Schneider Electric

Schneider Electric LC1D95E7 IEC contactor, TeSys Deca, nonreversing, 95A, 60HP at 480VAC, 3 phase, 3 pole, 3 NO, 48VAC 50/60Hz coil, open style

(No reviews yet) Write a Review
SKU:
LC1D95E7
MPN:
LC1D95E7
Condition:
New
Product Certifications:
CCC || UL || CB Scheme || CSA || CE || UKCA || Marine || EAC
Circularity Profile:
N/A
Net Weight:
1.61 kg
Reach Regulation:
Free of Substances of Very High Concern above the threshold
Country of Origin:
Czechia
Range Of Product:
TeSys Deca
Safety Reliability Level:
B10d = 1.3 Mcycles contactor with nominal load EN/ISO 13849-1 || B10d = 20 Mcycles contactor with mechanical load EN/ISO 13849-1
Hold-In Power Consumption In Va:
26-26 VA 60 Hz cos phi 0.3 (at 20°C) || 26-26 VA 50 Hz cos phi 0.3 (at 20°C)
Sustainable Offer Status:
Green Premium product
Product Or Component Type:
contactor
China Rohs Regulation:
Pro-active China RoHS declaration (out of China RoHS legal scope)
Power Dissipation Per Pole:
12.5 W AC-1 || 7.2 W AC-3 || 7.2 W AC-3e
Heat Dissipation:
6-10 W at 50/60 Hz
Control Circuit Voltage Limits:
0.8...1.1 Uc -40-55°C operational AC 50 Hz || 0.85...1.1 Uc -40-55°C operational AC 60 Hz || 0.3...0.6 Uc -40-70°C drop-out AC 50/60 Hz || 1...1.1 Uc 55-70°C operational AC 50/60 Hz
Environmental Disclosure:
ENVPEP110205EN
Weight:
1.61 kg
Rated Breaking Capacity:
1100 A at 440 V for power circuit conforming to IEC 60947
Overvoltage Category:
III
Contactor Application:
motor control || resistive load
Compatibility Code:
LC1D
Pollution Degree:
3
Maximum Horse Power Rating:
7.5 hp at 120 V AC 60 Hz for 1 phase motors || 15 hp at 230/240 V AC 60 Hz for 1 phase motors || 30 hp at 200/208 V AC 60 Hz for 3 phase motors || 30 hp at 230/240 V AC 60 Hz for 3 phase motors || 60 hp at 460/480 V AC 60 Hz for 3 phase motors || 60
Sustainable Packaging:
Yes
[Ith] Conventional Free Air Thermal Current:
10 A (at 60°C) for Signaling circuit || 125 A (at 60°C) for power circuit
Operating Altitude:
0...9842.52 ft (0...3000 m)
Irms Rated Making Capacity:
1100 A at 440 V AC for power circuit conforming to IEC 60947 || 140 A AC for Signaling circuit conforming to IEC 60947-5-1 || 250 A DC for Signaling circuit conforming to IEC 60947-5-1
[Uimp] Rated Impulse Withstand Voltage:
8 kV IEC 60947
Warranty:
18 months
[Uc] Control Circuit Voltage:
48 V AC 50/60 Hz
Toxic Heavy Metal Free:
Yes
Coil Technology:
without built-in suppressor module
Mechanical Durability:
4 Mcycles
Fire Resistance:
850°C IEC 60695-2-1
Depth:
130 mm
[Ui] Rated Insulation Voltage:
power circuit 1000 V IEC 60947-4-1 || power circuit 600 V CSA || power circuit 600 V UL || Signaling circuit 690 V IEC 60947-1 || Signaling circuit 600 V CSA || Signaling circuit 600 V UL
Maximum Operating Rate:
3600 cyc/h 60°C
Non-Overlap Time:
1.5 ms on de-energisation between NC and NO contact || 1.5 ms on energisation between NC and NO contact
Associated Fuse Rating:
10 A gG for Signaling circuit conforming to IEC 60947-5-1 || 200 A gG at <= 690 V coordination type 1 for power circuit || 160 A gG at <= 690 V coordination type 2 for power circuit
Connections - Terminals:
control circuit: screw clamp terminals 2 1-2.5 mm² - cable stiffness: flexible with cable end || control circuit: screw clamp terminals 1 1-2.5 mm² - cable stiffness: flexible with cable end || control circuit: screw clamp terminals 1 1-4 mm² - ca
Electrical Durability:
1.2 Mcycles 95 A AC-3 || 1.3 Mcycles 125 A AC-1 || 1.2 Mcycles 95 A AC-3e
Reach Free Of Svhc:
Yes
Minimum Switching Current:
5 mA for Signaling circuit
Auxiliary Contact Composition:
1 NO + 1 NC
Eu Rohs Directive:
Compliant
Height:
127 mm
Flame Retardance:
V1 conforming to UL 94
Control Circuit Type:
AC 50/60 Hz standard
Protective Cover:
with
Minimum Switching Voltage:
17 V for Signaling circuit
$437.00

Description

TeSys D contactors have been designed for perfect integration into control systems. They can be used to create motor starters for almost any type of application. TeSys D contactors are available in 13 contactor ratings for inductive motor applications up to 150 full-load amps and resistive loads up to 200 amps. This 95A inductive 3 pole IEC contactor can be mounted on DIN rail or mounted directly to a panel. Contactors have both Horsepower and Kw motor rating for international acceptance. Contactor is rated for 25HP at 200 to 208VAC, 30HP at 240VAC, 60HP at 480VAC and 60HP at 600VAC three phase. Contactor is also rated for 7.5HP at 115VAC and 15HP at 240VAC single phase. Contactor is supplied with a 48 VAC 50/60 Hz coil. Contactor has one normally open and one normally closed auxiliary contact built-in as standard. The NC contact is mirror certified. Screw clamp terminals are used for load and auxiliary connections. An extensive line of accessories makes it easy to meet the requirements of most applications. The contactor is 5.00 inches tall, 3.35 inches wide and 5.12 inches deep. It weighs 3.55 lbs. Contactor is certified to UL, CSA, IEC, CCC, EAC and Marine standards. Contactor also meets the requirements of RoHS/REACh making it a Green Premium product.
View AllClose