Schneider Electric

Schneider Electric LC1D80AG7 IEC contactor, TeSys Deca, nonreversing, 80A, 40HP at 480VAC, 3 phase, 3 pole, 3 NO, 120VAC 50/60Hz coil, open style

(No reviews yet) Write a Review
SKU:
LC1D80AG7
MPN:
LC1D80AG7
Condition:
New
[Ui] Rated Insulation Voltage:
Signaling circuit 690 V IEC 60947-1 || power circuit 690 V IEC 60947-4-1
Heat Dissipation:
4-5 W at 60 Hz
Pollution Degree:
3
[Uimp] Rated Impulse Withstand Voltage:
6 kV IEC 60947
Inrush Power In Va:
140-140 VA 60 Hz cos phi 0.75 (at 20°C)
Maximum Horse Power Rating:
5 hp at 115 V AC 60 Hz for 1 phase motors || 10 hp at 230/240 V AC 60 Hz for 1 phase motors || 20 hp at 200/208 V AC 60 Hz for 3 phase motors || 20 hp at 230/240 V AC 60 Hz for 3 phase motors || 40 hp at 460/480 V AC 60 Hz for 3 phase motors || 50 hp
Irms Rated Making Capacity:
140 A AC for Signaling circuit conforming to IEC 60947-5-1 || 250 A DC for Signaling circuit conforming to IEC 60947-5-1 || 1000 A at 440 V AC for power circuit conforming to IEC 60947
China Rohs Regulation:
Pro-active China RoHS declaration (out of China RoHS legal scope)
[Ie] Rated Operational Current:
80 A (at <60°C) at <= 440 V AC-1 for power circuit || 66 A (at <60°C) at <= 440 V AC-3 for power circuit || 66 A (at <60°C) at <= 440 V AC-3e for power circuit
Net Weight:
0.86 kg
Contactor Application:
motor control || resistive load
Product Or Component Type:
contactor
[Uc] Control Circuit Voltage:
120 V AC 60 Hz
Pvc Free:
Yes
Mechanical Durability:
6 Mcycles
Eu Rohs Directive:
Compliant
Control Circuit Type:
AC 60 Hz
Sustainable Offer Status:
Green Premium product
Utilisation Category:
AC-1 || AC-4 || AC-3 || AC-3e
[Icw] Rated Short-Time Withstand Current:
640 A 40°C - 10 s for power circuit || 900 A 40°C - 1 s for power circuit || 110 A 40°C - 10 min for power circuit || 260 A 40°C - 1 min for power circuit || 100 A - 1 s for Signaling circuit || 120 A - 500 ms for Signaling circuit || 140 A - 100 ms
Device Short Name:
LC1D
Toxic Heavy Metal Free:
Yes
Ip Degree Of Protection:
IP20 front face IEC 60529
Auxiliary Contacts Type:
mechanically linked 1 NO + 1 NC IEC 60947-5-1 || mirror contact 1 NC IEC 60947-4-1
Hold-In Power Consumption In Va:
13-13 VA 60 Hz cos phi 0.3 (at 20°C)
Compatibility Code:
LC1D
Weee:
The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins.
Fire Resistance:
850°C IEC 60695-2-1
Signaling Circuit Frequency:
25...400 Hz
Overvoltage Category:
III
Circularity Profile:
ENVEOLI1503009EN
Maximum Operating Rate:
3600 cyc/h 60°C
Average Impedance:
1.5 mOhm - Ith 80 A 50 Hz for power circuit
Country of Origin:
United States
Tightening Torque:
control circuit 1.7 N.m screw clamp terminals flat Ø 6 mm || control circuit 1.7 N.m screw clamp terminals Philips No 2 || power circuit 8 N.m EverLink BTR screw connectors 25-35 mm² hexagonal 4 mm || power circuit 5 N.m EverLink BTR screw connecto
Environmental Disclosure:
ENVPEP1503009EN
Minimum Switching Voltage:
17 V for Signaling circuit
Mounting Support:
plate || rail
Coil Technology:
without built-in suppressor module
Standards:
EN/IEC 60947-4-1 || EN/IEC 60947-5-1 || UL 60947-4-1 || CSA C22.2 No 60947-4-1 || IEC 60335-1
Connections - Terminals:
control circuit: screw clamp terminals 2 1-2.5 mm² - cable stiffness: flexible with cable end || control circuit: screw clamp terminals 1 1-4 mm² - cable stiffness: flexible with cable end || power circuit: EverLink BTR screw connectors 1 1-35 mm²
Protective Cover:
with
Protective Treatment:
THIEC 60068-2-30
Flame Retardance:
V1 conforming to UL 94
Mercury Free:
Yes
Reach Regulation:
Free of Substances of Very High Concern above the threshold
Safety Reliability Level:
B10d = 1369863 cycles contactor with nominal load EN/ISO 13849-1 || B10d = 20000000 cycles contactor with mechanical load EN/ISO 13849-1
Pole Contact Composition:
3 NO
Associated Fuse Rating:
10 A gG for Signaling circuit conforming to IEC 60947-5-1 || 125 A gG at <= 690 V coordination type 1 for power circuit || 125 A gG at <= 690 V coordination type 2 for power circuit
[Ith] Conventional Free Air Thermal Current:
10 A (at 60°C) for Signaling circuit || 80 A (at 60°C) for power circuit
$426.00

Description

TeSys D contactors have been designed for perfect integration into control systems. They can be used to create motor starters for almost any type of application. TeSys D contactors are available in 13 contactor ratings for inductive motor applications up to 150 full-load amps and resistive loads up to 200 amps. This 80A inductive 3 pole IEC contactor can be mounted on DIN rail or mounted directly to a panel. Contactors have both Horsepower and Kw motor rating for international acceptance. Contactor is rated for 25HP at 200 to 208VAC, 30HP at 240VAC, 40HP at 480VAC and 60HP at 600VAC three phase. Contactor is also rated for 7.5HP at 115VAC and 15HP at 240VAC single phase. Contactor is supplied with a 120 VAC 60 Hz coil. Contactor has one normally open and one normally closed auxiliary contact built-in as standard. The NC contact is mirror certified. Screw clamp terminals are used for load and auxiliary connections. An extensive line of accessories makes it easy to meet the requirements of most applications. The contactor is 4.80 inches tall, 2.17 inches wide and 4.72 inches deep. It weighs 1.90 lbs. Contactor is certified to UL, CSA, IEC, CCC, EAC and Marine standards. Contactor also meets the requirements of RoHS/REACh making it a Green Premium product.
View AllClose