Schneider Electric LC1DT25E7 IEC contactor, TeSys Deca, nonreversing, 25A resistive, 4 pole, 4 NO, 48VAC 50/60Hz coil, open style
Schneider Electric
$159.60
TeSys D contactors have been designed for perfect integration into control systems. They can be used to create motor starters for almost any type of application. TeSys D contactors are available in 13 contactor ratings for inductive motor applications up to 150 full-load amps and resistive loads up to 200 amps. This 4 pole IEC contactor can be mounted on DIN rail or mounted directly to a panel. Contactor has four normally open power contacts. Power contacts have a 25A resistive load rating. Contactor is supplied with a 48 VAC 50/60 Hz coil. Contactor has one normally open and one normally closed auxiliary contact built-in as standard. The NC contact is mirror certified. Screw clamp terminals are used for load and auxiliary connections. An extensive line of accessories makes it easy to meet the requirements of most applications. The contactor is 3.35 inches tall, 1.77 inches wide and 3.62 inches deep. It weighs 0.80 lbs. Contactor is certified to UL, CSA, IEC, CCC, EAC and Marine standards. Contactor also meets the requirements of RoHS/REACh making it a Green Premium product.
- [Ui] Rated Insulation Voltage:
- power circuit 600 V CSA || power circuit 600 V UL || Signaling circuit 690 V IEC 60947-1 || Signaling circuit 600 V CSA || Signaling circuit 600 V UL || power circuit 690 V IEC 60947-4-1
- Environmental Disclosure:
- ENVPEP1501004
- Device Short Name:
- LC1D
- Protective Treatment:
- THIEC 60068-2-30
- Mechanical Durability:
- 15 Mcycles
- Warranty:
- 18 months
- Product Certifications:
- DNV || GL || CCC || LROS (Lloyds register of shipping) || RINA || BV || GOST || UL || CSA || CB
- Insulation Resistance:
- > 10 MOhm for Signaling circuit
- [Icw] Rated Short-Time Withstand Current:
- 30 A 40°C - 10 min for power circuit || 61 A 40°C - 1 min for power circuit || 105 A 40°C - 10 s for power circuit || 210 A 40°C - 1 s for power circuit || 100 A - 1 s for Signaling circuit || 120 A - 500 ms for Signaling circuit || 140 A - 100 ms fo
- Weee:
- The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins.
- Mercury Free:
- Yes
- Pollution Degree:
- 3
- Minimum Switching Voltage:
- 17 V for Signaling circuit
- [Ith] Conventional Free Air Thermal Current:
- 10 A (at 60°C) for Signaling circuit || 25 A (at 60°C) for power circuit
- Toxic Heavy Metal Free:
- Yes
- Heat Dissipation:
- 2-3 W at 50/60 Hz
- Net Weight:
- 0.365 kg
- Circularity Profile:
- ENVEOLI1501004
- Compatibility Code:
- LC1D
- Rohs Exemption Information:
- Yes
- Inrush Power In Va:
- 70-70 VA 60 Hz cos phi 0.75 (at 20°C) || 70-70 VA 50 Hz cos phi 0.75 (at 20°C)
- Fire Resistance:
- 850°C IEC 60695-2-1
- [Ue] Rated Operational Voltage:
- power circuit <= 690 V AC 25...400 Hz || power circuit <= 300 V DC
- Protective Cover:
- with
- Operating Time:
- 4...19 ms opening || 12...22 ms closing
- Rated Breaking Capacity:
- 250 A at 440 V for power circuit conforming to IEC 60947
- Tightening Torque:
- control circuit 1.7 N.m screw clamp terminals flat Ø 6 mm || control circuit 1.7 N.m screw clamp terminals Philips No 2 || power circuit 1.7 N.m screw clamp terminals flat Ø 6 mm || power circuit 1.7 N.m screw clamp terminals Philips No 2 || contro
- Non-Overlap Time:
- 1.5 ms on de-energisation between NC and NO contact || 1.5 ms on energisation between NC and NO contact
- Standards:
- CSA C22.2 No 14 || EN 60947-4-1 || EN 60947-5-1 || IEC 60947-4-1 || IEC 60947-5-1 || UL 508 || IEC 60335-1
- Reach Regulation:
- Reference contains Substances of Very High Concern above the threshold
- Sustainable Offer Status:
- Green Premium product
- Control Circuit Type:
- AC 50/60 Hz
- [Ie] Rated Operational Current:
- 25 A (at <60°C) at <= 440 V AC AC-1 for power circuit
- Safety Reliability Level:
- B10d = 1369863 cycles contactor with nominal load EN/ISO 13849-1 || B10d = 20000000 cycles contactor with mechanical load EN/ISO 13849-1
- Maximum Operating Rate:
- 3600 cyc/h 60°C
- Utilisation Category:
- AC-1 || AC-3 || AC-3e || AC-4
- Range:
- TeSys || TeSys Deca
- Electrical Durability:
- 0.8 Mcycles 25 A AC-1 <= 440 V
- [Uimp] Rated Impulse Withstand Voltage:
- 6 kV IEC 60947
- Height:
- 85 mm
- Pole Contact Composition:
- 4 NO
- China Rohs Regulation:
- Pro-active China RoHS declaration (out of China RoHS legal scope)
- Overvoltage Category:
- III
- Permissible Ambient Air Temperature Around The Device:
- -40-60°C || 60-70°C with derating
- Width:
- 45 mm
- Coil Technology:
- without built-in suppressor module
- Climatic Withstand:
- IACS E10 exposure to damp heat || IEC 60947-1 Annex Q category D exposure to damp heat
- Hold-In Power Consumption In Va:
- 7.5-7.5 VA 60 Hz cos phi 0.3 (at 20°C) || 7-7 VA 50 Hz cos phi 0.3 (at 20°C)
- Eu Rohs Directive:
- Compliant