Schneider Electric LC1D95SD IEC contactor, TeSys Deca, nonreversing, 95A, 60HP at 480VAC, 3 phase, 3 pole, 3 NO, 72VDC coil, open style
Schneider Electric
$526.00
TeSys D contactors have been designed for perfect integration into control systems. They can be used to create motor starters for almost any type of application. TeSys D contactors are available in 13 contactor ratings for inductive motor applications up to 150 full-load amps and resistive loads up to 200 amps. This 95A inductive 3 pole IEC contactor can be mounted on DIN rail or mounted directly to a panel. Contactors have both Horsepower and Kw motor rating for international acceptance. Contactor is rated for 25HP at 200 to 208VAC, 30HP at 240VAC, 60HP at 480VAC and 60HP at 600VAC three phase. Contactor is also rated for 7.5HP at 115VAC and 15HP at 240VAC single phase. Contactor is supplied with a 72 VDC coil with transient suppressor module. Contactor has one normally open and one normally closed auxiliary contact built-in as standard. The NC contact is mirror certified. Screw clamp terminals are used for load and auxiliary connections. An extensive line of accessories makes it easy to meet the requirements of most applications. The contactor is 5.00 inches tall, 3.35 inches wide and 7.32 inches deep. It weighs 5.75 lbs. Contactor is certified to UL, CSA, IEC, CCC, EAC and Marine standards. Contactor also meets the requirements of RoHS/REACh making it a Green Premium product.
- Minimum Switching Voltage:
- 17 V for Signaling circuit
- Ip Degree Of Protection:
- IP20 front face IEC 60529
- Fire Resistance:
- 850°C IEC 60695-2-1
- Signaling Circuit Frequency:
- 25...400 Hz
- Climatic Withstand:
- IACS E10 exposure to damp heat
- Tightening Torque:
- control circuit 1.2 N.m screw clamp terminals flat Ø 6 mm || control circuit 1.2 N.m screw clamp terminals Philips No 2 || power circuit 12 N.m connector flat Ø 6 to Ø 8 mm || power circuit 12 N.m connector hexagonal 4 mm || control circuit 1.2 N.
- Weight:
- 2.61 kg
- [Ie] Rated Operational Current:
- 95 A (at <60°C) at <= 440 V AC-3 for power circuit || 125 A (at <60°C) at <= 690 V AC-1 for power circuit || 95 A (at <60°C) at <= 440 V AC-3e for power circuit
- Operating Altitude:
- 0...9842.52 ft (0...3000 m)
- Eu Rohs Directive:
- Compliant
- [Uc] Control Circuit Voltage:
- 72 V DC
- [Uimp] Rated Impulse Withstand Voltage:
- 8 kV IEC 60947
- Range:
- TeSys
- Maximum Operating Rate:
- 3600 cyc/h 60°C
- Width:
- 85 mm
- Safety Reliability Level:
- B10d = 1.3 Mcycles contactor with nominal load EN/ISO 13849-1 || B10d = 20 Mcycles contactor with mechanical load EN/ISO 13849-1
- Range Of Product:
- TeSys Deca
- Pvc Free:
- Yes
- Mounting Support:
- rail || plate
- Rohs Exemption Information:
- Yes
- Pollution Degree:
- 3
- Auxiliary Contact Composition:
- 1 NO + 1 NC
- Rated Breaking Capacity:
- 1100 A at 440 V for power circuit conforming to IEC 60947
- Protective Treatment:
- THIEC 60068-2-30
- Product Or Component Type:
- contactor
- Depth:
- 186 mm
- Standards:
- EN/IEC 60947-1 || EN/IEC 60947-4-1 || EN/IEC 60947-5-1 || GB/T 14048.4
- [Ith] Conventional Free Air Thermal Current:
- 10 A (at 60°C) for Signaling circuit || 125 A (at 60°C) for power circuit
- Permissible Ambient Air Temperature Around The Device:
- -40-60°C || 60-70°C with derating
- Mechanical Durability:
- 10 Mcycles
- Reach Free Of Svhc:
- Yes
- Non-Overlap Time:
- 1.5 ms on de-energisation between NC and NO contact || 1.5 ms on energisation between NC and NO contact
- Auxiliary Contacts Type:
- mechanically linked 1 NO + 1 NC IEC 60947-5-1 || mirror contact 1 NC IEC 60947-4-1
- Insulation Resistance:
- > 10 MOhm for Signaling circuit
- Associated Fuse Rating:
- 10 A gG for Signaling circuit conforming to IEC 60947-5-1 || 200 A gG at <= 690 V coordination type 1 for power circuit || 160 A gG at <= 690 V coordination type 2 for power circuit
- Mercury Free:
- Yes
- Weee:
- The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins.
- Average Impedance:
- 0.8 mOhm - Ith 125 A 50 Hz for power circuit
- Control Circuit Type:
- DC standard
- Minimum Switching Current:
- 5 mA for Signaling circuit
- Flame Retardance:
- V1 conforming to UL 94
- Control Circuit Voltage Limits:
- 0.1...0.3 Uc -40-70°C drop-out DC || 0.85...1.1 Uc -40-55°C operational DC || 1...1.1 Uc 55-70°C operational DC
- Time Constant:
- 75 ms
- Poles Description:
- 3P
- Connections - Terminals:
- control circuit: screw clamp terminals 2 1-2.5 mm² - cable stiffness: flexible with cable end || control circuit: screw clamp terminals 1 1-2.5 mm² - cable stiffness: flexible with cable end || control circuit: screw clamp terminals 1 1-4 mm² - ca
- [Ue] Rated Operational Voltage:
- power circuit <= 690 V AC 25...400 Hz
- Contactor Application:
- motor control || resistive load
- Pole Contact Composition:
- 3 NO
- Circularity Profile:
- N/A