Schneider Electric LC1D65008E7 IEC contactor, TeSys Deca, nonreversing, 80A resistive, 4 pole, 2 NO and 2 NC, 48VAC 50/60Hz coil, open style
Schneider Electric
$748.80
TeSys D contactors have been designed for perfect integration into control systems. They can be used to create motor starters for almost any type of application. TeSys D contactors are available in 13 contactor ratings for inductive motor applications up to 150 full-load amps and resistive loads up to 200 amps. This 4 pole IEC contactor can be mounted on DIN rail or mounted directly to a panel. Contactor has two normally open and two normally closed power contacts. Power contacts have a 80A resistive load rating. Contactor is supplied with a 48 VAC 50/60 Hz coil. Screw clamp terminals are used for load and auxiliary connections. An extensive line of accessories makes it easy to meet the requirements of most applications. The contactor is 5.00 inches tall, 3.35 inches wide and 4.92 inches deep. It weighs 3.20 lbs. Contactor is certified to UL, CSA, IEC, CCC, EAC and Marine standards. Contactor also meets the requirements of RoHS/REACh making it a Green Premium product.
- Control Circuit Voltage Limits:
- 0.3...0.6 Uc -40-70°C drop-out AC 50/60 Hz || 0.8...1.1 Uc -40-60°C operational AC 50 Hz || 0.85...1.1 Uc -40-60°C operational AC 60 Hz || 1...1.1 Uc 60-70°C operational AC 50/60 Hz
- Mechanical Robustness:
- shocks contactor open 8 Gn for 11 ms) || shocks contactor closed 10 Gn for 11 ms) || vibrations contactor opened 2 Gn, 5...300 Hz) || vibrations contactor closed 3 Gn, 5...300 Hz)
- Mounting Support:
- plate || rail
- Mercury Free:
- Yes
- Safety Reliability Level:
- B10d = 1369863 cycles contactor with nominal load EN/ISO 13849-1 || B10d = 20000000 cycles contactor with mechanical load EN/ISO 13849-1
- Maximum Operating Rate:
- 3600 cyc/h 60°C
- Standards:
- CSA C22.2 No 14 || EN 60947-4-1 || EN 60947-5-1 || IEC 60947-4-1 || IEC 60947-5-1 || UL 508
- Country of Origin:
- Czechia
- Environmental Disclosure:
- ENVPEP110205EN
- Sustainable Offer Status:
- Green Premium product
- [Uimp] Rated Impulse Withstand Voltage:
- 6 kV IEC 60947
- Range:
- TeSys
- Control Circuit Type:
- AC 50/60 Hz
- Protective Treatment:
- THIEC 60068-2-30
- Pollution Degree:
- 3
- Inrush Power In Va:
- 140-140 VA 60 Hz cos phi 0.75 (at 20°C) || 160-160 VA 50 Hz cos phi 0.75 (at 20°C)
- Product Or Component Type:
- contactor
- Compatibility Code:
- LC1D
- Protective Cover:
- without
- Hold-In Power Consumption In Va:
- 13-13 VA 60 Hz cos phi 0.3 (at 20°C) || 15-15 VA 50 Hz cos phi 0.3 (at 20°C)
- Reach Free Of Svhc:
- Yes
- Device Short Name:
- LC1D
- [Ue] Rated Operational Voltage:
- power circuit <= 1000 V AC 25...400 Hz || 0...5.115 V
- Net Weight:
- 1.45 kg
- Poles Description:
- 4P
- Product Certifications:
- GL || BV || UL || DNV || LROS (Lloyds register of shipping) || CCC || CSA || RINA || GOST
- Pvc Free:
- Yes
- Height:
- 127 mm
- Permissible Ambient Air Temperature Around The Device:
- -40-60°C || 60-70°C with derating
- Irms Rated Making Capacity:
- 1000 A at 440 V for power circuit conforming to IEC 60947
- Tightening Torque:
- control circuit 1.7 N.m screw clamp terminals flat Ø 6 mm || control circuit 1.7 N.m screw clamp terminals Philips No 2 || power circuit 8 N.m screw clamp terminals 25-35 mm² hexagonal 4 mm || power circuit 5 N.m screw clamp terminals 1-25 mm² hex
- Power Dissipation Per Pole:
- 9.6 W AC-1
- Operating Altitude:
- 0...9842.52 ft (0...3000 m)
- Rated Breaking Capacity:
- 1000 A at 440 V for power circuit conforming to IEC 60947
- Eu Rohs Directive:
- Compliant
- Depth:
- 125 mm
- Fire Resistance:
- 850°C IEC 60695-2-1
- Heat Dissipation:
- 4-5 W at 50/60 Hz
- Associated Fuse Rating:
- 125 A gG at <= 690 V coordination type 1 for power circuit || 125 A gG at <= 690 V coordination type 2 for power circuit
- Electrical Durability:
- 1.4 Mcycles 80 A AC-1 <= 440 V
- Circularity Profile:
- N/A
- Rohs Exemption Information:
- Yes
- [Ith] Conventional Free Air Thermal Current:
- 80 A (at 60°C) for power circuit
- Climatic Withstand:
- IACS E10 exposure to damp heat
- [Ui] Rated Insulation Voltage:
- power circuit 600 V CSA || power circuit 600 V UL || power circuit 690 V IEC 60947-4-1
- Toxic Heavy Metal Free:
- Yes
- [Ie] Rated Operational Current:
- 80 A (at <60°C) at <= 440 V AC AC-1 for power circuit
- Width:
- 85 mm
- China Rohs Regulation:
- Pro-active China RoHS declaration (out of China RoHS legal scope)