Schneider Electric

Schneider Electric LC1D65AP7 IEC contactor, TeSys Deca, nonreversing, 65A, 40HP at 480VAC, up to 100kA SCCR, 3 phase, 3 NO, 230VAC 50/60Hz coil, open

(No reviews yet) Write a Review
SKU:
LC1D65AP7
MPN:
LC1D65AP7
Condition:
New
Range:
TeSys || TeSys Deca
[Ie] Rated Operational Current:
80 A (at <60°C) at <= 440 V AC AC-1 for power circuit || 65 A (at <60°C) at <= 440 V AC AC-3 for power circuit || 65 A (at <60°C) at <= 440 V AC AC-3e for power circuit
Mercury Free:
Yes
Flame Retardance:
V1 conforming to UL 94
Irms Rated Making Capacity:
140 A AC for Signaling circuit conforming to IEC 60947-5-1 || 250 A DC for Signaling circuit conforming to IEC 60947-5-1 || 1000 A at 440 V for power circuit conforming to IEC 60947
Auxiliary Contact Composition:
1 NO + 1 NC
Maximum Horse Power Rating:
40 hp at 460/480 V AC 50/60 Hz for 3 phase motors || 5 hp at 115 V AC 50/60 Hz for 1 phase motors || 10 hp at 230/240 V AC 50/60 Hz for 1 phase motors || 20 hp at 200/208 V AC 50/60 Hz for 3 phase motors || 20 hp at 230/240 V AC 50/60 Hz for 3 phase
Connections - Terminals:
control circuit: screw clamp terminals 2 1-2.5 mm² - cable stiffness: flexible with cable end || control circuit: screw clamp terminals 1 1-4 mm² - cable stiffness: flexible without cable end || control circuit: screw clamp terminals 2 1-4 mm² - c
Mechanical Durability:
6 Mcycles
Weee:
The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins.
Toxic Heavy Metal Free:
Yes
Tightening Torque:
control circuit 1.7 N.m EverLink BTR screw connectors flat Ø 6 mm || control circuit 1.7 N.m EverLink BTR screw connectors Philips No 2 || power circuit 8 N.m EverLink BTR screw connectors 25-35 mm² hexagonal 4 mm || power circuit 5 N.m EverLink BT
Range Of Product:
TeSys Deca
Device Short Name:
LC1D
Operating Time:
4...19 ms opening || 12...26 ms closing
Electrical Durability:
1.4 Mcycles 80 A AC-1 <= 440 V || 1.45 Mcycles 65 A AC-3 <= 440 V || 1.45 Mcycles 65 A AC-3e <= 440 V
Associated Fuse Rating:
10 A gG for Signaling circuit conforming to IEC 60947-5-1 || 125 A gG at <= 690 V coordination type 1 for power circuit || 125 A gG at <= 690 V coordination type 2 for power circuit
Pollution Degree:
3
Pole Contact Composition:
3 NO
Control Circuit Type:
AC 50/60 Hz standard
Product Certifications:
CCC || UL || CB Scheme || CSA || CE || UKCA || Marine || EAC
Depth:
120 mm
[Ui] Rated Insulation Voltage:
power circuit 600 V CSA || power circuit 600 V UL || Signaling circuit 690 V IEC 60947-1 || Signaling circuit 600 V CSA || Signaling circuit 600 V UL || power circuit 690 V IEC 60947-4-1
Compatibility Code:
LC1D
Insulation Resistance:
> 10 MOhm for Signaling circuit
Mechanical Robustness:
vibrations contactor open 2 Gn, 5...300 Hz) || vibrations contactor closed 4 Gn, 5...300 Hz) || shocks contactor closed 15 Gn for 11 ms) || shocks contactor open 10 Gn for 11 ms)
Power Dissipation Per Pole:
9.6 W AC-1 || 6.3 W AC-3 || 6.3 W AC-3e
Permissible Ambient Air Temperature Around The Device:
-40-60°C || 60-70°C with derating
Coil Technology:
without built-in suppressor module
Maximum Operating Rate:
3600 cyc/h 60°C
Signaling Circuit Frequency:
25...400 Hz
Motor Power Kw:
11 kW at 400 V AC 50/60 Hz (AC-4) || 18.5 kW at 220...230 V AC 50/60 Hz (AC-3) || 30 kW at 380...400 V AC 50/60 Hz (AC-3) || 37 kW at 500 V AC 50/60 Hz (AC-3) || 37 kW at 660...690 V AC 50/60 Hz (AC-3) || 18.5 kW at 220...230 V AC 50/60 Hz (AC-3e) ||
Average Impedance:
1.5 mOhm - Ith 80 A 50 Hz for power circuit
Reach Regulation:
Free of Substances of Very High Concern above the threshold
Product Or Component Type:
contactor
Ip Degree Of Protection:
IP20 front face IEC 60529
Warranty:
18 months
Contactor Application:
resistive load || motor control
Fire Resistance:
850°C IEC 60695-2-1
Heat Dissipation:
4-5 W at 50/60 Hz
Protective Treatment:
THIEC 60068-2-30
Eu Rohs Directive:
Compliant
Pvc Free:
Yes
Sustainable Offer Status:
Green Premium product
Safety Reliability Level:
B10d = 1369863 cycles contactor with nominal load EN/ISO 13849-1 || B10d = 20000000 cycles contactor with mechanical load EN/ISO 13849-1
Overvoltage Category:
III
Circularity Profile:
ENVEOLI1503009EN
$386.40

Description

TeSys D contactors have been designed for perfect integration into control systems. They can be used to create motor starters for almost any type of application. TeSys D contactors are available in 13 contactor ratings for inductive motor applications up to 150 full-load amps and resistive loads up to 200 amps. This 65A inductive 3 pole IEC contactor can be mounted on DIN rail or mounted directly to a panel. Contactors have both Horsepower and Kw motor rating for international acceptance. Contactor is rated for 20HP at 200 to 208VAC, 20HP at 240VAC, 40HP at 480VAC and 50HP at 600VAC three phase. Contactor is also rated for 5HP at 115VAC and 10HP at 240VAC single phase. When used with a 480VAC up to 110A circuit breaker, this contactor can have a SCCR up to 100kA. When used with up to a 600VAC 125A Class J or CC fuse, this contactor can have a SCCR up to 100kA. Contactor is supplied with a 230 VAC 50/60 Hz coil. Contactor has one normally open and one normally closed auxiliary contact built-in as standard. The NC contact is mirror certified. Screw clamp terminals are used for load and auxiliary connections. An extensive line of accessories makes it easy to meet the requirements of most applications. The contactor is 4.80 inches tall, 2.17 inches wide and 4.72 inches deep. It weighs 1.90 lbs. Contactor is certified to UL, CSA, IEC, CCC, EAC and Marine standards. Contactor also meets the requirements of RoHS/REACh making it a Green Premium product.
View AllClose