Schneider Electric LC1D65008G6 IEC contactor, TeSys Deca, nonreversing, 80A resistive, 4 pole, 2 NO and 2 NC, 120VAC 60Hz coil, open style
Schneider Electric
$748.80
TeSys D contactors have been designed for perfect integration into control systems. They can be used to create motor starters for almost any type of application. TeSys D contactors are available in 13 contactor ratings for inductive motor applications up to 150 full-load amps and resistive loads up to 200 amps. This 4 pole IEC contactor can be mounted on DIN rail or mounted directly to a panel. Contactor has two normally open and two normally closed power contacts. Power contacts have a 80A resistive load rating. Contactor is supplied with a 120 VAC 60 Hz coil. Screw clamp terminals are used for load and auxiliary connections. An extensive line of accessories makes it easy to meet the requirements of most applications. The contactor is 5.00 inches tall, 3.35 inches wide and 4.92 inches deep. It weighs 3.20 lbs. Contactor is certified to UL, CSA, IEC, CCC, EAC and Marine standards. Contactor also meets the requirements of RoHS/REACh making it a Green Premium product.
- Toxic Heavy Metal Free:
- Yes
- Mounting Support:
- rail || plate
- Coil Technology:
- without built-in suppressor module
- Pollution Degree:
- 3
- Utilisation Category:
- AC-1
- [Ui] Rated Insulation Voltage:
- power circuit 600 V CSA || power circuit 600 V UL || power circuit 690 V IEC 60947-4-1
- Associated Fuse Rating:
- 125 A gG at <= 690 V coordination type 1 for power circuit || 125 A gG at <= 690 V coordination type 2 for power circuit
- Electrical Durability:
- 1.4 Mcycles 80 A AC-1 <= 440 V
- Depth:
- 125 mm
- Rohs Exemption Information:
- Yes
- Mechanical Robustness:
- shocks contactor open 8 Gn for 11 ms) || shocks contactor closed 10 Gn for 11 ms) || vibrations contactor opened 2 Gn, 5...300 Hz) || vibrations contactor closed 3 Gn, 5...300 Hz)
- Heat Dissipation:
- 4-5 W at 60 Hz
- Pole Contact Composition:
- 2 NO + 2 NC
- Rated Breaking Capacity:
- 1000 A at 440 V for power circuit conforming to IEC 60947
- Net Weight:
- 1.45 kg
- Mechanical Durability:
- 6 Mcycles
- Poles Description:
- 4P
- Operating Time:
- 4...19 ms opening || 12...26 ms closing
- [Uimp] Rated Impulse Withstand Voltage:
- 6 kV IEC 60947
- Flame Retardance:
- V1 conforming to UL 94
- Pvc Free:
- Yes
- Maximum Operating Rate:
- 3600 cyc/h 60°C
- Warranty:
- 18 months
- Eu Rohs Directive:
- Compliant
- Contactor Application:
- resistive load
- Country of Origin:
- Czechia
- Irms Rated Making Capacity:
- 1000 A at 440 V for power circuit conforming to IEC 60947
- [Uc] Control Circuit Voltage:
- 120 V AC 60 Hz
- Inrush Power In Va:
- 140-140 VA 60 Hz cos phi 0.75 (at 20°C)
- Hold-In Power Consumption In Va:
- 13-13 VA 60 Hz cos phi 0.3 (at 20°C)
- Tightening Torque:
- control circuit 1.7 N.m screw clamp terminals flat Ø 6 mm || control circuit 1.7 N.m screw clamp terminals Philips No 2 || power circuit 8 N.m screw clamp terminals 25-35 mm² hexagonal 4 mm || power circuit 5 N.m screw clamp terminals 1-25 mm² hex
- Weee:
- The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins.
- Control Circuit Voltage Limits:
- 0.85...1.1 Uc -40-60°C operational AC 60 Hz || 0.3...0.6 Uc -40-70°C drop-out AC 60 Hz || 1...1.1 Uc 60-70°C operational AC 60 Hz
- Protective Treatment:
- THIEC 60068-2-30
- Environmental Disclosure:
- ENVPEP110205EN
- [Ue] Rated Operational Voltage:
- power circuit <= 690 V AC 25...400 Hz || power circuit <= 300 V DC
- Range:
- TeSys
- Height:
- 127 mm
- Product Or Component Type:
- contactor
- [Ith] Conventional Free Air Thermal Current:
- 80 A (at 60°C) for power circuit
- Control Circuit Type:
- AC 60 Hz
- [Icw] Rated Short-Time Withstand Current:
- 520 A 40°C - 10 s for power circuit || 900 A 40°C - 1 s for power circuit || 110 A 40°C - 10 min for power circuit || 260 A 40°C - 1 min for power circuit
- Power Dissipation Per Pole:
- 9.6 W AC-1
- Overvoltage Category:
- III
- Standards:
- CSA C22.2 No 14 || EN 60947-4-1 || EN 60947-5-1 || IEC 60947-4-1 || IEC 60947-5-1 || UL 508
- Reach Free Of Svhc:
- Yes
- Safety Reliability Level:
- B10d = 1369863 cycles contactor with nominal load EN/ISO 13849-1 || B10d = 20000000 cycles contactor with mechanical load EN/ISO 13849-1