Schneider Electric

Schneider Electric LC1D80JD IEC contactor, TeSys D, nonreversing, 80A, 60HP at 480VAC, up to 100kA SCCR, 3 phase, 3 NO, 12VDC coil, open style

(No reviews yet) Write a Review
SKU:
LC1D80JD
MPN:
LC1D80JD
Condition:
New
[Ui] Rated Insulation Voltage:
power circuit 600 V CSA || power circuit 600 V UL || power circuit 1000 V IEC 60947-4-1 || Signaling circuit 690 V IEC 60947-1 || Signaling circuit 600 V CSA || Signaling circuit 600 V UL
Auxiliary Contact Composition:
1 NO + 1 NC
Utilisation Category:
AC-3 || AC-3e || AC-4 || AC-1
Mercury Free:
Yes
Weight:
2.59 kg
Reach Regulation:
Free of Substances of Very High Concern above the threshold
Electrical Durability:
0.8 Mcycles 125 A AC-1 <= 440 V || 1.5 Mcycles 80 A AC-3 <= 440 V || 1.5 Mcycles 80 A AC-3e <= 440 V
[Uc] Control Circuit Voltage:
12 V DC
Rohs Exemption Information:
Yes
Pollution Degree:
3
[Ie] Rated Operational Current:
125 A (at <60°C) at <= 440 V AC AC-1 for power circuit || 80 A (at <60°C) at <= 440 V AC AC-3 for power circuit || 80 A (at <60°C) at <= 440 V AC AC-3e for power circuit
Product Certifications:
CCC || UL || CB Scheme || CSA || CE || UKCA || Marine || EAC
Mounting Support:
rail || plate
Mechanical Robustness:
vibrations contactor open 2 Gn, 5...300 Hz) || shocks contactor open 8 Gn for 11 ms) || vibrations contactor closed 3 Gn, 5...300 Hz) || shocks contactor closed 10 Gn for 11 ms)
Mechanical Durability:
4 Mcycles
Pvc Free:
Yes
Non-Overlap Time:
1.5 ms on de-energisation between NC and NO contact || 1.5 ms on energisation between NC and NO contact
Pole Contact Composition:
3 NO
Overvoltage Category:
III
Poles Description:
3P
Depth:
186 mm
[Ith] Conventional Free Air Thermal Current:
10 A (at 60°C) for Signaling circuit || 125 A (at 60°C) for power circuit
Control Circuit Type:
DC standard
Warranty:
18 months
Auxiliary Contacts Type:
mechanically linked 1 NO + 1 NC IEC 60947-5-1 || mirror contact 1 NC IEC 60947-4-1
Inrush Power In W:
22-22 W 20°C)
Safety Reliability Level:
B10d = 1369863 cycles contactor with nominal load EN/ISO 13849-1 || B10d = 20000000 cycles contactor with mechanical load EN/ISO 13849-1
Eu Rohs Directive:
Compliant
Operating Time:
95...130 ms closing || 20...35 ms opening
[Icw] Rated Short-Time Withstand Current:
640 A 40°C - 10 s for power circuit || 990 A 40°C - 1 s for power circuit || 135 A 40°C - 10 min for power circuit || 320 A 40°C - 1 min for power circuit || 100 A - 1 s for Signaling circuit || 120 A - 500 ms for Signaling circuit || 140 A - 100 ms
Height:
127 mm
Coil Technology:
without built-in suppressor module
Reach Free Of Svhc:
Yes
Fire Resistance:
850°C IEC 60695-2-1
Device Short Name:
LC1D
Insulation Resistance:
> 10 MOhm for Signaling circuit
Climatic Withstand:
IACS E10 exposure to damp heat
Country of Origin:
Czechia
Minimum Switching Current:
5 mA for Signaling circuit
Width:
85 mm
Power Dissipation Per Pole:
5.1 W AC-3 || 12.5 W AC-1 || 5.1 W AC-3e
Ip Degree Of Protection:
IP20 front face IEC 60529
Hold-In Power Consumption In W:
22-22 W 20°C
Net Weight:
2.59 kg
Control Circuit Voltage Limits:
0.1...0.3 Uc -40-70°C drop-out DC || 0.85...1.1 Uc -40-55°C operational DC || 1...1.1 Uc 55-70°C operational DC
Associated Fuse Rating:
10 A gG for Signaling circuit conforming to IEC 60947-5-1 || 200 A gG at <= 690 V coordination type 1 for power circuit || 160 A gG at <= 690 V coordination type 2 for power circuit
[Uimp] Rated Impulse Withstand Voltage:
8 kV IEC 60947
Time Constant:
75 ms
Maximum Horse Power Rating:
7.5 hp at 120 V AC 50/60 Hz for 1 phase motors || 15 hp at 230/240 V AC 50/60 Hz for 1 phase motors || 30 hp at 200/208 V AC 50/60 Hz for 3 phase motors || 30 hp at 230/240 V AC 50/60 Hz for 3 phase motors || 60 hp at 460/480 V AC 50/60 Hz for 3 phas
$447.00

Description

TeSys D contactors have been designed for perfect integration into control systems. They can be used to create motor starters for almost any type of application. TeSys D contactors are available in 13 contactor ratings for inductive motor applications up to 150 full-load amps and resistive loads up to 200 amps. This 80A inductive 3 pole IEC contactor can be mounted on DIN rail or mounted directly to a panel. Contactors have both Horsepower and Kw motor rating for international acceptance. Contactor is rated for 25HP at 200 to 208VAC, 30HP at 240VAC, 60HP at 480VAC and 60HP at 600VAC three phase. Contactor is also rated for 7.5HP at 115VAC and 15HP at 240VAC single phase. When used with a 480VAC up to 150A circuit breaker, this contactor can have a SCCR up to 100kA. When used with up to a 600VAC 175A Class J or CC fuse, this contactor can have a SCCR up to 100kA. Contactor is supplied with a 12 VDC coil with transient suppressor module. Contactor has one normally open and one normally closed auxiliary contact built-in as standard. The NC contact is mirror certified. Screw clamp terminals are used for load and auxiliary connections. An extensive line of accessories makes it easy to meet the requirements of most applications. The contactor is 5.00 inches tall, 3.35 inches wide and 7.32 inches deep. It weighs 5.71 lbs. Contactor is certified to UL, CSA, IEC, CCC, EAC and Marine standards. Contactor also meets the requirements of RoHS/REACh making it a Green Premium product.
View AllClose