Schneider Electric LC1D50AGD IEC contactor, TeSys Deca, nonreversing, 50A, 40HP at 480VAC, up to 100kA SCCR, 3 phase, 3 NO, 125VDC coil, open style
Schneider Electric
$306.00
TeSys D contactors have been designed for perfect integration into control systems. They can be used to create motor starters for almost any type of application. TeSys D contactors are available in 13 contactor ratings for inductive motor applications up to 150 full-load amps and resistive loads up to 200 amps. This 50A inductive 3 pole IEC contactor can be mounted on DIN rail or mounted directly to a panel. Contactors have both Horsepower and Kw motor rating for international acceptance. Contactor is rated for 15HP at 200 to 208VAC, 15HP at 240VAC, 40HP at 480VAC and 40HP at 600VAC three phase. Contactor is also rated for 3HP at 115VAC and 7.5HP at 240VAC single phase. When used with a 480VAC up to 110A circuit breaker, this contactor can have a SCCR up to 100kA. When used with up to a 600VAC 110A Class J or CC fuse, this contactor can have a SCCR up to 100kA. Contactor is supplied with a 125 VDC coil with transient suppressor module. Contactor has one normally open and one normally closed auxiliary contact built-in as standard. The NC contact is mirror certified. Screw clamp terminals are used for load and auxiliary connections. An extensive line of accessories makes it easy to meet the requirements of most applications. The contactor is 4.80 inches tall, 2.17 inches wide and 4.72 inches deep. It weighs 1.87 lbs. Contactor is certified to UL, CSA, IEC, CCC, EAC and Marine standards. Contactor also meets the requirements of RoHS/REACh making it a Green Premium product.
- Inrush Power In W:
- 19-19 W 20°C)
- Mechanical Durability:
- 10 Mcycles
- Rated Breaking Capacity:
- 900 A at 440 V for power circuit conforming to IEC 60947
- Fire Resistance:
- 850°C IEC 60695-2-1
- Maximum Horse Power Rating:
- 3 hp at 115 V AC 50/60 Hz for 1 phase motors || 7.5 hp at 230/240 V AC 50/60 Hz for 1 phase motors || 15 hp at 200/208 V AC 50/60 Hz for 3 phase motors || 15 hp at 230/240 V AC 50/60 Hz for 3 phase motors || 40 hp at 460/480 V AC 50/60 Hz for 3 phase
- Mounting Support:
- plate || rail
- Depth:
- 120 mm
- Warranty:
- 18 months
- Minimum Switching Current:
- 5 mA for Signaling circuit
- Rohs Exemption Information:
- Yes
- Insulation Resistance:
- > 10 MOhm for Signaling circuit
- Net Weight:
- 0.93 kg
- Mercury Free:
- Yes
- Hold-In Power Consumption In W:
- 7.4-7.4 W 20°C
- Signaling Circuit Frequency:
- 25...400 Hz
- Weight:
- 0.93 kg
- Reach Free Of Svhc:
- Yes
- Protective Cover:
- with
- Average Impedance:
- 1.5 mOhm - Ith 80 A 50 Hz for power circuit
- Time Constant:
- 34 ms
- [Ith] Conventional Free Air Thermal Current:
- 10 A (at 60°C) for Signaling circuit || 80 A (at 60°C) for power circuit
- Non-Overlap Time:
- 1.5 ms on de-energisation between NC and NO contact || 1.5 ms on energisation between NC and NO contact
- Compatibility Code:
- LC1D
- Sustainable Offer Status:
- Green Premium product
- Power Dissipation Per Pole:
- 3.7 W AC-3 || 9.6 W AC-1 || 3.7 W AC-3e
- Flame Retardance:
- V1 conforming to UL 94
- Pole Contact Composition:
- 3 NO
- [Ui] Rated Insulation Voltage:
- power circuit 600 V CSA || power circuit 600 V UL || Signaling circuit 690 V IEC 60947-1 || Signaling circuit 600 V CSA || Signaling circuit 600 V UL || power circuit 690 V IEC 60947-4-1
- Mechanical Robustness:
- vibrations contactor open 2 Gn, 5...300 Hz) || vibrations contactor closed 4 Gn, 5...300 Hz) || shocks contactor closed 15 Gn for 11 ms) || shocks contactor open 10 Gn for 11 ms)
- Reach Regulation:
- Free of Substances of Very High Concern above the threshold
- Weee:
- The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins.
- Safety Reliability Level:
- B10d = 1369863 cycles contactor with nominal load EN/ISO 13849-1 || B10d = 20000000 cycles contactor with mechanical load EN/ISO 13849-1
- Contactor Application:
- resistive load || motor control
- Poles Description:
- 3P
- Overvoltage Category:
- III
- Ip Degree Of Protection:
- IP20 front face IEC 60529
- Tightening Torque:
- control circuit 1.7 N.m EverLink BTR screw connectors flat Ø 6 mm || control circuit 1.7 N.m EverLink BTR screw connectors Philips No 2 || power circuit 8 N.m EverLink BTR screw connectors 25-35 mm² hexagonal 4 mm || power circuit 5 N.m EverLink BT
- Operating Altitude:
- 0...9842.52 ft (0...3000 m)
- Motor Power Kw:
- 15 kW at 220...230 V AC 50/60 Hz (AC-3) || 22 kW at 380...400 V AC 50/60 Hz (AC-3) || 30 kW at 500 V AC 50/60 Hz (AC-3) || 33 kW at 660...690 V AC 50/60 Hz (AC-3) || 25 kW at 415 V AC 50/60 Hz (AC-3) || 30 kW at 440 V AC 50/60 Hz (AC-3) || 11 kW at 4
- Eu Rohs Directive:
- Compliant
- Irms Rated Making Capacity:
- 140 A AC for Signaling circuit conforming to IEC 60947-5-1 || 250 A DC for Signaling circuit conforming to IEC 60947-5-1 || 900 A at 440 V for power circuit conforming to IEC 60947
- Auxiliary Contact Composition:
- 1 NO + 1 NC
- Utilisation Category:
- AC-4 || AC-1 || AC-3 || AC-3e
- [Ue] Rated Operational Voltage:
- power circuit <= 690 V AC 25...400 Hz || power circuit <= 300 V DC
- China Rohs Regulation:
- Pro-active China RoHS declaration (out of China RoHS legal scope)
- [Ie] Rated Operational Current:
- 50 A (at <60°C) at <= 440 V AC AC-3 for power circuit || 80 A (at <60°C) at <= 440 V AC AC-1 for power circuit || 50 A (at <60°C) at <= 440 V AC AC-3e for power circuit
- Minimum Switching Voltage:
- 17 V for Signaling circuit