Schneider Electric

Schneider Electric LC1D65ALE7 IEC contactor, TeSys Deca, nonreversing, 65A, 40HP at 480VAC, up to 100kA SCCR, 3 phase, 3 NO, 208VAC 50/60Hz coil, open

(No reviews yet) Write a Review
SKU:
LC1D65ALE7
MPN:
LC1D65ALE7
Condition:
New
Mechanical Durability:
6 Mcycles
Rated Breaking Capacity:
1000 A at 440 V for power circuit conforming to IEC 60947
Reach Regulation:
Free of Substances of Very High Concern above the threshold
Control Circuit Type:
AC 60 Hz
Product Certifications:
CCC || UL || CB Scheme || CSA || CE || UKCA || Marine || EAC
Sustainable Offer Status:
Green Premium product
Tightening Torque:
control circuit 1.7 N.m EverLink BTR screw connectors flat Ø 6 mm || control circuit 1.7 N.m EverLink BTR screw connectors Philips No 2 || power circuit 8 N.m EverLink BTR screw connectors 25-35 mm² hexagonal 4 mm || power circuit 5 N.m EverLink BT
[Ui] Rated Insulation Voltage:
power circuit 600 V CSA || power circuit 600 V UL || Signaling circuit 690 V IEC 60947-1 || Signaling circuit 600 V CSA || Signaling circuit 600 V UL || power circuit 690 V IEC 60947-4-1
Non-Overlap Time:
1.5 ms on de-energisation between NC and NO contact || 1.5 ms on energisation between NC and NO contact
Pollution Degree:
3
Warranty:
18 months
Maximum Horse Power Rating:
40 hp at 460/480 V AC 50/60 Hz for 3 phase motors || 5 hp at 115 V AC 50/60 Hz for 1 phase motors || 10 hp at 230/240 V AC 50/60 Hz for 1 phase motors || 20 hp at 200/208 V AC 50/60 Hz for 3 phase motors || 20 hp at 230/240 V AC 50/60 Hz for 3 phase
Auxiliary Contact Composition:
1 NO + 1 NC
Pole Contact Composition:
3 NO
Coil Technology:
without built-in suppressor module
Rohs Exemption Information:
Yes
Weight:
0.86 kg
Toxic Heavy Metal Free:
Yes
Compatibility Code:
LC1D
Height:
122 mm
Auxiliary Contacts Type:
mechanically linked 1 NO + 1 NC IEC 60947-5-1 || mirror contact 1 NC IEC 60947-4-1
Irms Rated Making Capacity:
140 A AC for Signaling circuit conforming to IEC 60947-5-1 || 250 A DC for Signaling circuit conforming to IEC 60947-5-1 || 1000 A at 440 V for power circuit conforming to IEC 60947
Country of Origin:
United States
China Rohs Regulation:
Pro-active China RoHS declaration (out of China RoHS legal scope)
Pvc Free:
Yes
Sustainable Packaging:
Yes
Electrical Durability:
1.4 Mcycles 80 A AC-1 <= 440 V || 1.45 Mcycles 65 A AC-3 <= 440 V || 1.45 Mcycles 65 A AC-3e <= 440 V
Flame Retardance:
V1 conforming to UL 94
[Ie] Rated Operational Current:
80 A (at <60°C) at <= 440 V AC AC-1 for power circuit || 65 A (at <60°C) at <= 440 V AC AC-3 for power circuit || 65 A (at <60°C) at <= 440 V AC AC-3e for power circuit
Depth:
120 mm
Overvoltage Category:
III
Protective Treatment:
THIEC 60068-2-30
Associated Fuse Rating:
10 A gG for Signaling circuit conforming to IEC 60947-5-1 || 125 A gG at <= 690 V coordination type 1 for power circuit || 125 A gG at <= 690 V coordination type 2 for power circuit
Safety Reliability Level:
B10d = 1369863 cycles contactor with nominal load EN/ISO 13849-1 || B10d = 20000000 cycles contactor with mechanical load EN/ISO 13849-1
Fire Resistance:
850°C IEC 60695-2-1
Contactor Application:
motor control || resistive load
Standards:
EN 60947-4-1 || EN 60947-5-1 || IEC 60947-4-1 || IEC 60947-5-1 || CSA C22.2 No 14 || UL 60947-4-1 || IEC 60335-2-40:Annex JJ || UL 60335-2-40:Annex JJ || IEC 60335-1:Clause 30.2
[Ue] Rated Operational Voltage:
power circuit <= 690 V AC 25...400 Hz || power circuit <= 300 V DC
Product Or Component Type:
contactor
Hold-In Power Consumption In Va:
13-13 VA 60 Hz cos phi 0.3 (at 20°C)
Range:
TeSys || TeSys Deca
Utilisation Category:
AC-4 || AC-1 || AC-3 || AC-3e
Mechanical Robustness:
vibrations contactor open 2 Gn, 5...300 Hz) || vibrations contactor closed 4 Gn, 5...300 Hz) || shocks contactor closed 15 Gn for 11 ms) || shocks contactor open 10 Gn for 11 ms)
Protective Cover:
with
Signaling Circuit Frequency:
25...400 Hz
Connections - Terminals:
control circuit: screw clamp terminals 2 1-2.5 mm² - cable stiffness: flexible with cable end || control circuit: screw clamp terminals 1 1-4 mm² - cable stiffness: flexible without cable end || control circuit: screw clamp terminals 2 1-4 mm² - c
Permissible Ambient Air Temperature Around The Device:
-40-60°C || 60-70°C with derating
Environmental Disclosure:
ENVPEP1503009EN
Net Weight:
0.86 kg
Device Short Name:
LC1D
$386.40

Description

TeSys D contactors have been designed for perfect integration into control systems. They can be used to create motor starters for almost any type of application. TeSys D contactors are available in 13 contactor ratings for inductive motor applications up to 150 full-load amps and resistive loads up to 200 amps. This 65A inductive 3 pole IEC contactor can be mounted on DIN rail or mounted directly to a panel. Contactors have both Horsepower and Kw motor rating for international acceptance. Contactor is rated for 20HP at 200 to 208VAC, 20HP at 240VAC, 40HP at 480VAC and 50HP at 600VAC three phase. Contactor is also rated for 5HP at 115VAC and 10HP at 240VAC single phase. When used with a 480VAC up to 110A circuit breaker, this contactor can have a SCCR up to 100kA. When used with up to a 600VAC 125A Class J or CC fuse, this contactor can have a SCCR up to 100kA. Contactor is supplied with a 208 VAC 60 Hz coil. Contactor has one normally open and one normally closed auxiliary contact built-in as standard. The NC contact is mirror certified. Screw clamp terminals are used for load and auxiliary connections. An extensive line of accessories makes it easy to meet the requirements of most applications. The contactor is 4.80 inches tall, 2.17 inches wide and 4.72 inches deep. It weighs 1.90 lbs. Contactor is certified to UL, CSA, IEC, CCC, EAC and Marine standards. Contactor also meets the requirements of RoHS/REACh making it a Green Premium product.
View AllClose