Schneider Electric

Schneider Electric LC1D65A6BD IEC contactor, TeSys Deca, nonreversing, 65A, 40HP at 480VAC, 3 phase, 3 pole, 3 NO, 24VDC coil, open style

(No reviews yet) Write a Review
SKU:
LC1D65A6BD
MPN:
LC1D65A6BD
Condition:
New
Insulation Resistance:
> 10 MOhm for Signaling circuit
Electrical Durability:
0.5 Mcycles 80 A AC-1 <= 440 V || 1.45 Mcycles 65 A AC-3 <= 440 V || 1.45 Mcycles 65 A AC-3e <= 440 V
Weee:
The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins.
[Uc] Control Circuit Voltage:
24 V DC
Compatibility Code:
LC1D
Utilisation Category:
AC-4 || AC-1 || AC-3 || AC-3e
Circularity Profile:
ENVEOLI1503009EN
Maximum Horse Power Rating:
40 hp at 460/480 V AC 50/60 Hz for 3 phase motors || 5 hp at 115 V AC 50/60 Hz for 1 phase motors || 10 hp at 230/240 V AC 50/60 Hz for 1 phase motors || 20 hp at 200/208 V AC 50/60 Hz for 3 phase motors || 20 hp at 230/240 V AC 50/60 Hz for 3 phase
Permissible Ambient Air Temperature Around The Device:
-40-60°C || 60-70°C with derating
Contactor Application:
resistive load || motor control
Product Or Component Type:
contactor
Product Certifications:
CCC || UL || CB Scheme || CSA || CE || UKCA || Marine || EAC
China Rohs Regulation:
Pro-active China RoHS declaration (out of China RoHS legal scope)
Non-Overlap Time:
1.5 ms on de-energisation between NC and NO contact || 1.5 ms on energisation between NC and NO contact
Signaling Circuit Frequency:
25...400 Hz
Pvc Free:
Yes
Environmental Disclosure:
ENVPEP1503009EN
Tightening Torque:
control circuit 1.7 N.m EverLink BTR screw connectors flat Ø 6 mm M3.5 || control circuit 1.7 N.m EverLink BTR screw connectors Philips No 2 M3.5 || power circuit 6 N.m EverLink BTR screw connectors hexagonal 10 mm M6 || control circuit 1.7 N.m Ever
Sustainable Offer Status:
Green Premium product
Hold-In Power Consumption In W:
7.4-7.4 W 20°C
Width:
55 mm
Fire Resistance:
850°C IEC 60695-2-1
[Icw] Rated Short-Time Withstand Current:
640 A 40°C - 10 s for power circuit || 900 A 40°C - 1 s for power circuit || 110 A 40°C - 10 min for power circuit || 260 A 40°C - 1 min for power circuit || 100 A - 1 s for Signaling circuit || 120 A - 500 ms for Signaling circuit || 140 A - 100 ms
Control Circuit Type:
DC standard
Associated Fuse Rating:
10 A gG for Signaling circuit conforming to IEC 60947-5-1 || 125 A gG at <= 690 V coordination type 1 for power circuit || 125 A gG at <= 690 V coordination type 2 for power circuit
[Ui] Rated Insulation Voltage:
power circuit 600 V CSA || power circuit 600 V UL || Signaling circuit 690 V IEC 60947-1 || Signaling circuit 600 V CSA || Signaling circuit 600 V UL || power circuit 690 V IEC 60947-4-1
Weight:
0.935 kg
Inrush Power In W:
19-19 W 20°C)
Overvoltage Category:
III
Minimum Switching Current:
5 mA for Signaling circuit
Net Weight:
0.935 kg
[Ith] Conventional Free Air Thermal Current:
10 A (at 60°C) for Signaling circuit || 80 A (at 60°C) for power circuit
Depth:
120 mm
Eu Rohs Directive:
Compliant
Poles Description:
3P
Auxiliary Contact Composition:
1 NO + 1 NC
Height:
122 mm
Pole Contact Composition:
3 NO
Coil Technology:
built-in bidirectional peak limiting diode suppressor
Mechanical Durability:
10 Mcycles
Range Of Product:
TeSys Deca
Average Impedance:
1.5 mOhm - Ith 80 A 50 Hz for power circuit
Mounting Support:
rail || plate
Operating Time:
50±15 % ms closing || 16...24 ms opening
Climatic Withstand:
IACS E10 exposure to damp heat || IEC 60947-1 Annex Q category D exposure to damp heat
Operating Altitude:
0...9842.52 ft (0...3000 m)
Time Constant:
34 ms
Auxiliary Contacts Type:
mechanically linked 1 NO + 1 NC IEC 60947-5-1 || mirror contact 1 NC IEC 60947-4-1
Safety Reliability Level:
B10d = 1369863 cycles contactor with nominal load EN/ISO 13849-1 || B10d = 20000000 cycles contactor with mechanical load EN/ISO 13849-1
$403.00

Description

TeSys D contactors have been designed for perfect integration into control systems. They can be used to create motor starters for almost any type of application. TeSys D contactors are available in 13 contactor ratings for inductive motor applications up to 150 full-load amps and resistive loads up to 200 amps. This 65A inductive 3 pole IEC contactor can be mounted on DIN rail or mounted directly to a panel. Contactors have both Horsepower and Kw motor rating for international acceptance. Contactor is rated for 20HP at 200 to 208VAC, 20HP at 240VAC, 40HP at 480VAC and 50HP at 600VAC three phase. Contactor is also rated for 5HP at 115VAC and 10HP at 240VAC single phase. Contactor is supplied with a 24 VDC coil with transient suppressor module. Contactor has one normally open and one normally closed auxiliary contact built-in as standard. The NC contact is mirror certified. Ring-lug screw terminals are used for load and auxiliary connections. An extensive line of accessories makes it easy to meet the requirements of most applications. The contactor is 4.80 inches tall, 2.17 inches wide and 4.72 inches deep. It weighs 1.90 lbs. Contactor is certified to UL, CSA, IEC, CCC, EAC and Marine standards. Contactor also meets the requirements of RoHS/REACh making it a Green Premium product.
View AllClose