Schneider Electric

Schneider Electric LC1D80AV7 IEC contactor, TeSys Deca, nonreversing, 80A, 40HP at 480VAC, 3 phase, 3 pole, 3 NO, 400VAC 50/60Hz coil, open style

(No reviews yet) Write a Review
SKU:
LC1D80AV7
MPN:
LC1D80AV7
Condition:
New
Minimum Switching Current:
5 mA for Signaling circuit
Mechanical Robustness:
vibrations contactor open 2 Gn, 5...300 Hz) || vibrations contactor closed 4 Gn, 5...300 Hz) || shocks contactor closed 15 Gn for 11 ms) || shocks contactor open 10 Gn for 11 ms)
Connections - Terminals:
control circuit: screw clamp terminals 2 1-2.5 mm² - cable stiffness: flexible with cable end || control circuit: screw clamp terminals 1 1-4 mm² - cable stiffness: flexible with cable end || power circuit: EverLink BTR screw connectors 1 1-35 mm²
Rated Breaking Capacity:
1000 A at 440 V for power circuit conforming to IEC 60947
Depth:
120 mm
Protective Treatment:
THIEC 60068-2-30
Auxiliary Contacts Type:
mechanically linked 1 NO + 1 NC IEC 60947-5-1 || mirror contact 1 NC IEC 60947-4-1
Operating Altitude:
0...9842.52 ft (0...3000 m)
Maximum Horse Power Rating:
5 hp at 115 V AC 60 Hz for 1 phase motors || 10 hp at 230/240 V AC 60 Hz for 1 phase motors || 20 hp at 200/208 V AC 60 Hz for 3 phase motors || 20 hp at 230/240 V AC 60 Hz for 3 phase motors || 40 hp at 460/480 V AC 60 Hz for 3 phase motors || 50 hp
Hold-In Power Consumption In Va:
13-13 VA 60 Hz cos phi 0.3 (at 20°C) || 15-15 VA 50 Hz cos phi 0.3 (at 20°C)
Pollution Degree:
3
Device Short Name:
LC1D
[Icw] Rated Short-Time Withstand Current:
640 A 40°C - 10 s for power circuit || 900 A 40°C - 1 s for power circuit || 110 A 40°C - 10 min for power circuit || 260 A 40°C - 1 min for power circuit || 100 A - 1 s for Signaling circuit || 120 A - 500 ms for Signaling circuit || 140 A - 100 ms
Pvc Free:
Yes
Rohs Exemption Information:
Yes
Reach Regulation:
Free of Substances of Very High Concern above the threshold
Circularity Profile:
ENVEOLI1503009EN
Standards:
EN/IEC 60947-4-1 || EN/IEC 60947-5-1 || UL 60947-4-1 || CSA C22.2 No 60947-4-1 || IEC 60335-1
Utilisation Category:
AC-1 || AC-4 || AC-3 || AC-3e
Associated Fuse Rating:
10 A gG for Signaling circuit conforming to IEC 60947-5-1 || 125 A gG at <= 690 V coordination type 1 for power circuit || 125 A gG at <= 690 V coordination type 2 for power circuit
Protective Cover:
with
Permissible Ambient Air Temperature Around The Device:
-40-60°C || 60-70°C with derating
Insulation Resistance:
> 10 MOhm for Signaling circuit
Electrical Durability:
0.7 Mcycles 80 A AC-1 <= 440 V || 1 Mcycles 66 A AC-3 <= 440 V || 1 Mcycles 66 A AC-3e <= 440 V
Power Dissipation Per Pole:
9.6 W AC-1 || 6.3 W AC-3 || 6.3 W AC-3e
Inrush Power In Va:
140-140 VA 60 Hz cos phi 0.75 (at 20°C) || 160-160 VA 50 Hz cos phi 0.75 (at 20°C)
Range Of Product:
TeSys Deca
Eu Rohs Directive:
Compliant
Warranty:
18 months
[Ith] Conventional Free Air Thermal Current:
10 A (at 60°C) for Signaling circuit || 80 A (at 60°C) for power circuit
Mechanical Durability:
6 Mcycles
Overvoltage Category:
III
Operating Time:
4...19 ms opening || 12...26 ms closing
Compatibility Code:
LC1D
Width:
55 mm
Height:
122 mm
Weight:
0.86 kg
Toxic Heavy Metal Free:
Yes
Net Weight:
0.86 kg
[Ui] Rated Insulation Voltage:
Signaling circuit 690 V IEC 60947-1 || power circuit 690 V IEC 60947-4-1
Poles Description:
3P
Control Circuit Type:
AC 50/60 Hz standard
Ip Degree Of Protection:
IP20 front face IEC 60529
Average Impedance:
1.5 mOhm - Ith 80 A 50 Hz for power circuit
Auxiliary Contact Composition:
1 NO + 1 NC
Mounting Support:
plate || rail
Heat Dissipation:
4-5 W at 50/60 Hz
Contactor Application:
motor control || resistive load
Maximum Operating Rate:
3600 cyc/h 60°C
Irms Rated Making Capacity:
140 A AC for Signaling circuit conforming to IEC 60947-5-1 || 250 A DC for Signaling circuit conforming to IEC 60947-5-1 || 1000 A at 440 V AC for power circuit conforming to IEC 60947
$426.00

Description

TeSys D contactors have been designed for perfect integration into control systems. They can be used to create motor starters for almost any type of application. TeSys D contactors are available in 13 contactor ratings for inductive motor applications up to 150 full-load amps and resistive loads up to 200 amps. This 80A inductive 3 pole IEC contactor can be mounted on DIN rail or mounted directly to a panel. Contactors have both Horsepower and Kw motor rating for international acceptance. Contactor is rated for 25HP at 200 to 208VAC, 30HP at 240VAC, 40HP at 480VAC and 60HP at 600VAC three phase. Contactor is also rated for 7.5HP at 115VAC and 15HP at 240VAC single phase. Contactor is supplied with a 400 VAC 50/60 Hz coil. Contactor has one normally open and one normally closed auxiliary contact built-in as standard. The NC contact is mirror certified. Screw clamp terminals are used for load and auxiliary connections. An extensive line of accessories makes it easy to meet the requirements of most applications. The contactor is 4.80 inches tall, 2.17 inches wide and 4.72 inches deep. It weighs 1.90 lbs. Contactor is certified to UL, CSA, IEC, CCC, EAC and Marine standards. Contactor also meets the requirements of RoHS/REACh making it a Green Premium product.