Schneider Electric

Schneider Electric LC1D95FE7 IEC contactor, TeSys Deca, nonreversing, 95A, 60HP at 480VAC, 3 phase, 3 pole, 3 NO, 115VAC 50/60Hz coil, open style

(No reviews yet) Write a Review
SKU:
LC1D95FE7
MPN:
LC1D95FE7
Condition:
New
Protective Cover:
with
Mercury Free:
Yes
Compatibility Code:
LC1D
[Ue] Rated Operational Voltage:
power circuit <= 690 V AC 25...400 Hz
Product Certifications:
CCC || UL || CB Scheme || CSA || CE || UKCA || Marine || EAC
Safety Reliability Level:
B10d = 1.3 Mcycles contactor with nominal load EN/ISO 13849-1 || B10d = 20 Mcycles contactor with mechanical load EN/ISO 13849-1
Ip Degree Of Protection:
IP20 front face IEC 60529
Pollution Degree:
3
Permissible Ambient Air Temperature Around The Device:
-40-60°C || 60-70°C with derating
Range Of Product:
TeSys Deca
Utilisation Category:
AC-3 || AC-3e || AC-4 || AC-1
[Ith] Conventional Free Air Thermal Current:
10 A (at 60°C) for Signaling circuit || 125 A (at 60°C) for power circuit
Overvoltage Category:
III
Fire Resistance:
850°C IEC 60695-2-1
Poles Description:
3P
Associated Fuse Rating:
10 A gG for Signaling circuit conforming to IEC 60947-5-1 || 200 A gG at <= 690 V coordination type 1 for power circuit || 160 A gG at <= 690 V coordination type 2 for power circuit
Mechanical Durability:
4 Mcycles
China Rohs Regulation:
Pro-active China RoHS declaration (out of China RoHS legal scope)
Eu Rohs Directive:
Compliant
[Uc] Control Circuit Voltage:
115 V AC 50/60 Hz
Depth:
130 mm
Minimum Switching Voltage:
17 V for Signaling circuit
Mechanical Robustness:
vibrations contactor open 2 Gn, 5...300 Hz) || shocks contactor open 8 Gn for 11 ms) || vibrations contactor closed 3 Gn, 5...300 Hz) || shocks contactor closed 10 Gn for 11 ms)
Maximum Operating Rate:
3600 cyc/h 60°C
Warranty:
18 months
[Uimp] Rated Impulse Withstand Voltage:
8 kV IEC 60947
Product Or Component Type:
contactor
Heat Dissipation:
6-10 W at 50/60 Hz
Width:
85 mm
Weight:
1.61 kg
Reach Free Of Svhc:
Yes
Range:
TeSys
Control Circuit Type:
AC 50/60 Hz standard
Maximum Horse Power Rating:
7.5 hp at 120 V AC 60 Hz for 1 phase motors || 15 hp at 230/240 V AC 60 Hz for 1 phase motors || 30 hp at 200/208 V AC 60 Hz for 3 phase motors || 30 hp at 230/240 V AC 60 Hz for 3 phase motors || 60 hp at 460/480 V AC 60 Hz for 3 phase motors || 60
Flame Retardance:
V1 conforming to UL 94
[Ui] Rated Insulation Voltage:
power circuit 1000 V IEC 60947-4-1 || power circuit 600 V CSA || power circuit 600 V UL || Signaling circuit 690 V IEC 60947-1 || Signaling circuit 600 V CSA || Signaling circuit 600 V UL
Country of Origin:
Czechia
Power Dissipation Per Pole:
12.5 W AC-1 || 7.2 W AC-3 || 7.2 W AC-3e
Net Weight:
1.61 kg
Protective Treatment:
THIEC 60068-2-30
Weee:
The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins.
Pvc Free:
Yes
Pole Contact Composition:
3 NO
Auxiliary Contacts Type:
mechanically linked 1 NO + 1 NC IEC 60947-5-1 || mirror contact 1 NC IEC 60947-4-1
Circularity Profile:
N/A
Motor Power Kw:
25 kW at 220...230 V AC 50 Hz (AC-3) || 45 kW at 380...400 V AC 50 Hz (AC-3) || 45 kW at 415...440 V AC 50 Hz (AC-3) || 55 kW at 500 V AC 50 Hz (AC-3) || 45 kW at 660...690 V AC 50 Hz (AC-3) || 15 kW at 400 V AC 50 Hz (AC-4) || 25 kW at 220...230 V A
[Ie] Rated Operational Current:
95 A (at <60°C) at <= 440 V AC-3 for power circuit || 125 A (at <60°C) at <= 690 V AC-1 for power circuit || 95 A (at <60°C) at <= 440 V AC-3e for power circuit
$437.00

Description

TeSys D contactors have been designed for perfect integration into control systems. They can be used to create motor starters for almost any type of application. TeSys D contactors are available in 13 contactor ratings for inductive motor applications up to 150 full-load amps and resistive loads up to 200 amps. This 95A inductive 3 pole IEC contactor can be mounted on DIN rail or mounted directly to a panel. Contactors have both Horsepower and Kw motor rating for international acceptance. Contactor is rated for 25HP at 200 to 208VAC, 30HP at 240VAC, 60HP at 480VAC and 60HP at 600VAC three phase. Contactor is also rated for 7.5HP at 115VAC and 15HP at 240VAC single phase. Contactor is supplied with a 115 VAC 50/60 Hz coil. Contactor has one normally open and one normally closed auxiliary contact built-in as standard. The NC contact is mirror certified. Screw clamp terminals are used for load and auxiliary connections. An extensive line of accessories makes it easy to meet the requirements of most applications. The contactor is 5.00 inches tall, 3.35 inches wide and 5.12 inches deep. It weighs 3.55 lbs. Contactor is certified to UL, CSA, IEC, CCC, EAC and Marine standards. Contactor also meets the requirements of RoHS/REACh making it a Green Premium product.
View AllClose