Schneider Electric LC1D80004P7 IEC contactor, TeSys Deca, nonreversing, 125A resistive, 4 pole, 4 NO, 230VAC 50/60Hz coil, open style
Schneider Electric
$526.40
TeSys D contactors have been designed for perfect integration into control systems. They can be used to create motor starters for almost any type of application. TeSys D contactors are available in 13 contactor ratings for inductive motor applications up to 150 full-load amps and resistive loads up to 200 amps. This 4 pole IEC contactor can be mounted on DIN rail or mounted directly to a panel. Contactor has four normally open power contacts. Power contacts have a 110A resistive load rating. Contactor is supplied with a 230 VAC 50/60 Hz coil. Screw clamp terminals are used for load and auxiliary connections. An extensive line of accessories makes it easy to meet the requirements of most applications. The contactor is 5.00 inches tall, 3.78 inches wide and 4.92 inches deep. It weighs 3.88 lbs. Contactor is certified to UL, CSA, IEC, CCC, EAC and Marine standards. Contactor also meets the requirements of RoHS/REACh making it a Green Premium product.
- Range:
- TeSys
- Mounting Support:
- rail || plate
- China Rohs Regulation:
- Pro-active China RoHS declaration (out of China RoHS legal scope)
- Rated Breaking Capacity:
- 1100 A at 440 V for power circuit conforming to IEC 60947
- Maximum Operating Rate:
- 3600 cyc/h 60°C
- Compatibility Code:
- LC1D
- Ip Degree Of Protection:
- IP20 front face IEC 60529
- Toxic Heavy Metal Free:
- Yes
- Inrush Power In Va:
- 245-245 VA 60 Hz cos phi 0.75 (at 20°C) || 245-245 VA 50 Hz cos phi 0.75 (at 20°C)
- Mercury Free:
- Yes
- Net Weight:
- 1.76 kg
- Power Dissipation Per Pole:
- 12.5 W AC-1
- Operating Altitude:
- 0...9842.52 ft (0...3000 m)
- Control Circuit Type:
- AC 50/60 Hz
- Country of Origin:
- Czechia
- Associated Fuse Rating:
- 200 A gG at <= 690 V coordination type 1 for power circuit || 160 A gG at <= 690 V coordination type 2 for power circuit
- Flame Retardance:
- V1 conforming to UL 94
- Permissible Ambient Air Temperature Around The Device:
- -40-60°C || 60-70°C with derating
- Climatic Withstand:
- IACS E10 exposure to damp heat
- Connections - Terminals:
- control circuit: screw clamp terminals 2 1-2.5 mm² - cable stiffness: flexible with cable end || control circuit: screw clamp terminals 1 1-2.5 mm² - cable stiffness: flexible with cable end || control circuit: screw clamp terminals 1 1-4 mm² - ca
- [Uc] Control Circuit Voltage:
- 230 V AC 50/60 Hz
- Pvc Free:
- Yes
- Width:
- 96 mm
- Contactor Application:
- resistive load
- Reach Regulation:
- Free of Substances of Very High Concern above the threshold
- Sustainable Packaging:
- Yes
- Sustainable Offer Status:
- Green Premium product
- Range Of Product:
- TeSys Deca
- Irms Rated Making Capacity:
- 1100 A at 440 V for power circuit conforming to IEC 60947
- Average Impedance:
- 0.8 mOhm - Ith 125 A 50 Hz for power circuit
- [Icw] Rated Short-Time Withstand Current:
- 640 A 40°C - 10 s for power circuit || 990 A 40°C - 1 s for power circuit || 135 A 40°C - 10 min for power circuit || 320 A 40°C - 1 min for power circuit
- Mechanical Robustness:
- vibrations contactor open 2 Gn, 5...300 Hz) || shocks contactor open 8 Gn for 11 ms) || vibrations contactor closed 3 Gn, 5...300 Hz) || shocks contactor closed 10 Gn for 11 ms)
- Device Short Name:
- LC1D
- Reach Free Of Svhc:
- Yes
- Overvoltage Category:
- III
- Warranty:
- 18 months
- [Ui] Rated Insulation Voltage:
- power circuit 600 V CSA || power circuit 600 V UL || power circuit 1000 V IEC 60947-4-1
- Operating Time:
- 20...35 ms closing || 6...20 ms opening
- Protective Cover:
- without
- Mechanical Durability:
- 4 Mcycles
- Tightening Torque:
- control circuit 1.2 N.m screw clamp terminals flat Ø 6 mm || control circuit 1.2 N.m screw clamp terminals Philips No 2 || power circuit 12 N.m connector flat Ø 6 to Ø 8 mm || power circuit 12 N.m connector hexagonal 4 mm || control circuit 1.2 N.
- Eu Rohs Directive:
- Compliant
- Standards:
- EN 60947-4-1 || EN 60947-5-1 || IEC 60947-4-1 || IEC 60947-5-1 || CSA C22.2 No 14 || UL 60947-4-1 || IEC 60335-2-40:Annex JJ || UL 60335-2-40:Annex JJ || IEC 60335-1:Clause 30.2
- [Ue] Rated Operational Voltage:
- power circuit <= 300 V DC 25...400 Hz || power circuit <= 690 V AC
- Product Or Component Type:
- contactor
- [Ie] Rated Operational Current:
- 125 A (at <60°C) at <= 440 V AC AC-1 for power circuit || 80 A (at <60°C) at <= 440 V AC AC-3 for power circuit || 80 A (at <60°C) at <= 440 V AC AC-3e for power circuit || 55 A (at <60°C) at <= 400 V AC AC-4 for power circuit
- Rohs Exemption Information:
- Yes
- Utilisation Category:
- AC-1 || AC-3 || AC-3e || AC-4
- Protective Treatment:
- THIEC 60068-2-30