Schneider Electric LC1DLKU7 Capacitor contactor, Tesys Deca, 20kVAR at 400/415V 50Hz, 240V AC 50/60Hz coil, screw clamp terminals
Schneider Electric
$534.00
TeSys D contactor, 3 poles (3NO), for switching 3-phase capacitor banks up to 20kVAR@400V 50Hz (33kVAR@690V). It provides a 240V 50/60Hz AC coil, 1NO+2NC instantaneous auxiliary contacts, with front mounted early make poles and pre-wired damping resistors for current limitation. For operating rates until 240 cycles/hour and environments until 60°C, it procures high reliability and durability. Compact (45mm width), DIN-rail mounting or screw fixing. Certified IEC 60947 and compliant with shunt capacitors standard IEC 60831, Green Premium product (RoHS/REACh).
- Product Name:
- TeSys LC1D.K || TeSys Deca
- Eu Rohs Directive:
- Compliant
- Net Weight:
- 0.6 kg
- Mercury Free:
- Yes
- Ip Degree Of Protection:
- IP20 front face IEC 60529
- Device Location In System:
- line interruption || inside delta interruption
- China Rohs Regulation:
- Pro-active China RoHS declaration (out of China RoHS legal scope)
- [Ue] Rated Operational Voltage:
- power circuit 690 V AC 50/60 Hz
- Warranty:
- 18 months
- Auxiliary Contacts Type:
- mechanically linked 1 NO + 2 NC IEC 60947-5-1
- [Uc] Control Circuit Voltage:
- 240 V AC 50/60 Hz
- Environmental Disclosure:
- ENVPEP111274EN
- Operating Altitude:
- 0...9842.52 ft (0...3000 m)
- Toxic Heavy Metal Free:
- Yes
- Circularity Profile:
- N/A
- Reactive Power Rating:
- 11 kvar 230-230 V AC 50 Hz 60°C || 20 kvar 400-400 V AC 50 Hz 60°C || 21 kvar 440-440 V AC 50 Hz 60°C || 33 kvar 690-690 V AC 50 Hz 60°C
- Range:
- TeSys
- Poles Description:
- 3P
- California Proposition 65:
- WARNING: This product can expose you to chemicals including: Lead and lead compounds, which is known to the State of California to cause cancer and birth defects or other reproductive harm. For more information go to www.P65Warnings.ca.gov
- Electrical Durability:
- 300000 cycles 400 V || 200000 cycles 690 V
- Rohs Exemption Information:
- Yes
- Tightening Torque:
- control circuit 1.7 N.m screw clamp terminals || power circuit 2.5 N.m screw clamp terminals
- Product Certifications:
- IECEE CB Scheme || UKCA
- Contactor Application:
- power factor correction
- Reach Free Of Svhc:
- Yes
- Weight:
- 0.6 kg
- Standards:
- EN/IEC 60947-1 || EN/IEC 60947-4-1
- Reach Regulation:
- Free of Substances of Very High Concern above the threshold
- Mounting Support:
- DIN rail || plate
- Depth:
- 127 mm
- Maximum Operating Rate:
- 240 cyc/h
- Device Short Name:
- LC1DLK
- Utilisation Category:
- AC-6b
- Ambient Air Temperature For Operation:
- -5-60°C
- Sustainable Offer Status:
- Green Premium product
- Connections - Terminals:
- control circuit: screw clamp terminals 1 1-4 mm² - cable stiffness: solid || control circuit: screw clamp terminals 2 1-4 mm² - cable stiffness: solid || control circuit: screw clamp terminals 1 1-4 mm² - cable stiffness: flexible without cable en
- Country of Origin:
- France
- Control Circuit Type:
- AC 50/60 Hz
- Auxiliary Contact Composition:
- 1 NO + 2 NC instantaneous
- Pole Contact Composition:
- 3 NO
- Ambient Air Temperature For Storage:
- -60-80°C
- Product Or Component Type:
- capacitor duty contactor
- Device Application:
- control