Schneider Electric

Schneider Electric LC1D95F7 IEC contactor, TeSys Deca, nonreversing, 95A, 60HP at 480VAC, 3 phase, 3 pole, 3 NO, 110VAC 50/60Hz coil, open style

(No reviews yet) Write a Review
SKU:
LC1D95F7
MPN:
LC1D95F7
Condition:
New
Height:
127 mm
[Uc] Control Circuit Voltage:
110 V AC 50/60 Hz
Net Weight:
1.61 kg
Product Certifications:
CCC || UL || CB Scheme || CSA || CE || UKCA || Marine || EAC
Rohs Exemption Information:
Yes
Control Circuit Voltage Limits:
0.8...1.1 Uc -40-55°C operational AC 50 Hz || 0.85...1.1 Uc -40-55°C operational AC 60 Hz || 0.3...0.6 Uc -40-70°C drop-out AC 50/60 Hz || 1...1.1 Uc 55-70°C operational AC 50/60 Hz
Maximum Operating Rate:
3600 cyc/h 60°C
Mounting Support:
rail || plate
China Rohs Regulation:
Pro-active China RoHS declaration (out of China RoHS legal scope)
Protective Treatment:
THIEC 60068-2-30
Minimum Switching Voltage:
17 V for Signaling circuit
Inrush Power In Va:
245-245 VA 60 Hz cos phi 0.75 (at 20°C) || 245-245 VA 50 Hz cos phi 0.75 (at 20°C)
Operating Altitude:
0...9842.52 ft (0...3000 m)
[Icw] Rated Short-Time Withstand Current:
1100 A 40°C - 1 s for power circuit || 800 A 40°C - 10 s for power circuit || 400 A 40°C - 1 min for power circuit || 135 A 40°C - 10 min for power circuit || 140 A - 100 ms for Signaling circuit || 120 A - 500 ms for Signaling circuit || 100 A - 1 s
Power Dissipation Per Pole:
12.5 W AC-1 || 7.2 W AC-3 || 7.2 W AC-3e
Depth:
130 mm
Associated Fuse Rating:
10 A gG for Signaling circuit conforming to IEC 60947-5-1 || 200 A gG at <= 690 V coordination type 1 for power circuit || 160 A gG at <= 690 V coordination type 2 for power circuit
Coil Technology:
without built-in suppressor module
Mercury Free:
Yes
Country of Origin:
Czechia
Protective Cover:
with
Mechanical Robustness:
vibrations contactor open 2 Gn, 5...300 Hz) || shocks contactor open 8 Gn for 11 ms) || vibrations contactor closed 3 Gn, 5...300 Hz) || shocks contactor closed 10 Gn for 11 ms)
Maximum Horse Power Rating:
7.5 hp at 120 V AC 60 Hz for 1 phase motors || 15 hp at 230/240 V AC 60 Hz for 1 phase motors || 30 hp at 200/208 V AC 60 Hz for 3 phase motors || 30 hp at 230/240 V AC 60 Hz for 3 phase motors || 60 hp at 460/480 V AC 60 Hz for 3 phase motors || 60
Contactor Application:
motor control || resistive load
Insulation Resistance:
> 10 MOhm for Signaling circuit
Toxic Heavy Metal Free:
Yes
Reach Free Of Svhc:
Yes
Ip Degree Of Protection:
IP20 front face IEC 60529
Utilisation Category:
AC-3 || AC-3e || AC-4 || AC-1
Minimum Switching Current:
5 mA for Signaling circuit
Auxiliary Contact Composition:
1 NO + 1 NC
Device Short Name:
LC1D
Range:
TeSys
Sustainable Packaging:
Yes
Reach Regulation:
Free of Substances of Very High Concern above the threshold
[Ie] Rated Operational Current:
95 A (at <60°C) at <= 440 V AC-3 for power circuit || 125 A (at <60°C) at <= 690 V AC-1 for power circuit || 95 A (at <60°C) at <= 440 V AC-3e for power circuit
Hold-In Power Consumption In Va:
26-26 VA 60 Hz cos phi 0.3 (at 20°C) || 26-26 VA 50 Hz cos phi 0.3 (at 20°C)
Signaling Circuit Frequency:
25...400 Hz
Fire Resistance:
850°C IEC 60695-2-1
Eu Rohs Directive:
Compliant
Sustainable Offer Status:
Green Premium product
Operating Time:
20...35 ms closing || 6...20 ms opening
Weight:
1.61 kg
Pvc Free:
Yes
Heat Dissipation:
6-10 W at 50/60 Hz
[Ith] Conventional Free Air Thermal Current:
10 A (at 60°C) for Signaling circuit || 125 A (at 60°C) for power circuit
Tightening Torque:
control circuit 1.2 N.m screw clamp terminals flat Ø 6 mm || control circuit 1.2 N.m screw clamp terminals Philips No 2 || power circuit 12 N.m connector flat Ø 6 to Ø 8 mm || power circuit 12 N.m connector hexagonal 4 mm || control circuit 1.2 N.
Non-Overlap Time:
1.5 ms on de-energisation between NC and NO contact || 1.5 ms on energisation between NC and NO contact
Safety Reliability Level:
B10d = 1.3 Mcycles contactor with nominal load EN/ISO 13849-1 || B10d = 20 Mcycles contactor with mechanical load EN/ISO 13849-1
$437.00

Description

TeSys D contactors have been designed for perfect integration into control systems. They can be used to create motor starters for almost any type of application. TeSys D contactors are available in 13 contactor ratings for inductive motor applications up to 150 full-load amps and resistive loads up to 200 amps. This 95A inductive 3 pole IEC contactor can be mounted on DIN rail or mounted directly to a panel. Contactors have both Horsepower and Kw motor rating for international acceptance. Contactor is rated for 25HP at 200 to 208VAC, 30HP at 240VAC, 60HP at 480VAC and 60HP at 600VAC three phase. Contactor is also rated for 7.5HP at 115VAC and 15HP at 240VAC single phase. Contactor is supplied with a 110 VAC 50/60 Hz coil. Contactor has one normally open and one normally closed auxiliary contact built-in as standard. The NC contact is mirror certified. Screw clamp terminals are used for load and auxiliary connections. An extensive line of accessories makes it easy to meet the requirements of most applications. The contactor is 5.00 inches tall, 3.35 inches wide and 5.12 inches deep. It weighs 3.55 lbs. Contactor is certified to UL, CSA, IEC, CCC, EAC and Marine standards. Contactor also meets the requirements of RoHS/REACh making it a Green Premium product.
View AllClose