Schneider Electric LC1D80AV7 IEC contactor, TeSys Deca, nonreversing, 80A, 40HP at 480VAC, 3 phase, 3 pole, 3 NO, 400VAC 50/60Hz coil, open style
Schneider Electric
$426.00
TeSys D contactors have been designed for perfect integration into control systems. They can be used to create motor starters for almost any type of application. TeSys D contactors are available in 13 contactor ratings for inductive motor applications up to 150 full-load amps and resistive loads up to 200 amps. This 80A inductive 3 pole IEC contactor can be mounted on DIN rail or mounted directly to a panel. Contactors have both Horsepower and Kw motor rating for international acceptance. Contactor is rated for 25HP at 200 to 208VAC, 30HP at 240VAC, 40HP at 480VAC and 60HP at 600VAC three phase. Contactor is also rated for 7.5HP at 115VAC and 15HP at 240VAC single phase. Contactor is supplied with a 400 VAC 50/60 Hz coil. Contactor has one normally open and one normally closed auxiliary contact built-in as standard. The NC contact is mirror certified. Screw clamp terminals are used for load and auxiliary connections. An extensive line of accessories makes it easy to meet the requirements of most applications. The contactor is 4.80 inches tall, 2.17 inches wide and 4.72 inches deep. It weighs 1.90 lbs. Contactor is certified to UL, CSA, IEC, CCC, EAC and Marine standards. Contactor also meets the requirements of RoHS/REACh making it a Green Premium product.
- Minimum Switching Current:
- 5 mA for Signaling circuit
- Mechanical Robustness:
- vibrations contactor open 2 Gn, 5...300 Hz) || vibrations contactor closed 4 Gn, 5...300 Hz) || shocks contactor closed 15 Gn for 11 ms) || shocks contactor open 10 Gn for 11 ms)
- Connections - Terminals:
- control circuit: screw clamp terminals 2 1-2.5 mm² - cable stiffness: flexible with cable end || control circuit: screw clamp terminals 1 1-4 mm² - cable stiffness: flexible with cable end || power circuit: EverLink BTR screw connectors 1 1-35 mm²
- Rated Breaking Capacity:
- 1000 A at 440 V for power circuit conforming to IEC 60947
- Depth:
- 120 mm
- Protective Treatment:
- THIEC 60068-2-30
- Auxiliary Contacts Type:
- mechanically linked 1 NO + 1 NC IEC 60947-5-1 || mirror contact 1 NC IEC 60947-4-1
- Operating Altitude:
- 0...9842.52 ft (0...3000 m)
- Maximum Horse Power Rating:
- 5 hp at 115 V AC 60 Hz for 1 phase motors || 10 hp at 230/240 V AC 60 Hz for 1 phase motors || 20 hp at 200/208 V AC 60 Hz for 3 phase motors || 20 hp at 230/240 V AC 60 Hz for 3 phase motors || 40 hp at 460/480 V AC 60 Hz for 3 phase motors || 50 hp
- Hold-In Power Consumption In Va:
- 13-13 VA 60 Hz cos phi 0.3 (at 20°C) || 15-15 VA 50 Hz cos phi 0.3 (at 20°C)
- Pollution Degree:
- 3
- Device Short Name:
- LC1D
- [Icw] Rated Short-Time Withstand Current:
- 640 A 40°C - 10 s for power circuit || 900 A 40°C - 1 s for power circuit || 110 A 40°C - 10 min for power circuit || 260 A 40°C - 1 min for power circuit || 100 A - 1 s for Signaling circuit || 120 A - 500 ms for Signaling circuit || 140 A - 100 ms
- Pvc Free:
- Yes
- Rohs Exemption Information:
- Yes
- Reach Regulation:
- Free of Substances of Very High Concern above the threshold
- Circularity Profile:
- ENVEOLI1503009EN
- Standards:
- EN/IEC 60947-4-1 || EN/IEC 60947-5-1 || UL 60947-4-1 || CSA C22.2 No 60947-4-1 || IEC 60335-1
- Utilisation Category:
- AC-1 || AC-4 || AC-3 || AC-3e
- Associated Fuse Rating:
- 10 A gG for Signaling circuit conforming to IEC 60947-5-1 || 125 A gG at <= 690 V coordination type 1 for power circuit || 125 A gG at <= 690 V coordination type 2 for power circuit
- Protective Cover:
- with
- Permissible Ambient Air Temperature Around The Device:
- -40-60°C || 60-70°C with derating
- Insulation Resistance:
- > 10 MOhm for Signaling circuit
- Electrical Durability:
- 0.7 Mcycles 80 A AC-1 <= 440 V || 1 Mcycles 66 A AC-3 <= 440 V || 1 Mcycles 66 A AC-3e <= 440 V
- Power Dissipation Per Pole:
- 9.6 W AC-1 || 6.3 W AC-3 || 6.3 W AC-3e
- Inrush Power In Va:
- 140-140 VA 60 Hz cos phi 0.75 (at 20°C) || 160-160 VA 50 Hz cos phi 0.75 (at 20°C)
- Range Of Product:
- TeSys Deca
- Eu Rohs Directive:
- Compliant
- Warranty:
- 18 months
- [Ith] Conventional Free Air Thermal Current:
- 10 A (at 60°C) for Signaling circuit || 80 A (at 60°C) for power circuit
- Mechanical Durability:
- 6 Mcycles
- Overvoltage Category:
- III
- Operating Time:
- 4...19 ms opening || 12...26 ms closing
- Compatibility Code:
- LC1D
- Width:
- 55 mm
- Height:
- 122 mm
- Weight:
- 0.86 kg
- Toxic Heavy Metal Free:
- Yes
- Net Weight:
- 0.86 kg
- [Ui] Rated Insulation Voltage:
- Signaling circuit 690 V IEC 60947-1 || power circuit 690 V IEC 60947-4-1
- Poles Description:
- 3P
- Control Circuit Type:
- AC 50/60 Hz standard
- Ip Degree Of Protection:
- IP20 front face IEC 60529
- Average Impedance:
- 1.5 mOhm - Ith 80 A 50 Hz for power circuit
- Auxiliary Contact Composition:
- 1 NO + 1 NC
- Mounting Support:
- plate || rail
- Heat Dissipation:
- 4-5 W at 50/60 Hz
- Contactor Application:
- motor control || resistive load
- Maximum Operating Rate:
- 3600 cyc/h 60°C
- Irms Rated Making Capacity:
- 140 A AC for Signaling circuit conforming to IEC 60947-5-1 || 250 A DC for Signaling circuit conforming to IEC 60947-5-1 || 1000 A at 440 V AC for power circuit conforming to IEC 60947