Schneider Electric LC1D65008B7 IEC contactor, TeSys Deca, nonreversing, 80A resistive, 4 pole, 2 NO and 2 NC, 24VAC 50/60Hz coil, open style
Schneider Electric
$748.80
TeSys D contactors have been designed for perfect integration into control systems. They can be used to create motor starters for almost any type of application. TeSys D contactors are available in 13 contactor ratings for inductive motor applications up to 150 full-load amps and resistive loads up to 200 amps. This 4 pole IEC contactor can be mounted on DIN rail or mounted directly to a panel. Contactor has two normally open and two normally closed power contacts. Power contacts have a 80A resistive load rating. Contactor is supplied with a 24 VAC 50/60 Hz coil. Screw clamp terminals are used for load and auxiliary connections. An extensive line of accessories makes it easy to meet the requirements of most applications. The contactor is 5.00 inches tall, 3.35 inches wide and 4.92 inches deep. It weighs 3.20 lbs. Contactor is certified to UL, CSA, IEC, CCC, EAC and Marine standards. Contactor also meets the requirements of RoHS/REACh making it a Green Premium product.
- Environmental Disclosure:
- ENVPEP110205EN
- Hold-In Power Consumption In Va:
- 13-13 VA 60 Hz cos phi 0.3 (at 20°C) || 15-15 VA 50 Hz cos phi 0.3 (at 20°C)
- China Rohs Regulation:
- Pro-active China RoHS declaration (out of China RoHS legal scope)
- [Uimp] Rated Impulse Withstand Voltage:
- 6 kV IEC 60947
- Mercury Free:
- Yes
- Maximum Operating Rate:
- 3600 cyc/h 60°C
- Width:
- 85 mm
- Inrush Power In Va:
- 140-140 VA 60 Hz cos phi 0.75 (at 20°C) || 160-160 VA 50 Hz cos phi 0.75 (at 20°C)
- Electrical Durability:
- 1.4 Mcycles 80 A AC-1 <= 440 V
- Compatibility Code:
- LC1D
- Height:
- 127 mm
- Coil Technology:
- without built-in suppressor module
- Utilisation Category:
- AC-1
- Net Weight:
- 1.45 kg
- Associated Fuse Rating:
- 125 A gG at <= 690 V coordination type 1 for power circuit || 125 A gG at <= 690 V coordination type 2 for power circuit
- Mechanical Durability:
- 6 Mcycles
- Weee:
- The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins.
- Contactor Application:
- resistive load
- Average Impedance:
- 1.5 mOhm - Ith 80 A 50 Hz for power circuit
- [Uc] Control Circuit Voltage:
- 24 V AC 50/60 Hz
- Power Dissipation Per Pole:
- 9.6 W AC-1
- Poles Description:
- 4P
- Circularity Profile:
- N/A
- Connections - Terminals:
- control circuit: screw clamp terminals 2 1-2.5 mm² - cable stiffness: flexible with cable end || control circuit: screw clamp terminals 1 1-4 mm² - cable stiffness: flexible without cable end || control circuit: screw clamp terminals 2 1-4 mm² - c
- Operating Altitude:
- 0...9842.52 ft (0...3000 m)
- Safety Reliability Level:
- B10d = 1369863 cycles contactor with nominal load EN/ISO 13849-1 || B10d = 20000000 cycles contactor with mechanical load EN/ISO 13849-1
- Tightening Torque:
- control circuit 1.7 N.m screw clamp terminals flat Ø 6 mm || control circuit 1.7 N.m screw clamp terminals Philips No 2 || power circuit 8 N.m screw clamp terminals 25-35 mm² hexagonal 4 mm || power circuit 5 N.m screw clamp terminals 1-25 mm² hex
- Country of Origin:
- Czechia
- Reach Free Of Svhc:
- Yes
- Device Short Name:
- LC1D
- Depth:
- 125 mm
- Product Or Component Type:
- contactor
- Pole Contact Composition:
- 2 NO + 2 NC
- Ip Degree Of Protection:
- IP20 front face IEC 60529
- Warranty:
- 18 months
- Climatic Withstand:
- IACS E10 exposure to damp heat
- Operating Time:
- 4...19 ms opening || 12...26 ms closing
- Product Certifications:
- CSA || GL || UL || BV || CCC || DNV || LROS (Lloyds register of shipping) || GOST || RINA
- Weight:
- 1.45 kg
- Pollution Degree:
- 3
- Rated Breaking Capacity:
- 1000 A at 440 V for power circuit conforming to IEC 60947
- Irms Rated Making Capacity:
- 1000 A at 440 V for power circuit conforming to IEC 60947
- Protective Cover:
- without
- Control Circuit Type:
- AC 50/60 Hz
- [Ue] Rated Operational Voltage:
- power circuit <= 690 V AC 25...400 Hz || power circuit <= 300 V DC
- Reach Regulation:
- Free of Substances of Very High Concern above the threshold
- Standards:
- CSA C22.2 No 14 || EN 60947-4-1 || EN 60947-5-1 || IEC 60947-4-1 || IEC 60947-5-1 || UL 508
- [Ith] Conventional Free Air Thermal Current:
- 80 A (at 60°C) for power circuit
- Flame Retardance:
- V1 conforming to UL 94