Schneider Electric LC1D95M7 IEC contactor, TeSys Deca, nonreversing, 95A, 60HP at 480VAC, 3 phase, 3 pole, 3 NO, 220VAC 50/60Hz coil, open style
Schneider Electric
$437.00
TeSys D contactors have been designed for perfect integration into control systems. They can be used to create motor starters for almost any type of application. TeSys D contactors are available in 13 contactor ratings for inductive motor applications up to 150 full-load amps and resistive loads up to 200 amps. This 95A inductive 3 pole IEC contactor can be mounted on DIN rail or mounted directly to a panel. Contactors have both Horsepower and Kw motor rating for international acceptance. Contactor is rated for 25HP at 200 to 208VAC, 30HP at 240VAC, 60HP at 480VAC and 60HP at 600VAC three phase. Contactor is also rated for 7.5HP at 115VAC and 15HP at 240VAC single phase. Contactor is supplied with a 220 VAC 50/60 Hz coil. Contactor has one normally open and one normally closed auxiliary contact built-in as standard. The NC contact is mirror certified. Screw clamp terminals are used for load and auxiliary connections. An extensive line of accessories makes it easy to meet the requirements of most applications. The contactor is 5.00 inches tall, 3.35 inches wide and 5.12 inches deep. It weighs 3.55 lbs. Contactor is certified to UL, CSA, IEC, CCC, EAC and Marine standards. Contactor also meets the requirements of RoHS/REACh making it a Green Premium product.
- Reach Regulation:
- Free of Substances of Very High Concern above the threshold
- Range:
- TeSys
- [Icw] Rated Short-Time Withstand Current:
- 1100 A 40°C - 1 s for power circuit || 800 A 40°C - 10 s for power circuit || 400 A 40°C - 1 min for power circuit || 135 A 40°C - 10 min for power circuit || 140 A - 100 ms for Signaling circuit || 120 A - 500 ms for Signaling circuit || 100 A - 1 s
- Climatic Withstand:
- IACS E10 exposure to damp heat
- Tightening Torque:
- control circuit 1.2 N.m screw clamp terminals flat Ø 6 mm || control circuit 1.2 N.m screw clamp terminals Philips No 2 || power circuit 12 N.m connector flat Ø 6 to Ø 8 mm || power circuit 12 N.m connector hexagonal 4 mm || control circuit 1.2 N.
- Sustainable Offer Status:
- Green Premium product
- Operating Time:
- 20...35 ms closing || 6...20 ms opening
- Device Short Name:
- LC1D
- Overvoltage Category:
- III
- Standards:
- EN 60947-4-1 || EN 60947-5-1 || IEC 60947-4-1 || IEC 60947-5-1 || CSA C22.2 No 14 || UL 60947-4-1 || IEC 60335-2-40:Annex JJ || UL 60335-2-40:Annex JJ || IEC 60335-1:Clause 30.2
- Flame Retardance:
- V1 conforming to UL 94
- Signaling Circuit Frequency:
- 25...400 Hz
- Maximum Operating Rate:
- 3600 cyc/h 60°C
- Operating Altitude:
- 0...9842.52 ft (0...3000 m)
- Pvc Free:
- Yes
- Range Of Product:
- TeSys Deca
- Rated Breaking Capacity:
- 1100 A at 440 V for power circuit conforming to IEC 60947
- Rohs Exemption Information:
- Yes
- Minimum Switching Voltage:
- 17 V for Signaling circuit
- Control Circuit Type:
- AC 50/60 Hz standard
- Product Or Component Type:
- contactor
- Warranty:
- 18 months
- Net Weight:
- 1.61 kg
- Eu Rohs Directive:
- Compliant
- Fire Resistance:
- 850°C IEC 60695-2-1
- Average Impedance:
- 0.8 mOhm - Ith 125 A 50 Hz for power circuit
- Utilisation Category:
- AC-3 || AC-3e || AC-4 || AC-1
- Heat Dissipation:
- 6-10 W at 50/60 Hz
- Height:
- 127 mm
- [Uimp] Rated Impulse Withstand Voltage:
- 8 kV IEC 60947
- Insulation Resistance:
- > 10 MOhm for Signaling circuit
- Irms Rated Making Capacity:
- 1100 A at 440 V AC for power circuit conforming to IEC 60947 || 140 A AC for Signaling circuit conforming to IEC 60947-5-1 || 250 A DC for Signaling circuit conforming to IEC 60947-5-1
- [Ui] Rated Insulation Voltage:
- power circuit 1000 V IEC 60947-4-1 || power circuit 600 V CSA || power circuit 600 V UL || Signaling circuit 690 V IEC 60947-1 || Signaling circuit 600 V CSA || Signaling circuit 600 V UL
- Protective Cover:
- with
- Motor Power Kw:
- 25 kW at 220...230 V AC 50 Hz (AC-3) || 45 kW at 380...400 V AC 50 Hz (AC-3) || 45 kW at 415...440 V AC 50 Hz (AC-3) || 55 kW at 500 V AC 50 Hz (AC-3) || 45 kW at 660...690 V AC 50 Hz (AC-3) || 15 kW at 400 V AC 50 Hz (AC-4) || 25 kW at 220...230 V A
- [Ue] Rated Operational Voltage:
- power circuit <= 690 V AC 25...400 Hz
- Contactor Application:
- motor control || resistive load
- Protective Treatment:
- THIEC 60068-2-30
- Safety Reliability Level:
- B10d = 1.3 Mcycles contactor with nominal load EN/ISO 13849-1 || B10d = 20 Mcycles contactor with mechanical load EN/ISO 13849-1
- Compatibility Code:
- LC1D
- Ip Degree Of Protection:
- IP20 front face IEC 60529
- Weee:
- The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins.
- Minimum Switching Current:
- 5 mA for Signaling circuit
- Connections - Terminals:
- control circuit: screw clamp terminals 2 1-2.5 mm² - cable stiffness: flexible with cable end || control circuit: screw clamp terminals 1 1-2.5 mm² - cable stiffness: flexible with cable end || control circuit: screw clamp terminals 1 1-4 mm² - ca
- Depth:
- 130 mm
- Mechanical Durability:
- 4 Mcycles
- Electrical Durability:
- 1.2 Mcycles 95 A AC-3 || 1.3 Mcycles 125 A AC-1 || 1.2 Mcycles 95 A AC-3e