Schneider Electric

Schneider Electric LC1D80008U7 IEC contactor, TeSys Deca, nonreversing, 125A resistive, 4 pole, 2 NO and 2 NC, 240VAC 50/60 Hz coil, open style

(No reviews yet) Write a Review
SKU:
LC1D80008U7
MPN:
LC1D80008U7
Condition:
New
Reach Free Of Svhc:
Yes
Irms Rated Making Capacity:
1100 A at 440 V for power circuit conforming to IEC 60947
Reach Regulation:
Free of Substances of Very High Concern above the threshold
Product Certifications:
CCC || UL || CB Scheme || CSA || CE || UKCA || Marine || EAC
China Rohs Regulation:
Pro-active China RoHS declaration (out of China RoHS legal scope)
Poles Description:
4P
Range:
TeSys
Country of Origin:
United States
Rohs Exemption Information:
Yes
Device Short Name:
LC1D
[Ith] Conventional Free Air Thermal Current:
125 A (at 60°C) for power circuit
[Ui] Rated Insulation Voltage:
power circuit 600 V CSA || power circuit 600 V UL || power circuit 1000 V IEC 60947-4-1
Contactor Application:
resistive load
Safety Reliability Level:
B10d = 1369863 cycles contactor with nominal load EN/ISO 13849-1 || B10d = 20000000 cycles contactor with mechanical load EN/ISO 13849-1
Pollution Degree:
3
Range Of Product:
TeSys Deca
Electrical Durability:
0.8 Mcycles 125 A AC-1 <= 440 V
Utilisation Category:
AC-1
Inrush Power In Va:
245-245 VA 60 Hz cos phi 0.75 (at 20°C) || 245-245 VA 50 Hz cos phi 0.75 (at 20°C)
Height:
127 mm
Protective Cover:
without
Compatibility Code:
LC1D
[Uimp] Rated Impulse Withstand Voltage:
8 kV IEC 60947
Coil Technology:
without built-in suppressor module
Power Dissipation Per Pole:
12.5 W AC-1
Mechanical Robustness:
vibrations contactor open 2 Gn, 5...300 Hz) || shocks contactor open 8 Gn for 11 ms) || vibrations contactor closed 3 Gn, 5...300 Hz) || shocks contactor closed 10 Gn for 11 ms)
Mechanical Durability:
4 Mcycles
Operating Time:
20...35 ms closing || 6...20 ms opening
Control Circuit Voltage Limits:
0.85...1.1 Uc -40-55°C operational AC 60 Hz || 0.3...0.6 Uc -40-55°C drop-out AC 50/60 Hz || 0.8...1.1 Uc -40-55°C operational AC 50 Hz
Net Weight:
1.84 kg
Circularity Profile:
N/A
Control Circuit Type:
AC 50/60 Hz
Weee:
The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins.
Depth:
140 mm
Protective Treatment:
THIEC 60068-2-30
Eu Rohs Directive:
Compliant
[Ue] Rated Operational Voltage:
power circuit <= 690 V AC 25...400 Hz
Connections - Terminals:
control circuit: screw clamp terminals 2 1-2.5 mm² - cable stiffness: flexible with cable end || control circuit: screw clamp terminals 1 1-2.5 mm² - cable stiffness: flexible with cable end || control circuit: screw clamp terminals 1 1-4 mm² - ca
Mercury Free:
Yes
Heat Dissipation:
6-10 W at 50/60 Hz
Associated Fuse Rating:
200 A gG at <= 690 V coordination type 1 for power circuit || 160 A gG at <= 690 V coordination type 2 for power circuit
Fire Resistance:
850°C IEC 60695-2-1
Tightening Torque:
control circuit 1.2 N.m screw clamp terminals flat Ø 6 mm || control circuit 1.2 N.m screw clamp terminals Philips No 2 || power circuit 12 N.m connector flat Ø 6 to Ø 8 mm || power circuit 12 N.m connector hexagonal 4 mm || control circuit 1.2 N.
Mounting Support:
plate || rail
[Ie] Rated Operational Current:
125 A (at <60°C) at <= 440 V AC AC-1 for power circuit
Standards:
EN 60947-4-1 || EN 60947-5-1 || IEC 60947-4-1 || IEC 60947-5-1 || CSA C22.2 No 14 || UL 60947-4-1 || IEC 60335-2-40:Annex JJ || UL 60335-2-40:Annex JJ || IEC 60335-1:Clause 30.2
[Icw] Rated Short-Time Withstand Current:
640 A 40°C - 10 s for power circuit || 990 A 40°C - 1 s for power circuit || 135 A 40°C - 10 min for power circuit || 320 A 40°C - 1 min for power circuit
Environmental Disclosure:
ENVPEP110205EN
$518.00

Description

TeSys D contactors have been designed for perfect integration into control systems. They can be used to create motor starters for almost any type of application. TeSys D contactors are available in 13 contactor ratings for inductive motor applications up to 150 full-load amps and resistive loads up to 200 amps. This 4 pole IEC contactor can be mounted on DIN rail or mounted directly to a panel. Contactor has two normally open and two normally closed power contacts. Power contacts have a 110A resistive load rating. Contactor is supplied with a 240 VAC 50/60 Hz coil. Screw clamp terminals are used for load and auxiliary connections. An extensive line of accessories makes it easy to meet the requirements of most applications. The contactor is 5.00 inches tall, 3.78 inches wide and 5.51 inches deep. It weighs 4.06 lbs. Contactor is certified to UL, CSA, IEC, CCC, EAC and Marine standards. Contactor also meets the requirements of RoHS/REACh making it a Green Premium product.
View AllClose