Schneider Electric

Schneider Electric LC1D80A3F7 IEC contactor, TeSys Deca, nonreversing, 80A, 40HP at 480VAC, 3 phase, 3 pole, 3 NO, 110VAC 50/60Hz coil, open style

(No reviews yet) Write a Review
SKU:
LC1D80A3F7
MPN:
LC1D80A3F7
Condition:
New
Weight:
0.86 kg
Operating Time:
4...19 ms opening || 12...26 ms closing
Mercury Free:
Yes
Irms Rated Making Capacity:
140 A AC for Signaling circuit conforming to IEC 60947-5-1 || 250 A DC for Signaling circuit conforming to IEC 60947-5-1 || 1000 A at 440 V AC for power circuit conforming to IEC 60947
Width:
55 mm
Pole Contact Composition:
3 NO
Minimum Switching Voltage:
17 V for Signaling circuit
[Ui] Rated Insulation Voltage:
Signaling circuit 690 V IEC 60947-1 || power circuit 690 V IEC 60947-4-1
Ip Degree Of Protection:
IP20 front face IEC 60529
Maximum Operating Rate:
3600 cyc/h 60°C
Motor Power Kw:
18.5 kW at 220...230 V AC 50 Hz (AC-3) || 37 kW at 380...400 V AC 50 Hz (AC-3) || 37 kW at 415 V AC 50 Hz (AC-3) || 37 kW at 440 V AC 50 Hz (AC-3) || 37 kW at 500 V AC 50 Hz (AC-3) || 37 kW at 660...690 V AC 50 Hz (AC-3)
Connections - Terminals:
power circuit: EverLink BTR screw connectors 1 1-35 mm² - cable stiffness: flexible with cable end || power circuit: EverLink BTR screw connectors 2 1-25 mm² - cable stiffness: flexible with cable end || control circuit: spring terminals 1 0.75-2.5
Auxiliary Contacts Type:
mechanically linked 1 NO + 1 NC IEC 60947-5-1 || mirror contact 1 NC IEC 60947-4-1
[Uimp] Rated Impulse Withstand Voltage:
6 kV IEC 60947
[Ue] Rated Operational Voltage:
power circuit 690 V AC 25...400 Hz || power circuit 300 V DC
Flame Retardance:
V1 conforming to UL 94
Heat Dissipation:
4-5 W at 50/60 Hz
Net Weight:
0.86 kg
Reach Free Of Svhc:
Yes
Tightening Torque:
power circuit 8 N.m EverLink BTR screw connectors 25-35 mm² hexagonal 4 mm || power circuit 5 N.m EverLink BTR screw connectors 1-25 mm² hexagonal 4 mm || control circuit 1.7 N.m screw clamp terminals pozidriv No 2 || power circuit 2.5 N.m screw cl
Weee:
The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins.
Associated Fuse Rating:
10 A gG for Signaling circuit conforming to IEC 60947-5-1 || 125 A gG at <= 690 V coordination type 1 for power circuit || 125 A gG at <= 690 V coordination type 2 for power circuit
Permissible Ambient Air Temperature Around The Device:
-40-60°C || 60-70°C with derating
Standards:
EN/IEC 60947-4-1 || EN/IEC 60947-5-1 || UL 60947-4-1 || CSA C22.2 No 60947-4-1 || IEC 60335-1
Device Short Name:
LC1D
Maximum Horse Power Rating:
5 hp at 115 V AC 60 Hz for 1 phase motors || 10 hp at 230/240 V AC 60 Hz for 1 phase motors || 20 hp at 200/208 V AC 60 Hz for 3 phase motors || 20 hp at 230/240 V AC 60 Hz for 3 phase motors || 40 hp at 460/480 V AC 60 Hz for 3 phase motors || 50 hp
Coil Technology:
without built-in suppressor module
Rohs Exemption Information:
Yes
[Ie] Rated Operational Current:
80 A (at <60°C) at <= 440 V AC-1 for power circuit || 66 A (at <60°C) at <= 440 V AC-3 for power circuit || 66 A (at <60°C) at <= 440 V AC-3e for power circuit
Average Impedance:
1.5 mOhm - Ith 80 A 50 Hz for power circuit
Minimum Switching Current:
5 mA for Signaling circuit
Inrush Power In Va:
140-140 VA 60 Hz cos phi 0.75 (at 20°C) || 160-160 VA 50 Hz cos phi 0.75 (at 20°C)
Pvc Free:
Yes
Range Of Product:
TeSys Deca
Control Circuit Type:
AC 50/60 Hz standard
Power Dissipation Per Pole:
9.6 W AC-1 || 6.3 W AC-3 || 6.3 W AC-3e
Compatibility Code:
LC1D
Auxiliary Contact Composition:
1 NO + 1 NC
Climatic Withstand:
IACS E10 exposure to damp heat || IEC 60947-1 Annex Q category D exposure to damp heat
[Ith] Conventional Free Air Thermal Current:
10 A (at 60°C) for Signaling circuit || 80 A (at 60°C) for power circuit
Poles Description:
3P
Mounting Support:
plate || rail
Control Circuit Voltage Limits:
0.3...0.6 Uc -40-70°C drop-out AC 50/60 Hz || 0.8...1.1 Uc -40-60°C operational AC 50 Hz || 0.85...1.1 Uc -40-60°C operational AC 60 Hz || 1...1.1 Uc 60-70°C operational AC 50/60 Hz
Sustainable Offer Status:
Green Premium product
[Icw] Rated Short-Time Withstand Current:
520 A 40°C - 10 s for power circuit || 900 A 40°C - 1 s for power circuit || 110 A 40°C - 10 min for power circuit || 260 A 40°C - 1 min for power circuit || 100 A - 1 s for Signaling circuit || 120 A - 500 ms for Signaling circuit || 140 A - 100 ms
Protective Treatment:
THIEC 60068-2-30
Environmental Disclosure:
ENVPEP1503009EN
Toxic Heavy Metal Free:
Yes
$426.00

Description

TeSys D contactors have been designed for perfect integration into control systems. They can be used to create motor starters for almost any type of application. TeSys D contactors are available in 13 contactor ratings for inductive motor applications up to 150 full-load amps and resistive loads up to 200 amps. This 80A inductive 3 pole IEC contactor can be mounted on DIN rail or mounted directly to a panel. Contactors have both Horsepower and Kw motor rating for international acceptance. Contactor is rated for 25HP at 200 to 208VAC, 30HP at 240VAC, 40HP at 480VAC and 40HP at 600VAC three phase. Contactor is also rated for 7.5HP at 115VAC and 15HP at 240VAC single phase. Contactor is supplied with a 110 VAC 50/60 Hz coil. Contactor has one normally open and one normally closed auxiliary contact built-in as standard. The NC contact is mirror certified. Spring terminals are used for load and auxiliary connections. An extensive line of accessories makes it easy to meet the requirements of most applications. The contactor is 4.80 inches tall, 2.17 inches wide and 4.72 inches deep. It weighs 1.90 lbs. Contactor is certified to UL, CSA, IEC, CCC, EAC and Marine standards. Contactor also meets the requirements of RoHS/REACh making it a Green Premium product.
View AllClose