TeSys D contactors have been designed for perfect integration into control systems. They can be used to create motor starters for almost any type of application. TeSys D contactors are available in 13 contactor ratings for inductive motor applications up to 150 full-load amps and resistive loads up to 200 amps. This 65A inductive 3 pole IEC contactor can be mounted on DIN rail or mounted directly to a panel. Contactors have both Horsepower and Kw motor rating for international acceptance. Contactor is rated for 20HP at 200 to 208VAC, 20HP at 240VAC, 40HP at 480VAC and 50HP at 600VAC three phase. Contactor is also rated for 5HP at 115VAC and 10HP at 240VAC single phase. When used with a 480VAC up to 110A circuit breaker, this contactor can have a SCCR up to 100kA. When used with up to a 600VAC 125A Class J or CC fuse, this contactor can have a SCCR up to 100kA. Contactor is supplied with a 200 VAC 50/60 Hz coil. Contactor has one normally open and one normally closed auxiliary contact built-in as standard. The NC contact is mirror certified. Screw clamp terminals are used for load and auxiliary connections. An extensive line of accessories makes it easy to meet the requirements of most applications. The contactor is 4.80 inches tall, 2.17 inches wide and 4.72 inches deep. It weighs 1.90 lbs. Contactor is certified to UL, CSA, IEC, CCC, EAC and Marine standards. Contactor also meets the requirements of RoHS/REACh making it a Green Premium product.
- Minimum Switching Current:
- 5 mA for Signaling circuit
- Reach Regulation:
- Free of Substances of Very High Concern above the threshold
- Tightening Torque:
- control circuit 1.7 N.m EverLink BTR screw connectors flat Ø 6 mm || control circuit 1.7 N.m EverLink BTR screw connectors Philips No 2 || power circuit 8 N.m EverLink BTR screw connectors 25-35 mm² hexagonal 4 mm || power circuit 5 N.m EverLink BT
- [Icw] Rated Short-Time Withstand Current:
- 640 A 40°C - 10 s for power circuit || 900 A 40°C - 1 s for power circuit || 110 A 40°C - 10 min for power circuit || 260 A 40°C - 1 min for power circuit || 100 A - 1 s for Signaling circuit || 120 A - 500 ms for Signaling circuit || 140 A - 100 ms
- Operating Altitude:
- 0...9842.52 ft (0...3000 m)
- Mounting Support:
- rail || plate
- Coil Technology:
- without built-in suppressor module
- Electrical Durability:
- 1.4 Mcycles 80 A AC-1 <= 440 V || 1.45 Mcycles 65 A AC-3 <= 440 V || 1.45 Mcycles 65 A AC-3e <= 440 V
- Toxic Heavy Metal Free:
- Yes
- Circularity Profile:
- ENVEOLI1503009EN
- Associated Fuse Rating:
- 10 A gG for Signaling circuit conforming to IEC 60947-5-1 || 125 A gG at <= 690 V coordination type 1 for power circuit || 125 A gG at <= 690 V coordination type 2 for power circuit
- Operating Time:
- 4...19 ms opening || 12...26 ms closing
- Irms Rated Making Capacity:
- 140 A AC for Signaling circuit conforming to IEC 60947-5-1 || 250 A DC for Signaling circuit conforming to IEC 60947-5-1 || 1000 A at 440 V for power circuit conforming to IEC 60947
- Eu Rohs Directive:
- Compliant
- Minimum Switching Voltage:
- 17 V for Signaling circuit
- Insulation Resistance:
- > 10 MOhm for Signaling circuit
- Pvc Free:
- Yes
- Weee:
- The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins.
- [Ue] Rated Operational Voltage:
- power circuit <= 690 V AC 25...400 Hz || power circuit <= 300 V DC
- Mechanical Durability:
- 6 Mcycles
- Signaling Circuit Frequency:
- 25...400 Hz
- China Rohs Regulation:
- Pro-active China RoHS declaration (out of China RoHS legal scope)
- Poles Description:
- 3P
- Reach Free Of Svhc:
- Yes
- Standards:
- EN 60947-4-1 || EN 60947-5-1 || IEC 60947-4-1 || IEC 60947-5-1 || CSA C22.2 No 14 || UL 60947-4-1 || IEC 60335-2-40:Annex JJ || UL 60335-2-40:Annex JJ || IEC 60335-1:Clause 30.2
- Height:
- 122 mm
- Width:
- 55 mm
- Fire Resistance:
- 850°C IEC 60695-2-1
- Weight:
- 0.86 kg
- Compatibility Code:
- LC1D
- Product Or Component Type:
- contactor
- Mercury Free:
- Yes
- Hold-In Power Consumption In Va:
- 13-13 VA 60 Hz cos phi 0.3 (at 20°C) || 15-15 VA 50 Hz cos phi 0.3 (at 20°C)
- Permissible Ambient Air Temperature Around The Device:
- -40-60°C || 60-70°C with derating
- Range Of Product:
- TeSys Deca
- Climatic Withstand:
- IACS E10 exposure to damp heat || IEC 60947-1 Annex Q category D exposure to damp heat
- Warranty:
- 18 months
- Contactor Application:
- resistive load || motor control
- Product Certifications:
- CCC || UL || CB Scheme || CSA || CE || UKCA || Marine || EAC
- Power Dissipation Per Pole:
- 9.6 W AC-1 || 6.3 W AC-3 || 6.3 W AC-3e
- Safety Reliability Level:
- B10d = 1369863 cycles contactor with nominal load EN/ISO 13849-1 || B10d = 20000000 cycles contactor with mechanical load EN/ISO 13849-1
- Sustainable Offer Status:
- Green Premium product
- [Ith] Conventional Free Air Thermal Current:
- 10 A (at 60°C) for Signaling circuit || 80 A (at 60°C) for power circuit
- Flame Retardance:
- V1 conforming to UL 94
- Mechanical Robustness:
- vibrations contactor open 2 Gn, 5...300 Hz) || vibrations contactor closed 4 Gn, 5...300 Hz) || shocks contactor closed 15 Gn for 11 ms) || shocks contactor open 10 Gn for 11 ms)
- Range:
- TeSys || TeSys Deca
- Auxiliary Contact Composition:
- 1 NO + 1 NC
- Connections - Terminals:
- control circuit: screw clamp terminals 2 1-2.5 mm² - cable stiffness: flexible with cable end || control circuit: screw clamp terminals 1 1-4 mm² - cable stiffness: flexible without cable end || control circuit: screw clamp terminals 2 1-4 mm² - c
- Control Circuit Voltage Limits:
- 0.3...0.6 Uc -40-70°C drop-out AC 50/60 Hz || 0.8...1.1 Uc -40-60°C operational AC 50 Hz || 0.85...1.1 Uc -40-60°C operational AC 60 Hz || 1...1.1 Uc 60-70°C operational AC 50/60 Hz
- Rohs Exemption Information:
- Yes