Schneider Electric

Schneider Electric LC1D65A6G7 IEC contactor, TeSys Deca, nonreversing, 65A, 40HP at 480VAC, 3 phase, 3 pole, 3 NO, 120VAC 50/60Hz coil, open style

(No reviews yet) Write a Review
SKU:
LC1D65A6G7
MPN:
LC1D65A6G7
Condition:
New
Auxiliary Contacts Type:
mechanically linked 1 NO + 1 NC IEC 60947-5-1 || mirror contact 1 NC IEC 60947-4-1
Poles Description:
3P
Circularity Profile:
ENVEOLI1503009EN
[Ith] Conventional Free Air Thermal Current:
10 A (at 60°C) for Signaling circuit || 80 A (at 60°C) for power circuit
Pollution Degree:
3
Utilisation Category:
AC-4 || AC-1 || AC-3 || AC-3e
Permissible Ambient Air Temperature Around The Device:
-40-60°C || 60-70°C with derating
Maximum Operating Rate:
3600 cyc/h 60°C
China Rohs Regulation:
Pro-active China RoHS declaration (out of China RoHS legal scope)
Heat Dissipation:
4-5 W at 60 Hz
Average Impedance:
1.5 mOhm - Ith 80 A 50 Hz for power circuit
Contactor Application:
motor control || resistive load
Fire Resistance:
850°C IEC 60695-2-1
Rohs Exemption Information:
Yes
Auxiliary Contact Composition:
1 NO + 1 NC
Net Weight:
0.86 kg
Electrical Durability:
1.4 Mcycles 80 A AC-1 <= 440 V || 1.45 Mcycles 65 A AC-3 <= 440 V || 1.45 Mcycles 65 A AC-3e <= 440 V
[Uc] Control Circuit Voltage:
120 V AC 60 Hz
Protective Treatment:
THIEC 60068-2-30
Tightening Torque:
control circuit 1.7 N.m EverLink BTR screw connectors flat Ø 6 mm M3.5 || control circuit 1.7 N.m EverLink BTR screw connectors Philips No 2 M3.5 || power circuit 6 N.m EverLink BTR screw connectors hexagonal 10 mm M6 || control circuit 1.7 N.m Ever
[Ie] Rated Operational Current:
80 A (at <60°C) at <= 440 V AC AC-1 for power circuit || 65 A (at <60°C) at <= 440 V AC AC-3 for power circuit || 65 A (at <60°C) at <= 440 V AC AC-3e for power circuit
Mechanical Robustness:
vibrations contactor open 2 Gn, 5...300 Hz) || vibrations contactor closed 4 Gn, 5...300 Hz) || shocks contactor closed 15 Gn for 11 ms) || shocks contactor open 10 Gn for 11 ms)
Toxic Heavy Metal Free:
Yes
Climatic Withstand:
IACS E10 exposure to damp heat || IEC 60947-1 Annex Q category D exposure to damp heat
Safety Reliability Level:
B10d = 1369863 cycles contactor with nominal load EN/ISO 13849-1 || B10d = 20000000 cycles contactor with mechanical load EN/ISO 13849-1
Environmental Disclosure:
ENVPEP1503009EN
Irms Rated Making Capacity:
140 A AC for Signaling circuit conforming to IEC 60947-5-1 || 250 A DC for Signaling circuit conforming to IEC 60947-5-1 || 1000 A at 440 V for power circuit conforming to IEC 60947
Operating Time:
4...19 ms opening || 12...26 ms closing
Ip Degree Of Protection:
IP20 front face IEC 60529
Weight:
0.86 kg
Rated Breaking Capacity:
1000 A at 440 V for power circuit conforming to IEC 60947
Width:
55 mm
Minimum Switching Current:
5 mA for Signaling circuit
Height:
122 mm
Non-Overlap Time:
1.5 ms on de-energisation between NC and NO contact || 1.5 ms on energisation between NC and NO contact
Operating Altitude:
0...9842.52 ft (0...3000 m)
Range:
TeSys || TeSys Deca
Eu Rohs Directive:
Compliant
Pvc Free:
Yes
Hold-In Power Consumption In Va:
13-13 VA 60 Hz cos phi 0.3 (at 20°C)
Flame Retardance:
V1 conforming to UL 94
[Ui] Rated Insulation Voltage:
power circuit 600 V CSA || power circuit 600 V UL || Signaling circuit 690 V IEC 60947-1 || Signaling circuit 600 V CSA || Signaling circuit 600 V UL || power circuit 690 V IEC 60947-4-1
Mounting Support:
rail || plate
Connections - Terminals:
control circuit: lugs-ring terminals - external diameter: 8 mm || power circuit: lugs-ring terminals - external diameter: 16.5 mm
Depth:
120 mm
Inrush Power In Va:
140-140 VA 60 Hz cos phi 0.75 (at 20°C)
Warranty:
18 months
Sustainable Offer Status:
Green Premium product
Protective Cover:
with
$386.40

Description

TeSys D contactors have been designed for perfect integration into control systems. They can be used to create motor starters for almost any type of application. TeSys D contactors are available in 13 contactor ratings for inductive motor applications up to 150 full-load amps and resistive loads up to 200 amps. This 65A inductive 3 pole IEC contactor can be mounted on DIN rail or mounted directly to a panel. Contactors have both Horsepower and Kw motor rating for international acceptance. Contactor is rated for 20HP at 200 to 208VAC, 20HP at 240VAC, 40HP at 480VAC and 50HP at 600VAC three phase. Contactor is also rated for 5HP at 115VAC and 10HP at 240VAC single phase. Contactor is supplied with a 120 VAC 60 Hz coil. Contactor has one normally open and one normally closed auxiliary contact built-in as standard. The NC contact is mirror certified. Ring-lug screw terminals are used for load and auxiliary connections. An extensive line of accessories makes it easy to meet the requirements of most applications. The contactor is 4.80 inches tall, 2.17 inches wide and 4.72 inches deep. It weighs 1.90 lbs. Contactor is certified to UL, CSA, IEC, CCC, EAC and Marine standards. Contactor also meets the requirements of RoHS/REACh making it a Green Premium product.