Schneider Electric

Schneider Electric LC1D65T6 IEC contactor, TeSys D, nonreversing, 65A, 40HP at 480VAC, up to 100kA SCCR, 3 phase, 3 NO, 480VAC 60Hz coil, open style

(No reviews yet) Write a Review
SKU:
LC1D65T6
MPN:
LC1D65T6
Condition:
New
Fire Resistance:
850°C IEC 60695-2-1
Average Impedance:
1 mOhm - Ith 80 A 50 Hz for power circuit
Reach Free Of Svhc:
Yes
Mounting Support:
plate || rail
Pole Contact Composition:
3 NO
[Ui] Rated Insulation Voltage:
control circuit 600 V CSA || control circuit 600 V UL || power circuit 600 V CSA || power circuit 600 V UL || control circuit 690 V IEC 60947-1 || power circuit 690 V IEC 60947-1
Connections - Terminals:
control circuit: screw clamp terminal 1 1-4 mm² - cable stiffness: solid without cable end || control circuit: screw clamp terminal 2 1-4 mm² - cable stiffness: solid without cable end || control circuit: screw clamp terminal 1 1-2.5 mm² - cable s
Insulation Resistance:
> 10 MOhm for control circuit
China Rohs Regulation:
Pro-active China RoHS declaration (out of China RoHS legal scope)
Protective Cover:
with
Depth:
119 mm
Sustainable Offer Status:
Green Premium product
Mechanical Robustness:
shocks contactor opened 10 Gn for 11 ms) || shocks contactor closed 15 Gn for 11 ms) || vibrations contactor opened 2 Gn, 5...300 Hz) || vibrations contactor closed 4 Gn, 5...300 Hz)
Minimum Switching Current:
5 mA for control circuit
Reach Regulation:
Free of Substances of Very High Concern above the threshold
[Uc] Control Circuit Voltage:
480 V AC 60 Hz
Overvoltage Category:
III
Ip Degree Of Protection:
IP2X IEC 60529 || IP2X VDE 0106
Auxiliary Contacts Type:
mirror contact 1 NC IEC 60947-4-1 || mechanically linked 1 NO + 1 NC IEC 60947-5-1
Climatic Withstand:
IACS E10 exposure to damp heat
Terminals Description Iso N°1:
(21-22)NC || (13-14)NO || (A1-A2)CO
Utilisation Category:
AC-3 || AC-4 || AC-1 || AC-2 || AC-3e
Motor Power Kw:
30 kW at 440 V AC 50/60 Hz || 30 kW at 380...400 V AC 50/60 Hz || 37 kW at 500 V AC 50/60 Hz || 37 kW at 660...690 V AC 50/60 Hz || 18.5 kW at 220...230 V AC 50/60 Hz || 30 kW at 415 V AC 50/60 Hz || 37 kW at 1000 V AC 50/60 Hz
Irms Rated Making Capacity:
140 A AC for control circuit conforming to IEC 60947-5-1 || 1000 A at 440 V for power circuit conforming to IEC 60947
Associated Fuse Rating:
10 A gG for control circuit conforming to IEC 60947-5-1 || 125 A gG at <= 690 V coordination type 1 for power circuit || 125 A gG at <= 690 V coordination type 2 for power circuit
Range Of Product:
TeSys Deca
Flame Retardance:
V1 conforming to UL 94
Operating Altitude:
9842.52 ft (3000 m) without derating
Heat Dissipation:
4-5 W at 50/60 Hz for control circuit
Maximum Horse Power Rating:
10 hp at 230/240 V AC 60 Hz for 1 phase motors conforming to CSA || 10 hp at 230/240 V AC 60 Hz for 1 phase motors conforming to UL || 20 hp at 200/208 V AC 60 Hz for 3 phase motors conforming to CSA || 20 hp at 200/208 V AC 60 Hz for 3 phase motors
Non-Overlap Time:
1.5 ms on de-energisation between NC and NO contacts || 1.5 ms on energisation between NC and NO contacts
Tightening Torque:
control circuit 1.2 N.m screw clamp terminal flat Ø 6 mm || control circuit 1.2 N.m screw clamp terminal Philips No 2 || power circuit 5 N.m screw clamp terminal flat Ø 6 mm || power circuit 5 N.m screw clamp terminal flat Ø 8 mm || control circui
Compatibility Code:
LC1D
Mechanical Durability:
6000000 cycles
Pvc Free:
Yes
[Ue] Rated Operational Voltage:
power circuit <= 690 V AC 25...400 Hz
Product Certifications:
CSA || BV || UL || GL || CCC || GOST || LROS (pending) || DNV || RINA || UKCA
Contactor Application:
motor control || resistive load
[Uimp] Rated Impulse Withstand Voltage:
8 kV IEC 60947
Power Dissipation Per Pole:
6.4 W AC-1
Weight:
1.4 kg
Poles Description:
3P
Operating Time:
12...26 ms closing || 4...19 ms opening
Device Short Name:
LC1D
Country of Origin:
Czechia
$532.80

Description

TeSys D contactors have been designed for perfect integration into control systems. They can be used to create motor starters for almost any type of application. TeSys D contactors are available in 13 contactor ratings for inductive motor applications up to 150 full-load amps and resistive loads up to 200 amps. This 65A inductive 3 pole IEC contactor can be mounted on DIN rail or mounted directly to a panel. Contactors have both Horsepower and Kw motor rating for international acceptance. Contactor is rated for 20HP at 200 to 208VAC, 20HP at 240VAC, 40HP at 480VAC and 50HP at 600VAC three phase. Contactor is also rated for 5HP at 115VAC and 10HP at 240VAC single phase. When used with a 480VAC up to 110A circuit breaker, this contactor can have a SCCR up to 100kA. When used with up to a 600VAC 125A Class J or CC fuse, this contactor can have a SCCR up to 100kA. Contactor is supplied with a 480 VAC 50/60 Hz coil. Contactor has one normally open and one normally closed auxiliary contact built-in as standard. The NC contact is mirror certified. Screw clamp terminals are used for load and auxiliary connections. An extensive line of accessories makes it easy to meet the requirements of most applications. The contactor is 4.80 inches tall, 2.17 inches wide and 4.72 inches deep. It weighs 1.90 lbs. Contactor is certified to UL, CSA, IEC, CCC, EAC and Marine standards. Contactor also meets the requirements of RoHS/REACh making it a Green Premium product.
View AllClose