Schneider Electric

Schneider Electric LC1DT20U7 IEC contactor, TeSys Deca, nonreversing, 20A resistive, 4 pole, 4 NO, 240VAC 50/60Hz coil, open style

(No reviews yet) Write a Review
SKU:
LC1DT20U7
MPN:
LC1DT20U7
Condition:
New
Utilisation Category:
AC-1
Rohs Exemption Information:
Yes
Permissible Ambient Air Temperature Around The Device:
-40-60°C || 60-70°C with derating
[Ui] Rated Insulation Voltage:
power circuit 600 V CSA || power circuit 600 V UL || Signaling circuit 690 V IEC 60947-1 || Signaling circuit 600 V CSA || Signaling circuit 600 V UL || power circuit 690 V IEC 60947-4-1
Tightening Torque:
control circuit 1.7 N.m screw clamp terminals flat Ø 6 mm || control circuit 1.7 N.m screw clamp terminals Philips No 2 || power circuit 1.7 N.m screw clamp terminals flat Ø 6 mm || power circuit 1.7 N.m screw clamp terminals Philips No 2 || contro
Signaling Circuit Frequency:
25...400 Hz
Insulation Resistance:
> 10 MOhm for Signaling circuit
Ip Degree Of Protection:
IP20 front face IEC 60529
Heat Dissipation:
2-3 W at 50/60 Hz
[Ie] Rated Operational Current:
20 A (at <60°C) at <= 440 V AC AC-1 for power circuit
Overvoltage Category:
III
Range Of Product:
TeSys Deca
Fire Resistance:
850°C IEC 60695-2-1
Poles Description:
4P
Safety Reliability Level:
B10d = 1369863 cycles contactor with nominal load EN/ISO 13849-1 || B10d = 20000000 cycles contactor with mechanical load EN/ISO 13849-1
Height:
85 mm
Circularity Profile:
ENVEOLI1501004
Protective Treatment:
THIEC 60068-2-30
Minimum Switching Voltage:
17 V for Signaling circuit
Product Or Component Type:
contactor
Auxiliary Contacts Type:
mechanically linked 1 NO + 1 NC IEC 60947-5-1 || mirror contact 1 NC IEC 60947-4-1
Control Circuit Voltage Limits:
0.3...0.6 Uc -40-70°C drop-out AC 50/60 Hz || 0.8...1.1 Uc -40-60°C operational AC 50 Hz || 0.85...1.1 Uc -40-60°C operational AC 60 Hz || 1...1.1 Uc 60-70°C operational AC 50/60 Hz
Toxic Heavy Metal Free:
Yes
Sustainable Offer Status:
Green Premium product
Climatic Withstand:
IACS E10 exposure to damp heat || IEC 60947-1 Annex Q category D exposure to damp heat
Net Weight:
0.365 kg
Mechanical Durability:
15 Mcycles
[Ith] Conventional Free Air Thermal Current:
10 A (at 60°C) for Signaling circuit || 20 A (at 60°C) for power circuit
Depth:
92 mm
Mounting Support:
plate || rail
Pole Contact Composition:
4 NO
Average Impedance:
2.5 mOhm - Ith 20 A 50 Hz for power circuit
Mechanical Robustness:
vibrations contactor open 2 Gn, 5...300 Hz) || vibrations contactor closed 4 Gn, 5...300 Hz) || shocks contactor closed 15 Gn for 11 ms) || shocks contactor open 10 Gn for 11 ms)
Country of Origin:
France
[Icw] Rated Short-Time Withstand Current:
30 A 40°C - 10 min for power circuit || 61 A 40°C - 1 min for power circuit || 105 A 40°C - 10 s for power circuit || 210 A 40°C - 1 s for power circuit || 100 A - 1 s for Signaling circuit || 120 A - 500 ms for Signaling circuit || 140 A - 100 ms fo
Minimum Switching Current:
5 mA for Signaling circuit
Weight:
0.365 kg
Inrush Power In Va:
70-70 VA 60 Hz cos phi 0.75 (at 20°C) || 70-70 VA 50 Hz cos phi 0.75 (at 20°C)
Protective Cover:
with
Connections - Terminals:
control circuit: screw clamp terminals 2 1-2.5 mm² - cable stiffness: flexible with cable end || control circuit: screw clamp terminals 1 1-4 mm² - cable stiffness: flexible without cable end || control circuit: screw clamp terminals 2 1-4 mm² - c
Maximum Operating Rate:
3600 cyc/h 60°C
Flame Retardance:
V1 conforming to UL 94
Rated Breaking Capacity:
250 A at 440 V for power circuit conforming to IEC 60947
Irms Rated Making Capacity:
140 A AC for Signaling circuit conforming to IEC 60947-5-1 || 250 A DC for Signaling circuit conforming to IEC 60947-5-1 || 250 A at 440 V for power circuit conforming to IEC 60947
[Uimp] Rated Impulse Withstand Voltage:
6 kV IEC 60947
Auxiliary Contact Composition:
1 NO + 1 NC
Compatibility Code:
LC1D
Standards:
CSA C22.2 No 14 || EN 60947-4-1 || EN 60947-5-1 || IEC 60947-4-1 || IEC 60947-5-1 || UL 508 || IEC 60335-1
$126.00

Description

TeSys D contactors have been designed for perfect integration into control systems. They can be used to create motor starters for almost any type of application. TeSys D contactors are available in 13 contactor ratings for inductive motor applications up to 150 full-load amps and resistive loads up to 200 amps. This 4 pole IEC contactor can be mounted on DIN rail or mounted directly to a panel. Contactor has four normally open power contacts. Power contacts have a 20A resistive load rating. Contactor is supplied with a 240 VAC 50/60 Hz coil. Contactor has one normally open and one normally closed auxiliary contact built-in as standard. The NC contact is mirror certified. Screw clamp terminals are used for load and auxiliary connections. An extensive line of accessories makes it easy to meet the requirements of most applications. The contactor is 3.35 inches tall, 1.77 inches wide and 3.62 inches deep. It weighs 0.80 lbs. Contactor is certified to UL, CSA, IEC, CCC, EAC and Marine standards. Contactor also meets the requirements of RoHS/REACh making it a Green Premium product.
View AllClose