Tightening Torque:
control circuit 1.7 N.m EverLink BTR screw connectors flat Ø 6 mm M3.5 || control circuit 1.7 N.m EverLink BTR screw connectors Philips No 2 M3.5 || power circuit 6 N.m EverLink BTR screw connectors hexagonal 10 mm M6 || control circuit 1.7 N.m Ever
Signaling Circuit Frequency:
25...400 Hz
Range:
TeSys || TeSys Deca
Connections - Terminals:
control circuit: lugs-ring terminals - external diameter: 8 mm || power circuit: lugs-ring terminals - external diameter: 16.5 mm
Operating Time:
4...19 ms opening || 12...26 ms closing
Product Certifications:
CCC || UL || CB Scheme || CSA || CE || UKCA || Marine || EAC
Hold-In Power Consumption In Va:
13-13 VA 60 Hz cos phi 0.3 (at 20°C) || 15-15 VA 50 Hz cos phi 0.3 (at 20°C)
Environmental Disclosure:
ENVPEP1503009EN
Auxiliary Contact Composition:
1 NO + 1 NC
Pollution Degree:
3
Maximum Operating Rate:
3600 cyc/h 60°C
Weee:
The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins.
Product Or Component Type:
contactor
Fire Resistance:
850°C IEC 60695-2-1
Minimum Switching Voltage:
17 V for Signaling circuit
Non-Overlap Time:
1.5 ms on de-energisation between NC and NO contact || 1.5 ms on energisation between NC and NO contact
Minimum Switching Current:
5 mA for Signaling circuit
Mechanical Robustness:
vibrations contactor open 2 Gn, 5...300 Hz) || vibrations contactor closed 4 Gn, 5...300 Hz) || shocks contactor closed 15 Gn for 11 ms) || shocks contactor open 10 Gn for 11 ms)
Protective Treatment:
THIEC 60068-2-30
Sustainable Offer Status:
Green Premium product
Net Weight:
0.86 kg
Toxic Heavy Metal Free:
Yes
Power Dissipation Per Pole:
9.6 W AC-1 || 6.3 W AC-3 || 6.3 W AC-3e
Rohs Exemption Information:
Yes
Circularity Profile:
ENVEOLI1503009EN
Mercury Free:
Yes
Depth:
120 mm
Maximum Horse Power Rating:
40 hp at 460/480 V AC 50/60 Hz for 3 phase motors || 5 hp at 115 V AC 50/60 Hz for 1 phase motors || 10 hp at 230/240 V AC 50/60 Hz for 1 phase motors || 20 hp at 200/208 V AC 50/60 Hz for 3 phase motors || 20 hp at 230/240 V AC 50/60 Hz for 3 phase
Pvc Free:
Yes
Eu Rohs Directive:
Compliant
Rated Breaking Capacity:
1000 A at 440 V for power circuit conforming to IEC 60947
Associated Fuse Rating:
10 A gG for Signaling circuit conforming to IEC 60947-5-1 || 125 A gG at <= 690 V coordination type 1 for power circuit || 125 A gG at <= 690 V coordination type 2 for power circuit
[Ue] Rated Operational Voltage:
power circuit <= 690 V AC 25...400 Hz || power circuit <= 300 V DC
Poles Description:
3P
Pole Contact Composition:
3 NO
[Ie] Rated Operational Current:
80 A (at <60°C) at <= 440 V AC AC-1 for power circuit || 65 A (at <60°C) at <= 440 V AC AC-3 for power circuit || 65 A (at <60°C) at <= 440 V AC AC-3e for power circuit
Average Impedance:
1.5 mOhm - Ith 80 A 50 Hz for power circuit
Weight:
0.86 kg
Reach Free Of Svhc:
Yes
[Uc] Control Circuit Voltage:
100 V AC 50/60 Hz
Warranty:
18 months
Control Circuit Type:
AC 50/60 Hz
Heat Dissipation:
4-5 W at 50/60 Hz
Protective Cover:
with
Ip Degree Of Protection:
IP20 front face IEC 60529
Insulation Resistance:
> 10 MOhm for Signaling circuit
Flame Retardance:
V1 conforming to UL 94
[Ith] Conventional Free Air Thermal Current:
10 A (at 60°C) for Signaling circuit || 80 A (at 60°C) for power circuit
$483.00

Description

TeSys D contactors have been designed for perfect integration into control systems. They can be used to create motor starters for almost any type of application. TeSys D contactors are available in 13 contactor ratings for inductive motor applications up to 150 full-load amps and resistive loads up to 200 amps. This 65A inductive 3 pole IEC contactor can be mounted on DIN rail or mounted directly to a panel. Contactors have both Horsepower and Kw motor rating for international acceptance. Contactor is rated for 20HP at 200 to 208VAC, 20HP at 240VAC, 40HP at 480VAC and 50HP at 600VAC three phase. Contactor is also rated for 5HP at 115VAC and 10HP at 240VAC single phase. Contactor is supplied with a 100 VAC 50/60 Hz coil. Contactor has one normally open and one normally closed auxiliary contact built-in as standard. The NC contact is mirror certified. Ring-lug screw terminals are used for load and auxiliary connections. An extensive line of accessories makes it easy to meet the requirements of most applications. The contactor is 4.80 inches tall, 2.17 inches wide and 4.72 inches deep. It weighs 1.90 lbs. Contactor is certified to UL, CSA, IEC, CCC, EAC and Marine standards. Contactor also meets the requirements of RoHS/REACh making it a Green Premium product.