Schneider Electric LC1DT40BD IEC contactor, TeSys Deca, nonreversing, 40A resistive, 4 pole, 4 NO, 24VDC coil, open style
Schneider Electric
$245.70
TeSys D contactors have been designed for perfect integration into control systems. They can be used to create motor starters for almost any type of application. TeSys D contactors are available in 13 contactor ratings for inductive motor applications up to 150 full-load amps and resistive loads up to 200 amps. This 4 pole IEC contactor can be mounted on DIN rail or mounted directly to a panel. Contactor has four normally open power contacts. Power contacts have a 40A resistive load rating. Contactor is supplied with a 24 VDC coil with transient suppressor module. Contactor has one normally open and one normally closed auxiliary contact built-in as standard. The NC contact is mirror certified. Screw clamp terminals are used for load and auxiliary connections. An extensive line of accessories makes it easy to meet the requirements of most applications. The contactor is 3.58 inches tall, 1.77 inches wide and 4.21 inches deep. It weighs 0.94 lbs. Contactor is certified to UL, CSA, IEC, CCC, EAC and Marine standards. Contactor also meets the requirements of RoHS/REACh making it a Green Premium product.
- Mechanical Robustness:
- vibrations contactor open 2 Gn, 5...300 Hz) || vibrations contactor closed 4 Gn, 5...300 Hz) || shocks contactor closed 15 Gn for 11 ms) || shocks contactor open 8 Gn for 11 ms)
- Warranty:
- 18 months
- China Rohs Regulation:
- Pro-active China RoHS declaration (out of China RoHS legal scope)
- Product Or Component Type:
- contactor
- Width:
- 45 mm
- Circularity Profile:
- ENVEOLI1102030EN
- Mechanical Durability:
- 30 Mcycles
- Operating Time:
- 20±20 % ms opening || 63±15 % ms closing
- Rated Breaking Capacity:
- 450 A at 440 V for power circuit conforming to IEC 60947
- Hold-In Power Consumption In W:
- 5.4-5.4 W 20°C
- [Ith] Conventional Free Air Thermal Current:
- 10 A (at 60°C) for Signaling circuit || 40 A (at 60°C) for power circuit
- Signaling Circuit Frequency:
- 25...400 Hz
- Toxic Heavy Metal Free:
- Yes
- [Uimp] Rated Impulse Withstand Voltage:
- 6 kV IEC 60947
- Utilisation Category:
- AC-1 || AC-3 || AC-3e || AC-4
- Associated Fuse Rating:
- 10 A gG for Signaling circuit conforming to IEC 60947-5-1 || 63 A gG at <= 690 V coordination type 1 for power circuit || 40 A gG at <= 690 V coordination type 2 for power circuit
- Control Circuit Type:
- DC standard
- Sustainable Offer Status:
- Green Premium product
- Non-Overlap Time:
- 1.5 ms on de-energisation between NC and NO contact || 1.5 ms on energisation between NC and NO contact
- Product Certifications:
- DNV || GL || CCC || LROS (Lloyds register of shipping) || RINA || BV || GOST || UL || CSA || CB
- Time Constant:
- 28 ms
- Safety Reliability Level:
- B10d = 1369863 cycles contactor with nominal load EN/ISO 13849-1 || B10d = 20000000 cycles contactor with mechanical load EN/ISO 13849-1
- Depth:
- 107 mm
- Insulation Resistance:
- > 10 MOhm for Signaling circuit
- Connections - Terminals:
- control circuit: screw clamp terminals 2 1-2.5 mm² - cable stiffness: flexible with cable end || control circuit: screw clamp terminals 1 1-4 mm² - cable stiffness: flexible without cable end || control circuit: screw clamp terminals 2 1-4 mm² - c
- Power Dissipation Per Pole:
- 3.2 W AC-1
- Pole Contact Composition:
- 4 NO
- Tightening Torque:
- control circuit 1.7 N.m screw clamp terminals flat Ø 6 mm || control circuit 1.7 N.m screw clamp terminals Philips No 2 || control circuit 1.7 N.m screw clamp terminals pozidriv No 2 || power circuit 1.8 N.m screw clamps terminals flat Ø 6 mm || po
- Minimum Switching Voltage:
- 17 V for Signaling circuit
- Contactor Application:
- resistive load
- Standards:
- CSA C22.2 No 14 || EN 60947-4-1 || EN 60947-5-1 || IEC 60947-4-1 || IEC 60947-5-1 || UL 508 || IEC 60335-1
- Ip Degree Of Protection:
- IP20 front face IEC 60529
- Device Short Name:
- LC1D
- [Ie] Rated Operational Current:
- 40 A (at <60°C) at <= 440 V AC AC-1 for power circuit
- Climatic Withstand:
- IACS E10 exposure to damp heat || IEC 60947-1 Annex Q category D exposure to damp heat
- Range:
- TeSys || TeSys Deca
- Reach Regulation:
- Reference contains Substances of Very High Concern above the threshold
- Weight:
- 0.425 kg
- Control Circuit Voltage Limits:
- 0.1...0.25 Uc -40-70°C drop-out DC || 0.7...1.25 Uc -40-60°C operational DC || 1...1.25 Uc 60-70°C operational DC
- Inrush Power In W:
- 5.4-5.4 W 20°C)
- Environmental Disclosure:
- ENVPEP110230EN
- Minimum Switching Current:
- 5 mA for Signaling circuit
- Weee:
- The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins.
- Electrical Durability:
- 1.4 Mcycles 40 A AC-1 <= 440 V
- [Ui] Rated Insulation Voltage:
- power circuit 600 V CSA || power circuit 600 V UL || Signaling circuit 690 V IEC 60947-1 || Signaling circuit 600 V CSA || Signaling circuit 600 V UL || power circuit 690 V IEC 60947-4-1
- Maximum Operating Rate:
- 3600 cyc/h 60°C
- Mercury Free:
- Yes
- Rohs Exemption Information:
- Yes
- Eu Rohs Directive:
- Compliant
- Height:
- 91 mm