New
Minimum Switching Voltage:
17 V for Signaling circuit
Weight:
1.61 kg
Average Impedance:
0.8 mOhm - Ith 125 A 50 Hz for power circuit
Associated Fuse Rating:
10 A gG for Signaling circuit conforming to IEC 60947-5-1 || 200 A gG at <= 690 V coordination type 1 for power circuit || 160 A gG at <= 690 V coordination type 2 for power circuit
Width:
85 mm
[Ue] Rated Operational Voltage:
power circuit <= 690 V AC 25...400 Hz
Auxiliary Contact Composition:
1 NO + 1 NC
Coil Technology:
without built-in suppressor module
Pole Contact Composition:
3 NO
Utilisation Category:
AC-3 || AC-3e || AC-4 || AC-1
Heat Dissipation:
6-10 W at 50/60 Hz
Control Circuit Type:
AC 50/60 Hz
[Uc] Control Circuit Voltage:
380 V AC 50/60 Hz
[Uimp] Rated Impulse Withstand Voltage:
8 kV IEC 60947
Climatic Withstand:
IACS E10 exposure to damp heat
Flame Retardance:
V1 conforming to UL 94
Maximum Horse Power Rating:
7.5 hp at 120 V AC 60 Hz for 1 phase motors || 15 hp at 230/240 V AC 60 Hz for 1 phase motors || 30 hp at 200/208 V AC 60 Hz for 3 phase motors || 30 hp at 230/240 V AC 60 Hz for 3 phase motors || 60 hp at 460/480 V AC 60 Hz for 3 phase motors || 60
Environmental Disclosure:
ENVPEP110205EN
Country of Origin:
Czechia
[Icw] Rated Short-Time Withstand Current:
1100 A 40°C - 1 s for power circuit || 800 A 40°C - 10 s for power circuit || 400 A 40°C - 1 min for power circuit || 135 A 40°C - 10 min for power circuit || 140 A - 100 ms for Signaling circuit || 120 A - 500 ms for Signaling circuit || 100 A - 1 s
Control Circuit Voltage Limits:
0.8...1.1 Uc -40-55°C operational AC 50 Hz || 0.85...1.1 Uc -40-55°C operational AC 60 Hz || 0.3...0.6 Uc -40-70°C drop-out AC 50/60 Hz || 1...1.1 Uc 55-70°C operational AC 50/60 Hz
Non-Overlap Time:
1.5 ms on de-energisation between NC and NO contact || 1.5 ms on energisation between NC and NO contact
Reach Free Of Svhc:
Yes
Operating Altitude:
0...9842.52 ft (0...3000 m)
Product Or Component Type:
contactor
Power Dissipation Per Pole:
12.5 W AC-1 || 7.2 W AC-3 || 7.2 W AC-3e
Minimum Switching Current:
5 mA for Signaling circuit
Auxiliary Contacts Type:
mechanically linked 1 NO + 1 NC IEC 60947-5-1 || mirror contact 1 NC IEC 60947-4-1
China Rohs Regulation:
Pro-active China RoHS declaration (out of China RoHS legal scope)
Net Weight:
1.61 kg
Maximum Operating Rate:
3600 cyc/h 60°C
Ip Degree Of Protection:
IP20 front face IEC 60529
[Ith] Conventional Free Air Thermal Current:
10 A (at 60°C) for Signaling circuit || 125 A (at 60°C) for power circuit
Insulation Resistance:
> 10 MOhm for Signaling circuit
Height:
127 mm
Device Short Name:
LC1D
Warranty:
18 months
Reach Regulation:
Free of Substances of Very High Concern above the threshold
[Ui] Rated Insulation Voltage:
power circuit 1000 V IEC 60947-4-1 || power circuit 600 V CSA || power circuit 600 V UL || Signaling circuit 690 V IEC 60947-1 || Signaling circuit 600 V CSA || Signaling circuit 600 V UL
Mechanical Robustness:
vibrations contactor open 2 Gn, 5...300 Hz) || shocks contactor open 8 Gn for 11 ms) || vibrations contactor closed 3 Gn, 5...300 Hz) || shocks contactor closed 10 Gn for 11 ms)
Protective Cover:
with
Mounting Support:
rail || plate
Electrical Durability:
1.2 Mcycles 95 A AC-3 || 1.3 Mcycles 125 A AC-1 || 1.2 Mcycles 95 A AC-3e
Depth:
130 mm
Circularity Profile:
N/A
[Ie] Rated Operational Current:
95 A (at <60°C) at <= 440 V AC-3 for power circuit || 125 A (at <60°C) at <= 690 V AC-1 for power circuit || 95 A (at <60°C) at <= 440 V AC-3e for power circuit
Eu Rohs Directive:
Compliant
Compatibility Code:
LC1D
Mercury Free:
Yes
Operating Time:
20...35 ms closing || 6...20 ms opening
$437.00

Description

TeSys D contactors have been designed for perfect integration into control systems. They can be used to create motor starters for almost any type of application. TeSys D contactors are available in 13 contactor ratings for inductive motor applications up to 150 full-load amps and resistive loads up to 200 amps. This 95A inductive 3 pole IEC contactor can be mounted on DIN rail or mounted directly to a panel. Contactors have both Horsepower and Kw motor rating for international acceptance. Contactor is rated for 25HP at 200 to 208VAC, 30HP at 240VAC, 60HP at 480VAC and 60HP at 600VAC three phase. Contactor is also rated for 7.5HP at 115VAC and 15HP at 240VAC single phase. Contactor is supplied with a 380 VAC 50/60 Hz coil. Contactor has one normally open and one normally closed auxiliary contact built-in as standard. The NC contact is mirror certified. Screw clamp terminals are used for load and auxiliary connections. An extensive line of accessories makes it easy to meet the requirements of most applications. The contactor is 5.00 inches tall, 3.35 inches wide and 5.12 inches deep. It weighs 3.55 lbs. Contactor is certified to UL, CSA, IEC, CCC, EAC and Marine standards. Contactor also meets the requirements of RoHS/REACh making it a Green Premium product.