Schneider Electric

Schneider Electric LC1D65A6MD IEC contactor, TeSys Deca, nonreversing, 65A, 40HP at 480VAC, 3 phase, 3 pole, 3 NO, 220VDC coil, open style

(No reviews yet) Write a Review
SKU:
LC1D65A6MD
MPN:
LC1D65A6MD
Condition:
New
Fire Resistance:
850°C IEC 60695-2-1
Range:
TeSys || TeSys Deca
Auxiliary Contacts Type:
mechanically linked 1 NO + 1 NC IEC 60947-5-1 || mirror contact 1 NC IEC 60947-4-1
[Ie] Rated Operational Current:
80 A (at <60°C) at <= 440 V AC AC-1 for power circuit || 65 A (at <60°C) at <= 440 V AC AC-3 for power circuit || 65 A (at <60°C) at <= 440 V AC AC-3e for power circuit
Insulation Resistance:
> 10 MOhm for Signaling circuit
Compatibility Code:
LC1D
Time Constant:
34 ms
Permissible Ambient Air Temperature Around The Device:
-40-60°C || 60-70°C with derating
Auxiliary Contact Composition:
1 NO + 1 NC
Overvoltage Category:
III
[Icw] Rated Short-Time Withstand Current:
640 A 40°C - 10 s for power circuit || 900 A 40°C - 1 s for power circuit || 110 A 40°C - 10 min for power circuit || 260 A 40°C - 1 min for power circuit || 100 A - 1 s for Signaling circuit || 120 A - 500 ms for Signaling circuit || 140 A - 100 ms
Mercury Free:
Yes
Operating Altitude:
0...9842.52 ft (0...3000 m)
Average Impedance:
1.5 mOhm - Ith 80 A 50 Hz for power circuit
Control Circuit Voltage Limits:
0.1...0.3 Uc -40-70°C drop-out DC || 0.75...1.25 Uc -40-60°C operational DC || 1...1.25 Uc 60-70°C operational DC
Reach Free Of Svhc:
Yes
Hold-In Power Consumption In W:
7.4-7.4 W 20°C
Mechanical Robustness:
vibrations contactor open 2 Gn, 5...300 Hz) || vibrations contactor closed 4 Gn, 5...300 Hz) || shocks contactor closed 15 Gn for 11 ms) || shocks contactor open 10 Gn for 11 ms)
Environmental Disclosure:
ENVPEP1503009EN
[Ith] Conventional Free Air Thermal Current:
10 A (at 60°C) for Signaling circuit || 80 A (at 60°C) for power circuit
[Ue] Rated Operational Voltage:
power circuit <= 690 V AC 25...400 Hz || power circuit <= 300 V DC
Pvc Free:
Yes
Non-Overlap Time:
1.5 ms on de-energisation between NC and NO contact || 1.5 ms on energisation between NC and NO contact
Sustainable Packaging:
Yes
Signaling Circuit Frequency:
25...400 Hz
Minimum Switching Voltage:
17 V for Signaling circuit
Reach Regulation:
Free of Substances of Very High Concern above the threshold
China Rohs Regulation:
Pro-active China RoHS declaration (out of China RoHS legal scope)
[Uimp] Rated Impulse Withstand Voltage:
6 kV IEC 60947
Electrical Durability:
0.5 Mcycles 80 A AC-1 <= 440 V || 1.45 Mcycles 65 A AC-3 <= 440 V || 1.45 Mcycles 65 A AC-3e <= 440 V
Protective Cover:
with
Product Or Component Type:
contactor
Associated Fuse Rating:
10 A gG for Signaling circuit conforming to IEC 60947-5-1 || 125 A gG at <= 690 V coordination type 1 for power circuit || 125 A gG at <= 690 V coordination type 2 for power circuit
Country of Origin:
France
Standards:
EN 60947-4-1 || EN 60947-5-1 || IEC 60947-4-1 || IEC 60947-5-1 || CSA C22.2 No 14 || UL 60947-4-1 || IEC 60335-2-40:Annex JJ || UL 60335-2-40:Annex JJ || IEC 60335-1:Clause 30.2
Sustainable Offer Status:
Green Premium product
Mechanical Durability:
10 Mcycles
Safety Reliability Level:
B10d = 1369863 cycles contactor with nominal load EN/ISO 13849-1 || B10d = 20000000 cycles contactor with mechanical load EN/ISO 13849-1
Width:
55 mm
Protective Treatment:
THIEC 60068-2-30
Depth:
120 mm
Device Short Name:
LC1D
Pole Contact Composition:
3 NO
Control Circuit Type:
DC standard
Weight:
0.935 kg
Contactor Application:
motor control || resistive load
Warranty:
18 months
Range Of Product:
TeSys Deca
Height:
122 mm
$403.00

Description

TeSys D contactors have been designed for perfect integration into control systems. They can be used to create motor starters for almost any type of application. TeSys D contactors are available in 13 contactor ratings for inductive motor applications up to 150 full-load amps and resistive loads up to 200 amps. This 65A inductive 3 pole IEC contactor can be mounted on DIN rail or mounted directly to a panel. Contactors have both Horsepower and Kw motor rating for international acceptance. Contactor is rated for 20HP at 200 to 208VAC, 20HP at 240VAC, 40HP at 480VAC and 50HP at 600VAC three phase. Contactor is also rated for 5HP at 115VAC and 10HP at 240VAC single phase. Contactor is supplied with a 220 VDC coil with transient suppressor module. Contactor has one normally open and one normally closed auxiliary contact built-in as standard. The NC contact is mirror certified. Ring-lug screw terminals are used for load and auxiliary connections. An extensive line of accessories makes it easy to meet the requirements of most applications. The contactor is 4.80 inches tall, 2.17 inches wide and 4.72 inches deep. It weighs 1.90 lbs. Contactor is certified to UL, CSA, IEC, CCC, EAC and Marine standards. Contactor also meets the requirements of RoHS/REACh making it a Green Premium product.
View AllClose