Schneider Electric

Schneider Electric LC1DT20P7 IEC contactor, TeSys Deca, nonreversing, 20A resistive, 4 pole, 4 NO, 230VAC 50/60Hz coil, open style

(No reviews yet) Write a Review
SKU:
LC1DT20P7
MPN:
LC1DT20P7
Condition:
New
[Ith] Conventional Free Air Thermal Current:
10 A (at 60°C) for Signaling circuit || 20 A (at 60°C) for power circuit
Weee:
The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins.
Product Or Component Type:
contactor
Pollution Degree:
3
Auxiliary Contacts Type:
mechanically linked 1 NO + 1 NC IEC 60947-5-1 || mirror contact 1 NC IEC 60947-4-1
Auxiliary Contact Composition:
1 NO + 1 NC
Height:
85 mm
Net Weight:
0.365 kg
Pvc Free:
Yes
Standards:
CSA C22.2 No 14 || EN 60947-4-1 || EN 60947-5-1 || IEC 60947-4-1 || IEC 60947-5-1 || UL 508 || IEC 60335-1
Connections - Terminals:
control circuit: screw clamp terminals 2 1-2.5 mm² - cable stiffness: flexible with cable end || control circuit: screw clamp terminals 1 1-4 mm² - cable stiffness: flexible without cable end || control circuit: screw clamp terminals 2 1-4 mm² - c
Climatic Withstand:
IACS E10 exposure to damp heat || IEC 60947-1 Annex Q category D exposure to damp heat
Heat Dissipation:
2-3 W at 50/60 Hz
Depth:
92 mm
Utilisation Category:
AC-1
Fire Resistance:
850°C IEC 60695-2-1
Irms Rated Making Capacity:
140 A AC for Signaling circuit conforming to IEC 60947-5-1 || 250 A DC for Signaling circuit conforming to IEC 60947-5-1 || 250 A at 440 V for power circuit conforming to IEC 60947
Associated Fuse Rating:
10 A gG for Signaling circuit conforming to IEC 60947-5-1 || 25 A gG at <= 690 V coordination type 1 for power circuit || 20 A gG at <= 690 V coordination type 2 for power circuit
Inrush Power In Va:
70-70 VA 60 Hz cos phi 0.75 (at 20°C) || 70-70 VA 50 Hz cos phi 0.75 (at 20°C)
Average Impedance:
2.5 mOhm - Ith 20 A 50 Hz for power circuit
[Ue] Rated Operational Voltage:
power circuit <= 690 V AC 25...400 Hz || power circuit <= 300 V DC
Range:
TeSys || TeSys Deca
Permissible Ambient Air Temperature Around The Device:
-40-60°C || 60-70°C with derating
Minimum Switching Voltage:
17 V for Signaling circuit
Compatibility Code:
LC1D
Operating Time:
4...19 ms opening || 12...22 ms closing
Poles Description:
4P
Safety Reliability Level:
B10d = 1369863 cycles contactor with nominal load EN/ISO 13849-1 || B10d = 20000000 cycles contactor with mechanical load EN/ISO 13849-1
Tightening Torque:
control circuit 1.7 N.m screw clamp terminals flat Ø 6 mm || control circuit 1.7 N.m screw clamp terminals Philips No 2 || power circuit 1.7 N.m screw clamp terminals flat Ø 6 mm || power circuit 1.7 N.m screw clamp terminals Philips No 2 || contro
Power Dissipation Per Pole:
1.56 W AC-1
Operating Altitude:
0...9842.52 ft (0...3000 m)
Circularity Profile:
ENVEOLI1501004
Device Short Name:
LC1D
Weight:
0.365 kg
[Icw] Rated Short-Time Withstand Current:
30 A 40°C - 10 min for power circuit || 61 A 40°C - 1 min for power circuit || 105 A 40°C - 10 s for power circuit || 210 A 40°C - 1 s for power circuit || 100 A - 1 s for Signaling circuit || 120 A - 500 ms for Signaling circuit || 140 A - 100 ms fo
Mounting Support:
plate || rail
Minimum Switching Current:
5 mA for Signaling circuit
Country of Origin:
France
Protective Treatment:
THIEC 60068-2-30
Mercury Free:
Yes
Overvoltage Category:
III
Contactor Application:
resistive load
Hold-In Power Consumption In Va:
7.5-7.5 VA 60 Hz cos phi 0.3 (at 20°C) || 7-7 VA 50 Hz cos phi 0.3 (at 20°C)
Eu Rohs Directive:
Compliant
Non-Overlap Time:
1.5 ms on de-energisation between NC and NO contact || 1.5 ms on energisation between NC and NO contact
Product Certifications:
CCC || DNV || RINA || UL || BV || LROS (Lloyds register of shipping) || GOST || CSA || GL
Environmental Disclosure:
ENVPEP1501004
$126.00

Description

TeSys D contactors have been designed for perfect integration into control systems. They can be used to create motor starters for almost any type of application. TeSys D contactors are available in 13 contactor ratings for inductive motor applications up to 150 full-load amps and resistive loads up to 200 amps. This 4 pole IEC contactor can be mounted on DIN rail or mounted directly to a panel. Contactor has four normally open power contacts. Power contacts have a 20A resistive load rating. Contactor is supplied with a 230 VAC 50/60 Hz coil. Contactor has one normally open and one normally closed auxiliary contact built-in as standard. The NC contact is mirror certified. Screw clamp terminals are used for load and auxiliary connections. An extensive line of accessories makes it easy to meet the requirements of most applications. The contactor is 3.35 inches tall, 1.77 inches wide and 3.62 inches deep. It weighs 0.80 lbs. Contactor is certified to UL, CSA, IEC, CCC, EAC and Marine standards. Contactor also meets the requirements of RoHS/REACh making it a Green Premium product.
View AllClose