Schneider Electric LC1DT256M7 IEC contactor, TeSys Deca, nonreversing, 25A resistive, 4 pole, 4 NO, 220VAC 50/60Hz coil, open style
Schneider Electric
$159.60
TeSys D contactors have been designed for perfect integration into control systems. They can be used to create motor starters for almost any type of application. TeSys D contactors are available in 13 contactor ratings for inductive motor applications up to 150 full-load amps and resistive loads up to 200 amps. This 4 pole IEC contactor can be mounted on DIN rail or mounted directly to a panel. Contactor has four normally open power contacts. Power contacts have a 25A resistive load rating. Contactor is supplied with a 220 VAC 50/60 Hz coil. Contactor has one normally open and one normally closed auxiliary contact built-in as standard. The NC contact is mirror certified. Ring-lug screw terminals are used for load and auxiliary connections. An extensive line of accessories makes it easy to meet the requirements of most applications. The contactor is 3.35 inches tall, 1.77 inches wide and 3.62 inches deep. It weighs 0.80 lbs. Contactor is certified to UL, CSA, IEC, CCC, EAC and Marine standards. Contactor also meets the requirements of RoHS/REACh making it a Green Premium product.
- Sustainable Offer Status:
- Green Premium product
- Power Dissipation Per Pole:
- 1.56 W AC-1
- Country of Origin:
- Indonesia
- Rated Breaking Capacity:
- 250 A at 440 V for power circuit conforming to IEC 60947
- Average Impedance:
- 2.5 mOhm - Ith 25 A 50 Hz for power circuit
- Associated Fuse Rating:
- 10 A gG for Signaling circuit conforming to IEC 60947-5-1 || 40 A gG at <= 690 V coordination type 1 for power circuit || 25 A gG at <= 690 V coordination type 2 for power circuit
- [Ith] Conventional Free Air Thermal Current:
- 10 A (at 60°C) for Signaling circuit || 25 A (at 60°C) for power circuit
- Heat Dissipation:
- 2-3 W at 50/60 Hz
- Maximum Operating Rate:
- 3600 cyc/h 60°C
- Pollution Degree:
- 3
- China Rohs Regulation:
- Pro-active China RoHS declaration (out of China RoHS legal scope)
- Ip Degree Of Protection:
- IP20 front face IEC 60529
- Protective Treatment:
- THIEC 60068-2-30
- Pvc Free:
- Yes
- Device Short Name:
- LC1D
- Depth:
- 92 mm
- Safety Reliability Level:
- B10d = 1369863 cycles contactor with nominal load EN/ISO 13849-1 || B10d = 20000000 cycles contactor with mechanical load EN/ISO 13849-1
- Hold-In Power Consumption In Va:
- 7.5-7.5 VA 60 Hz cos phi 0.3 (at 20°C) || 7-7 VA 50 Hz cos phi 0.3 (at 20°C)
- Fire Resistance:
- 850°C IEC 60695-2-1
- Compatibility Code:
- LC1D
- Standards:
- CSA C22.2 No 14 || EN 60947-4-1 || EN 60947-5-1 || IEC 60947-4-1 || IEC 60947-5-1 || UL 508 || IEC 60335-1
- Non-Overlap Time:
- 1.5 ms on de-energisation between NC and NO contact || 1.5 ms on energisation between NC and NO contact
- Contactor Application:
- resistive load
- Circularity Profile:
- ENVEOLI1501004
- Tightening Torque:
- control circuit 1.7 N.m lugs-ring terminals flat Ø 6 mm M3.5 || control circuit 1.7 N.m lugs-ring terminals Philips No 2 M3.5 || power circuit 1.7 N.m lugs-ring terminals flat Ø 6 mm M3.5 || power circuit 1.7 N.m lugs-ring terminals Philips No 2 M3
- Reach Regulation:
- Reference contains Substances of Very High Concern above the threshold
- Flame Retardance:
- V1 conforming to UL 94
- Environmental Disclosure:
- ENVPEP1501004
- Operating Time:
- 4...19 ms opening || 12...22 ms closing
- Weee:
- The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins.
- Protective Cover:
- with
- Control Circuit Voltage Limits:
- 0.3...0.6 Uc -40-70°C drop-out AC 50/60 Hz || 0.8...1.1 Uc -40-60°C operational AC 50 Hz || 0.85...1.1 Uc -40-60°C operational AC 60 Hz || 1...1.1 Uc 60-70°C operational AC 50/60 Hz
- Product Certifications:
- DNV || GL || CCC || LROS (Lloyds register of shipping) || RINA || BV || GOST || UL || CSA || CB
- Pole Contact Composition:
- 4 NO
- Connections - Terminals:
- control circuit: lugs-ring terminals - external diameter: 8 mm || power circuit: lugs-ring terminals - external diameter: 8 mm
- Width:
- 45 mm
- Permissible Ambient Air Temperature Around The Device:
- -40-60°C || 60-70°C with derating
- [Icw] Rated Short-Time Withstand Current:
- 30 A 40°C - 10 min for power circuit || 61 A 40°C - 1 min for power circuit || 105 A 40°C - 10 s for power circuit || 210 A 40°C - 1 s for power circuit || 100 A - 1 s for Signaling circuit || 120 A - 500 ms for Signaling circuit || 140 A - 100 ms fo
- [Uc] Control Circuit Voltage:
- 220 V AC 50/60 Hz
- Minimum Switching Voltage:
- 17 V for Signaling circuit
- [Uimp] Rated Impulse Withstand Voltage:
- 6 kV IEC 60947
- Mounting Support:
- plate || rail
- Climatic Withstand:
- IACS E10 exposure to damp heat || IEC 60947-1 Annex Q category D exposure to damp heat
- Auxiliary Contact Composition:
- 1 NO + 1 NC
- Warranty:
- 18 months
- Minimum Switching Current:
- 5 mA for Signaling circuit
- Signaling Circuit Frequency:
- 25...400 Hz
- Utilisation Category:
- AC-1 || AC-3 || AC-3e || AC-4
- Poles Description:
- 4P
- Insulation Resistance:
- > 10 MOhm for Signaling circuit