Schneider Electric

Schneider Electric LC1D956BD IEC contactor, TeSys Deca, nonreversing, 95A, 60HP at 480VAC, 3 phase, 3 pole, 3 NO, 24VDC coil, open style

(No reviews yet) Write a Review
SKU:
LC1D956BD
MPN:
LC1D956BD
Condition:
New
Time Constant:
75 ms
Tightening Torque:
control circuit 1.2 N.m lugs-ring terminals flat Ø 6 mm M3.5 || control circuit 1.2 N.m lugs-ring terminals Philips No 2 M3.5 || power circuit 5 N.m lugs-ring terminals flat Ø 8 mm M6 || power circuit 5 N.m lugs-ring terminals hexagonal 10 mm M6 ||
Auxiliary Contact Composition:
1 NO + 1 NC
Device Short Name:
LC1D
Maximum Horse Power Rating:
7.5 hp at 120 V AC 60 Hz for 1 phase motors || 15 hp at 230/240 V AC 60 Hz for 1 phase motors || 30 hp at 200/208 V AC 60 Hz for 3 phase motors || 30 hp at 230/240 V AC 60 Hz for 3 phase motors || 60 hp at 460/480 V AC 60 Hz for 3 phase motors || 60
Mounting Support:
rail || plate
Range:
TeSys
Average Impedance:
0.8 mOhm - Ith 125 A 50 Hz for power circuit
Sustainable Offer Status:
Green Premium product
[Ith] Conventional Free Air Thermal Current:
10 A (at 60°C) for Signaling circuit || 125 A (at 60°C) for power circuit
Insulation Resistance:
> 10 MOhm for Signaling circuit
[Uc] Control Circuit Voltage:
24 V DC
Standards:
EN/IEC 60947-1 || EN/IEC 60947-4-1 || EN/IEC 60947-5-1 || GB/T 14048.4
Country of Origin:
Czechia
Electrical Durability:
1.2 Mcycles 95 A AC-3 || 1.3 Mcycles 125 A AC-1 || 1.2 Mcycles 95 A AC-3e
Pvc Free:
Yes
Weight:
2.61 kg
Hold-In Power Consumption In W:
22-22 W 20°C
[Ue] Rated Operational Voltage:
power circuit <= 690 V AC 25...400 Hz
[Uimp] Rated Impulse Withstand Voltage:
8 kV IEC 60947
Ip Degree Of Protection:
IP20 front face IEC 60529
Warranty:
18 months
Environmental Disclosure:
ENVPEP110205EN
Motor Power Kw:
25 kW at 220...230 V AC 50 Hz (AC-3) || 45 kW at 380...400 V AC 50 Hz (AC-3) || 45 kW at 415...440 V AC 50 Hz (AC-3) || 55 kW at 500 V AC 50 Hz (AC-3) || 45 kW at 660...690 V AC 50 Hz (AC-3) || 25 kW at 220...230 V AC 50 Hz (AC-3e) || 45 kW at 380...
Pole Contact Composition:
3 NO
Fire Resistance:
850°C IEC 60695-2-1
[Ie] Rated Operational Current:
95 A (at <60°C) at <= 440 V AC-3 for power circuit || 125 A (at <60°C) at <= 690 V AC-1 for power circuit || 95 A (at <60°C) at <= 440 V AC-3e for power circuit
Toxic Heavy Metal Free:
Yes
Contactor Application:
motor control || resistive load
Reach Regulation:
Free of Substances of Very High Concern above the threshold
Control Circuit Voltage Limits:
0.1...0.3 Uc -40-70°C drop-out DC || 0.85...1.1 Uc -40-55°C operational DC || 1...1.1 Uc 55-70°C operational DC
Inrush Power In W:
22-22 W 20°C)
Flame Retardance:
V1 conforming to UL 94
Weee:
The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins.
China Rohs Regulation:
Pro-active China RoHS declaration (out of China RoHS legal scope)
Compatibility Code:
LC1D
Product Or Component Type:
contactor
Control Circuit Type:
DC standard
[Ui] Rated Insulation Voltage:
power circuit 1000 V IEC 60947-4-1 || Signaling circuit 690 V IEC 60947-1
Permissible Ambient Air Temperature Around The Device:
-40-60°C || 60-70°C with derating
Minimum Switching Voltage:
17 V for Signaling circuit
Connections - Terminals:
control circuit: lugs-ring terminals - external diameter: 8 mm || power circuit: bars 1 - busbar cross section: 3 x 16 mm || power circuit: lugs-ring terminals - external diameter: 17 mm
Circularity Profile:
N/A
Product Certifications:
IECEE CB Scheme || CCC || EAC || LROS (Lloyds register of shipping) || RINA || BV || DNV-GL
Depth:
186 mm
Non-Overlap Time:
1.5 ms on de-energisation between NC and NO contact || 1.5 ms on energisation between NC and NO contact
$526.00

Description

TeSys D contactors have been designed for perfect integration into control systems. They can be used to create motor starters for almost any type of application. TeSys D contactors are available in 13 contactor ratings for inductive motor applications up to 150 full-load amps and resistive loads up to 200 amps. This 95A inductive 3 pole IEC contactor can be mounted on DIN rail or mounted directly to a panel. Contactors have both Horsepower and Kw motor rating for international acceptance. Contactor is rated for 25HP at 200 to 208VAC, 30HP at 240VAC, 60HP at 480VAC and 60HP at 600VAC three phase. Contactor is also rated for 7.5HP at 115VAC and 15HP at 240VAC single phase. Contactor is supplied with a 24 VDC coil with transient suppressor module. Contactor has one normally open and one normally closed auxiliary contact built-in as standard. The NC contact is mirror certified. Ring-lug screw terminals are used for load and auxiliary connections. An extensive line of accessories makes it easy to meet the requirements of most applications. The contactor is 5.00 inches tall, 3.35 inches wide and 7.32 inches deep. It weighs 5.75 lbs. Contactor is certified to UL, CSA, IEC, CCC, EAC and Marine standards. Contactor also meets the requirements of RoHS/REACh making it a Green Premium product.
View AllClose