuit
Insulation Resistance:
> 10 MOhm for Signaling circuit
Motor Power Kw:
15 kW at 220...230 V AC 50/60 Hz (AC-3) || 22 kW at 380...400 V AC 50/60 Hz (AC-3) || 30 kW at 500 V AC 50/60 Hz (AC-3) || 33 kW at 660...690 V AC 50/60 Hz (AC-3) || 25 kW at 415 V AC 50/60 Hz (AC-3) || 30 kW at 440 V AC 50/60 Hz (AC-3) || 11 kW at 4
Ip Degree Of Protection:
IP20 front face IEC 60529
[Ith] Conventional Free Air Thermal Current:
10 A (at 60°C) for Signaling circuit || 80 A (at 60°C) for power circuit
Permissible Ambient Air Temperature Around The Device:
-40-60°C || 60-70°C with derating
Control Circuit Voltage Limits:
0.1...0.3 Uc -40-70°C drop-out DC || 0.75...1.25 Uc -40-60°C operational DC || 1...1.25 Uc 60-70°C operational DC
Pollution Degree:
3
[Uc] Control Circuit Voltage:
110 V DC
[Icw] Rated Short-Time Withstand Current:
400 A 40°C - 10 s for power circuit || 810 A 40°C - 1 s for power circuit || 84 A 40°C - 10 min for power circuit || 208 A 40°C - 1 min for power circuit || 100 A - 1 s for Signaling circuit || 120 A - 500 ms for Signaling circuit || 140 A - 100 ms f
[Ue] Rated Operational Voltage:
power circuit <= 690 V AC 25...400 Hz || power circuit <= 300 V DC
Auxiliary Contact Composition:
1 NO + 1 NC
Protective Treatment:
THIEC 60068-2-30
$306.00

Description

TeSys D contactors have been designed for perfect integration into control systems. They can be used to create motor starters for almost any type of application. TeSys D contactors are available in 13 contactor ratings for inductive motor applications up to 150 full-load amps and resistive loads up to 200 amps. This 50A inductive 3 pole IEC contactor can be mounted on DIN rail or mounted directly to a panel. Contactors have both Horsepower and Kw motor rating for international acceptance. Contactor is rated for 15HP at 200 to 208VAC, 15HP at 240VAC, 40HP at 480VAC and 40HP at 600VAC three phase. Contactor is also rated for 3HP at 115VAC and 7.5HP at 240VAC single phase. When used with a 480VAC up to 110A circuit breaker, this contactor can have a SCCR up to 100kA. When used with up to a 600VAC 110A Class J or CC fuse, this contactor can have a SCCR up to 100kA. Contactor is supplied with a 110 VDC coil with transient suppressor module. Contactor has one normally open and one normally closed auxiliary contact built-in as standard. The NC contact is mirror certified. Screw clamp terminals are used for load and auxiliary connections. An extensive line of accessories makes it easy to meet the requirements of most applications. The contactor is 4.80 inches tall, 2.17 inches wide and 4.72 inches deep. It weighs 1.87 lbs. Contactor is certified to UL, CSA, IEC, CCC, EAC and Marine standards. Contactor also meets the requirements of RoHS/REACh making it a Green Premium product.
View AllClose