Schneider Electric LC1DT40FD IEC contactor, TeSys Deca, nonreversing, 40A resistive, 4 pole, 4 NO, 110VDC coil, open style
Schneider Electric
$245.70
TeSys D contactors have been designed for perfect integration into control systems. They can be used to create motor starters for almost any type of application. TeSys D contactors are available in 13 contactor ratings for inductive motor applications up to 150 full-load amps and resistive loads up to 200 amps. This 4 pole IEC contactor can be mounted on DIN rail or mounted directly to a panel. Contactor has four normally open power contacts. Power contacts have a 40A resistive load rating. Contactor is supplied with a 110 VDC coil with transient suppressor module. Contactor has one normally open and one normally closed auxiliary contact built-in as standard. The NC contact is mirror certified. Screw clamp terminals are used for load and auxiliary connections. An extensive line of accessories makes it easy to meet the requirements of most applications. The contactor is 3.58 inches tall, 1.77 inches wide and 4.21 inches deep. It weighs 0.94 lbs. Contactor is certified to UL, CSA, IEC, CCC, EAC and Marine standards. Contactor also meets the requirements of RoHS/REACh making it a Green Premium product.
- Mechanical Robustness:
- vibrations contactor open 2 Gn, 5...300 Hz) || vibrations contactor closed 4 Gn, 5...300 Hz) || shocks contactor closed 15 Gn for 11 ms) || shocks contactor open 8 Gn for 11 ms)
- Overvoltage Category:
- III
- Associated Fuse Rating:
- 10 A gG for Signaling circuit conforming to IEC 60947-5-1 || 63 A gG at <= 690 V coordination type 1 for power circuit || 40 A gG at <= 690 V coordination type 2 for power circuit
- Irms Rated Making Capacity:
- 140 A AC for Signaling circuit conforming to IEC 60947-5-1 || 250 A DC for Signaling circuit conforming to IEC 60947-5-1 || 450 A at 440 V for power circuit conforming to IEC 60947
- Depth:
- 107 mm
- Environmental Disclosure:
- ENVPEP110230EN
- Product Or Component Type:
- contactor
- Pole Contact Composition:
- 4 NO
- Device Short Name:
- LC1D
- Mercury Free:
- Yes
- Auxiliary Contacts Type:
- mechanically linked 1 NO + 1 NC IEC 60947-5-1 || mirror contact 1 NC IEC 60947-4-1
- Country of Origin:
- France
- [Uimp] Rated Impulse Withstand Voltage:
- 6 kV IEC 60947
- Protective Treatment:
- THIEC 60068-2-30
- Connections - Terminals:
- control circuit: screw clamp terminals 2 1-2.5 mm² - cable stiffness: flexible with cable end || control circuit: screw clamp terminals 1 1-4 mm² - cable stiffness: flexible without cable end || control circuit: screw clamp terminals 2 1-4 mm² - c
- [Icw] Rated Short-Time Withstand Current:
- 50 A 40°C - 10 min for power circuit || 120 A 40°C - 1 min for power circuit || 240 A 40°C - 10 s for power circuit || 380 A 40°C - 1 s for power circuit || 100 A - 1 s for Signaling circuit || 120 A - 500 ms for Signaling circuit || 140 A - 100 ms f
- Sustainable Offer Status:
- Green Premium product
- Minimum Switching Voltage:
- 17 V for Signaling circuit
- Range:
- TeSys || TeSys Deca
- Net Weight:
- 0.425 kg
- Fire Resistance:
- 850°C IEC 60695-2-1
- Warranty:
- 18 months
- Non-Overlap Time:
- 1.5 ms on de-energisation between NC and NO contact || 1.5 ms on energisation between NC and NO contact
- Time Constant:
- 28 ms
- Safety Reliability Level:
- B10d = 1369863 cycles contactor with nominal load EN/ISO 13849-1 || B10d = 20000000 cycles contactor with mechanical load EN/ISO 13849-1
- Weight:
- 0.425 kg
- [Ie] Rated Operational Current:
- 40 A (at <60°C) at <= 440 V AC AC-1 for power circuit
- Contactor Application:
- resistive load
- Reach Regulation:
- Reference contains Substances of Very High Concern above the threshold
- Insulation Resistance:
- > 10 MOhm for Signaling circuit
- Product Certifications:
- DNV || GL || CCC || LROS (Lloyds register of shipping) || RINA || BV || GOST || UL || CSA || CB
- Permissible Ambient Air Temperature Around The Device:
- -40-60°C || 60-70°C with derating
- [Uc] Control Circuit Voltage:
- 110 V DC
- Poles Description:
- 4P
- Mounting Support:
- plate || rail
- Inrush Power In W:
- 5.4-5.4 W 20°C)
- Protective Cover:
- with
- Average Impedance:
- 2 mOhm - Ith 40 A 50 Hz for power circuit
- Hold-In Power Consumption In W:
- 5.4-5.4 W 20°C
- Power Dissipation Per Pole:
- 3.2 W AC-1
- Minimum Switching Current:
- 5 mA for Signaling circuit
- Utilisation Category:
- AC-1 || AC-3 || AC-3e || AC-4
- Signaling Circuit Frequency:
- 25...400 Hz
- Toxic Heavy Metal Free:
- Yes
- Climatic Withstand:
- IACS E10 exposure to damp heat || IEC 60947-1 Annex Q category D exposure to damp heat
- Width:
- 45 mm
- Flame Retardance:
- V1 conforming to UL 94
- Rohs Exemption Information:
- Yes
- Operating Time:
- 20±20 % ms opening || 63±15 % ms closing