Schneider Electric

Schneider Electric LC1D80FD IEC contactor, TeSys Deca, nonreversing, 80A, 60HP at 480VAC, up to 100kA SCCR, 3 phase, 3 NO, 110VDC coil, open style

(No reviews yet) Write a Review
SKU:
LC1D80FD
MPN:
LC1D80FD
Condition:
New
[Icw] Rated Short-Time Withstand Current:
640 A 40°C - 10 s for power circuit || 990 A 40°C - 1 s for power circuit || 135 A 40°C - 10 min for power circuit || 320 A 40°C - 1 min for power circuit || 100 A - 1 s for Signaling circuit || 120 A - 500 ms for Signaling circuit || 140 A - 100 ms
Sustainable Offer Status:
Green Premium product
Insulation Resistance:
> 10 MOhm for Signaling circuit
Electrical Durability:
0.8 Mcycles 125 A AC-1 <= 440 V || 1.5 Mcycles 80 A AC-3 <= 440 V || 1.5 Mcycles 80 A AC-3e <= 440 V
Mercury Free:
Yes
Rohs Exemption Information:
Yes
Minimum Switching Voltage:
17 V for Signaling circuit
Control Circuit Voltage Limits:
0.1...0.3 Uc -40-70°C drop-out DC || 0.85...1.1 Uc -40-55°C operational DC || 1...1.1 Uc 55-70°C operational DC
Associated Fuse Rating:
10 A gG for Signaling circuit conforming to IEC 60947-5-1 || 200 A gG at <= 690 V coordination type 1 for power circuit || 160 A gG at <= 690 V coordination type 2 for power circuit
Warranty:
18 months
Weight:
2.59 kg
Device Short Name:
LC1D
Reach Free Of Svhc:
Yes
Maximum Horse Power Rating:
7.5 hp at 120 V AC 50/60 Hz for 1 phase motors || 15 hp at 230/240 V AC 50/60 Hz for 1 phase motors || 30 hp at 200/208 V AC 50/60 Hz for 3 phase motors || 30 hp at 230/240 V AC 50/60 Hz for 3 phase motors || 60 hp at 460/480 V AC 50/60 Hz for 3 phas
Maximum Operating Rate:
3600 cyc/h 60°C
Operating Time:
95...130 ms closing || 20...35 ms opening
Average Impedance:
0.8 mOhm - Ith 125 A 50 Hz for power circuit
Ip Degree Of Protection:
IP20 front face IEC 60529
Depth:
186 mm
Signaling Circuit Frequency:
25...400 Hz
[Ue] Rated Operational Voltage:
power circuit <= 300 V DC 25...400 Hz || power circuit <= 690 V AC
[Ie] Rated Operational Current:
125 A (at <60°C) at <= 440 V AC AC-1 for power circuit || 80 A (at <60°C) at <= 440 V AC AC-3 for power circuit || 80 A (at <60°C) at <= 440 V AC-3e for power circuit
Mounting Support:
plate || rail
Country of Origin:
Czechia
Flame Retardance:
V1 conforming to UL 94
Mechanical Durability:
4 Mcycles
China Rohs Regulation:
Pro-active China RoHS declaration (out of China RoHS legal scope)
Pole Contact Composition:
3 NO
Control Circuit Type:
DC standard
Eu Rohs Directive:
Compliant
Poles Description:
3P
Climatic Withstand:
IACS E10 exposure to damp heat
Product Certifications:
CCC || UL || CB Scheme || CSA || CE || UKCA || Marine || EAC
Protective Treatment:
THIEC 60068-2-30
Protective Cover:
with
Overvoltage Category:
III
Contactor Application:
motor control || resistive load
Auxiliary Contact Composition:
1 NO + 1 NC
Toxic Heavy Metal Free:
Yes
Minimum Switching Current:
5 mA for Signaling circuit
Tightening Torque:
control circuit 1.2 N.m screw clamp terminals flat Ø 6 mm || control circuit 1.2 N.m screw clamp terminals Philips No 2 || power circuit 12 N.m connector flat Ø 6 to Ø 8 mm || power circuit 12 N.m connector hexagonal 4 mm || control circuit 1.2 N.
Coil Technology:
without built-in suppressor module
Product Or Component Type:
contactor
Net Weight:
2.59 kg
Non-Overlap Time:
1.5 ms on de-energisation between NC and NO contact || 1.5 ms on energisation between NC and NO contact
$447.00

Description

TeSys D contactors have been designed for perfect integration into control systems. They can be used to create motor starters for almost any type of application. TeSys D contactors are available in 13 contactor ratings for inductive motor applications up to 150 full-load amps and resistive loads up to 200 amps. This 80A inductive 3 pole IEC contactor can be mounted on DIN rail or mounted directly to a panel. Contactors have both Horsepower and Kw motor rating for international acceptance. Contactor is rated for 25HP at 200 to 208VAC, 30HP at 240VAC, 60HP at 480VAC and 60HP at 600VAC three phase. Contactor is also rated for 7.5HP at 115VAC and 15HP at 240VAC single phase. When used with a 480VAC up to 150A circuit breaker, this contactor can have a SCCR up to 100kA. When used with up to a 600VAC 175A Class J or CC fuse, this contactor can have a SCCR up to 100kA. Contactor is supplied with a 110 VDC coil with transient suppressor module. Contactor has one normally open and one normally closed auxiliary contact built-in as standard. The NC contact is mirror certified. Screw clamp terminals are used for load and auxiliary connections. An extensive line of accessories makes it easy to meet the requirements of most applications. The contactor is 5.00 inches tall, 3.35 inches wide and 7.32 inches deep. It weighs 5.71 lbs. Contactor is certified to UL, CSA, IEC, CCC, EAC and Marine standards. Contactor also meets the requirements of RoHS/REACh making it a Green Premium product.
View AllClose