Schneider Electric

Schneider Electric LC1DT40D7 IEC contactor, TeSys Deca, nonreversing, 40A resistive, 4 pole, 4 NO, 42VAC 50/60Hz coil, open style

(No reviews yet) Write a Review
SKU:
LC1DT40D7
MPN:
LC1DT40D7
Condition:
New
Minimum Switching Current:
5 mA for Signaling circuit
Protective Cover:
with
Poles Description:
4P
Weee:
The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins.
Power Dissipation Per Pole:
3.2 W AC-1
Pvc Free:
Yes
Overvoltage Category:
III
[Icw] Rated Short-Time Withstand Current:
50 A 40°C - 10 min for power circuit || 120 A 40°C - 1 min for power circuit || 240 A 40°C - 10 s for power circuit || 380 A 40°C - 1 s for power circuit || 100 A - 1 s for Signaling circuit || 120 A - 500 ms for Signaling circuit || 140 A - 100 ms f
Fire Resistance:
850°C IEC 60695-2-1
Range:
TeSys || TeSys Deca
Climatic Withstand:
IACS E10 exposure to damp heat || IEC 60947-1 Annex Q category D exposure to damp heat
Pole Contact Composition:
4 NO
Connections - Terminals:
control circuit: screw clamp terminals 2 1-2.5 mm² - cable stiffness: flexible with cable end || control circuit: screw clamp terminals 1 1-4 mm² - cable stiffness: flexible without cable end || control circuit: screw clamp terminals 2 1-4 mm² - c
[Uc] Control Circuit Voltage:
42 V AC 50/60 Hz
Standards:
CSA C22.2 No 14 || EN 60947-4-1 || EN 60947-5-1 || IEC 60947-4-1 || IEC 60947-5-1 || UL 508 || IEC 60335-1
Average Impedance:
2 mOhm - Ith 40 A 50 Hz for power circuit
Signaling Circuit Frequency:
25...400 Hz
Compatibility Code:
LC1D
[Ui] Rated Insulation Voltage:
power circuit 600 V CSA || power circuit 600 V UL || Signaling circuit 690 V IEC 60947-1 || Signaling circuit 600 V CSA || Signaling circuit 600 V UL || power circuit 690 V IEC 60947-4-1
[Uimp] Rated Impulse Withstand Voltage:
6 kV IEC 60947
Coil Technology:
without built-in suppressor module
Non-Overlap Time:
1.5 ms on de-energisation between NC and NO contact || 1.5 ms on energisation between NC and NO contact
[Ie] Rated Operational Current:
40 A (at <60°C) at <= 440 V AC AC-1 for power circuit
Hold-In Power Consumption In Va:
7.5-7.5 VA 60 Hz cos phi 0.3 (at 20°C) || 7-7 VA 50 Hz cos phi 0.3 (at 20°C)
Net Weight:
0.425 kg
Rohs Exemption Information:
Yes
Width:
45 mm
Auxiliary Contact Composition:
1 NO + 1 NC
Insulation Resistance:
> 10 MOhm for Signaling circuit
Associated Fuse Rating:
10 A gG for Signaling circuit conforming to IEC 60947-5-1 || 63 A gG at <= 690 V coordination type 1 for power circuit || 40 A gG at <= 690 V coordination type 2 for power circuit
Electrical Durability:
1.4 Mcycles 40 A AC-1 <= 440 V
Minimum Switching Voltage:
17 V for Signaling circuit
Weight:
0.425 kg
Safety Reliability Level:
B10d = 1369863 cycles contactor with nominal load EN/ISO 13849-1 || B10d = 20000000 cycles contactor with mechanical load EN/ISO 13849-1
Pollution Degree:
3
Eu Rohs Directive:
Compliant
Maximum Operating Rate:
3600 cyc/h 60°C
Heat Dissipation:
2-3 W at 50/60 Hz
Utilisation Category:
AC-1 || AC-3 || AC-3e || AC-4
Warranty:
18 months
Mechanical Durability:
15 Mcycles
Permissible Ambient Air Temperature Around The Device:
-40-60°C || 60-70°C with derating
Rated Breaking Capacity:
450 A at 440 V for power circuit conforming to IEC 60947
Environmental Disclosure:
ENVPEP110229EN
Device Short Name:
LC1D
Ip Degree Of Protection:
IP20 front face IEC 60529
Circularity Profile:
ENVEOLI110229EN
$235.56

Description

TeSys D contactors have been designed for perfect integration into control systems. They can be used to create motor starters for almost any type of application. TeSys D contactors are available in 13 contactor ratings for inductive motor applications up to 150 full-load amps and resistive loads up to 200 amps. This 4 pole IEC contactor can be mounted on DIN rail or mounted directly to a panel. Contactor has four normally open power contacts. Power contacts have a 40A resistive load rating. Contactor is supplied with a 42 VAC 50/60 Hz coil. Contactor has one normally open and one normally closed auxiliary contact built-in as standard. The NC contact is mirror certified. Screw clamp terminals are used for load and auxiliary connections. An extensive line of accessories makes it easy to meet the requirements of most applications. The contactor is 3.58 inches tall, 1.77 inches wide and 3.90 inches deep. It weighs 0.94 lbs. Contactor is certified to UL, CSA, IEC, CCC, EAC and Marine standards. Contactor also meets the requirements of RoHS/REACh making it a Green Premium product.
View AllClose