Schneider Electric

Schneider Electric LC1D50P7 IEC contactor, TeSys D, nonreversing, 50A, 40HP at 480VAC, up to 100kA SCCR, 3 phase, 3 NO, 230VAC 50/60Hz coil, open

(No reviews yet) Write a Review
SKU:
LC1D50P7
MPN:
LC1D50P7
Condition:
New
Reach Free Of Svhc:
Yes
Mounting Support:
plate || rail
Reach Regulation:
Free of Substances of Very High Concern above the threshold
Device Short Name:
LC1D
Depth:
119 mm
[Uimp] Rated Impulse Withstand Voltage:
8 kV IEC 60947
Compatibility Code:
LC1D
Standards:
IEC 60947-5-1 || UL 508 || IEC 60947-4-1 || EN 60947-5-1 || EN 60947-4-1 || CSA C22.2 No 14
Minimum Switching Voltage:
17 V for control circuit
[Uc] Control Circuit Voltage:
230 V AC 50/60 Hz
[Ie] Rated Operational Current:
50 A (at <60°C) at <= 440 V AC AC-3 for power circuit || 80 A (at <60°C) at <= 440 V AC AC-1 for power circuit || 50 A (at <60°C) at <= 440 V AC AC-3e for power circuit
Maximum Horse Power Rating:
3 hp at 115 V AC 60 Hz for 1 phase motors || 7.5 hp at 230/240 V AC 60 Hz for 1 phase motors || 15 hp at 200/208 V AC 60 Hz for 3 phase motors || 15 hp at 230/240 V AC 60 Hz for 3 phase motors || 40 hp at 460/480 V AC 60 Hz for 3 phase motors || 40 h
Safety Reliability Level:
B10d = 1369863 cycles contactor with nominal load EN/ISO 13849-1 || B10d = 20000000 cycles contactor with mechanical load EN/ISO 13849-1
China Rohs Regulation:
Pro-active China RoHS declaration (out of China RoHS legal scope)
Country of Origin:
United States
Operating Altitude:
0...9842.52 ft (0...3000 m)
Hold-In Power Consumption In Va:
13-13 VA 60 Hz cos phi 0.3 (at 20°C) || 15-15 VA 50 Hz cos phi 0.3 (at 20°C)
Control Circuit Voltage Limits:
0.3...0.6 Uc -40-70°C drop-out AC 50/60 Hz || 0.8...1.1 Uc -40-60°C operational AC 50 Hz || 0.85...1.1 Uc -40-60°C operational AC 60 Hz || 1...1.1 Uc 60-70°C operational AC 50/60 Hz
[Ue] Rated Operational Voltage:
power circuit <= 690 V AC 25...400 Hz
Fire Resistance:
850°C IEC 60695-2-1
Net Weight:
1.4 kg
[Ith] Conventional Free Air Thermal Current:
10 A (at 60°C) for control circuit || 80 A (at 60°C) for power circuit
Heat Dissipation:
4-5 W at 50/60 Hz for control circuit
Rohs Exemption Information:
Yes
Climatic Withstand:
IACS E10 exposure to damp heat
Control Circuit Type:
AC 50/60 Hz
Operating Time:
4...19 ms opening || 12...26 ms closing
Weight:
1.4 kg
Non-Overlap Time:
1.5 ms on de-energisation between NC and NO contacts || 1.5 ms on energisation between NC and NO contacts
Range:
TeSys
Motor Power Kw:
22 kW at 380...400 V AC 50 Hz (AC-3) || 25 kW at 415 V AC 50 Hz (AC-3) || 30 kW at 440 V AC 50 Hz (AC-3) || 30 kW at 500 V AC 50 Hz (AC-3) || 33 kW at 660...690 V AC 50 Hz (AC-3) || 15 kW at 220...230 V AC 50 Hz (AC-3) || 11 kW at 400 V AC 50 Hz (AC-
Rated Breaking Capacity:
900 A at 440 V for power circuit conforming to IEC 60947
Contactor Application:
resistive load || motor control
Power Dissipation Per Pole:
3.7 W AC-3 || 9.6 W AC-1 || 3.7 W AC-3e
Range Of Product:
TeSys Deca
Circularity Profile:
N/A
Eu Rohs Directive:
Compliant
Utilisation Category:
AC-1 || AC-2 || AC-4 || AC-3 || AC-3e
Auxiliary Contacts Type:
mechanically linked 1 NO + 1 NC IEC 60947-5-1 || mirror contact 1 NC IEC 60947-4-1
[Ui] Rated Insulation Voltage:
control circuit 600 V CSA || control circuit 600 V UL || power circuit 600 V CSA || power circuit 600 V UL || control circuit 690 V IEC 60947-1 || power circuit 690 V IEC 60947-1
Sustainable Offer Status:
Green Premium product
Connections - Terminals:
control circuit: screw clamp terminals 1 1-4 mm² - cable stiffness: rigid || control circuit: screw clamp terminals 2 1-4 mm² - cable stiffness: rigid || control circuit: screw clamp terminals 1 1-4 mm² - cable stiffness: flexible without cable en
Flame Retardance:
V1 conforming to UL 94
Mercury Free:
Yes
Protective Cover:
with
Product Certifications:
LROS (Lloyds register of shipping) || RINA || UL || BV || GOST || CCC || DNV || GL || CSA || UKCA
Pole Contact Composition:
3 NO
$388.80

Description

TeSys D contactors have been designed for perfect integration into control systems. They can be used to create motor starters for almost any type of application. TeSys D contactors are available in 13 contactor ratings for inductive motor applications up to 150 full-load amps and resistive loads up to 200 amps. This 50A inductive 3 pole IEC contactor can be mounted on DIN rail or mounted directly to a panel. Contactors have both Horsepower and Kw motor rating for international acceptance. Contactor is rated for 15HP at 200 to 208VAC, 15HP at 240VAC, 40HP at 480VAC and 40HP at 600VAC three phase. Contactor is also rated for 3HP at 115VAC and 7.5HP at 240VAC single phase. When used with a 480VAC up to 110A circuit breaker, this contactor can have a SCCR up to 100kA. When used with up to a 600VAC 110A Class J or CC fuse, this contactor can have a SCCR up to 100kA. Contactor is supplied with a 230 VAC 50/60 Hz coil. Contactor has one normally open and one normally closed auxiliary contact built-in as standard. The NC contact is mirror certified. Screw clamp terminals are used for load and auxiliary connections. An extensive line of accessories makes it easy to meet the requirements of most applications. The contactor is 4.80 inches tall, 2.17 inches wide and 4.72 inches deep. It weighs 1.87 lbs. Contactor is certified to UL, CSA, IEC, CCC, EAC and Marine standards. Contactor also meets the requirements of RoHS/REACh making it a Green Premium product.
View AllClose