Schneider Electric

Schneider Electric LC1DT40GD IEC contactor, TeSys Deca, nonreversing, 40A resistive, 4 pole, 4 NO, 125VDC coil, open style

(No reviews yet) Write a Review
SKU:
LC1DT40GD
MPN:
LC1DT40GD
Condition:
New
China Rohs Regulation:
Pro-active China RoHS declaration (out of China RoHS legal scope)
Product Or Component Type:
contactor
Rated Breaking Capacity:
450 A at 440 V for power circuit conforming to IEC 60947
Protective Cover:
with
Power Dissipation Per Pole:
3.2 W AC-1
Time Constant:
28 ms
Toxic Heavy Metal Free:
Yes
Permissible Ambient Air Temperature Around The Device:
-40-60°C || 60-70°C with derating
Range:
TeSys || TeSys Deca
Inrush Power In W:
5.4-5.4 W 20°C)
Flame Retardance:
V1 conforming to UL 94
Weight:
0.425 kg
Climatic Withstand:
IACS E10 exposure to damp heat || IEC 60947-1 Annex Q category D exposure to damp heat
Tightening Torque:
control circuit 1.7 N.m screw clamp terminals flat Ø 6 mm || control circuit 1.7 N.m screw clamp terminals Philips No 2 || control circuit 1.7 N.m screw clamp terminals pozidriv No 2 || power circuit 1.8 N.m screw clamps terminals flat Ø 6 mm || po
Rohs Exemption Information:
Yes
Average Impedance:
2 mOhm - Ith 40 A 50 Hz for power circuit
Product Certifications:
DNV || CSA || UL || GOST || BV || LROS (Lloyds register of shipping) || CCC || GL || RINA
Warranty:
18 months
Control Circuit Voltage Limits:
0.1...0.25 Uc -40-70°C drop-out DC || 0.7...1.25 Uc -40-60°C operational DC || 1...1.25 Uc 60-70°C operational DC
[Uimp] Rated Impulse Withstand Voltage:
6 kV IEC 60947
Safety Reliability Level:
B10d = 1369863 cycles contactor with nominal load EN/ISO 13849-1 || B10d = 20000000 cycles contactor with mechanical load EN/ISO 13849-1
Eu Rohs Directive:
Compliant
Connections - Terminals:
control circuit: screw clamp terminals 2 1-2.5 mm² - cable stiffness: flexible with cable end || control circuit: screw clamp terminals 1 1-4 mm² - cable stiffness: flexible without cable end || control circuit: screw clamp terminals 2 1-4 mm² - c
Pollution Degree:
3
Range Of Product:
TeSys Deca
Control Circuit Type:
DC standard
Operating Time:
20±20 % ms opening || 63±15 % ms closing
Weee:
The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins.
Protective Treatment:
THIEC 60068-2-30
Mechanical Robustness:
vibrations contactor open 2 Gn, 5...300 Hz) || vibrations contactor closed 4 Gn, 5...300 Hz) || shocks contactor closed 15 Gn for 11 ms) || shocks contactor open 8 Gn for 11 ms)
Ip Degree Of Protection:
IP20 front face IEC 60529
Reach Regulation:
Reference contains Substances of Very High Concern above the threshold
Signaling Circuit Frequency:
25...400 Hz
Compatibility Code:
LC1D
Mechanical Durability:
30 Mcycles
Non-Overlap Time:
1.5 ms on de-energisation between NC and NO contact || 1.5 ms on energisation between NC and NO contact
Irms Rated Making Capacity:
140 A AC for Signaling circuit conforming to IEC 60947-5-1 || 250 A DC for Signaling circuit conforming to IEC 60947-5-1 || 450 A at 440 V for power circuit conforming to IEC 60947
Auxiliary Contacts Type:
mechanically linked 1 NO + 1 NC IEC 60947-5-1 || mirror contact 1 NC IEC 60947-4-1
Associated Fuse Rating:
10 A gG for Signaling circuit conforming to IEC 60947-5-1 || 63 A gG at <= 690 V coordination type 1 for power circuit || 40 A gG at <= 690 V coordination type 2 for power circuit
Depth:
107 mm
Sustainable Offer Status:
Green Premium product
Pole Contact Composition:
4 NO
Maximum Operating Rate:
3600 cyc/h 60°C
[Icw] Rated Short-Time Withstand Current:
50 A 40°C - 10 min for power circuit || 120 A 40°C - 1 min for power circuit || 240 A 40°C - 10 s for power circuit || 380 A 40°C - 1 s for power circuit || 100 A - 1 s for Signaling circuit || 120 A - 500 ms for Signaling circuit || 140 A - 100 ms f
Fire Resistance:
850°C IEC 60695-2-1
[Ui] Rated Insulation Voltage:
power circuit 600 V CSA || power circuit 600 V UL || Signaling circuit 690 V IEC 60947-1 || Signaling circuit 600 V CSA || Signaling circuit 600 V UL || power circuit 690 V IEC 60947-4-1
Hold-In Power Consumption In W:
5.4-5.4 W 20°C
$245.70

Description

TeSys D contactors have been designed for perfect integration into control systems. They can be used to create motor starters for almost any type of application. TeSys D contactors are available in 13 contactor ratings for inductive motor applications up to 150 full-load amps and resistive loads up to 200 amps. This 4 pole IEC contactor can be mounted on DIN rail or mounted directly to a panel. Contactor has four normally open power contacts. Power contacts have a 40A resistive load rating. Contactor is supplied with a 125 VDC coil with transient suppressor module. Contactor has one normally open and one normally closed auxiliary contact built-in as standard. The NC contact is mirror certified. Screw clamp terminals are used for load and auxiliary connections. An extensive line of accessories makes it easy to meet the requirements of most applications. The contactor is 3.58 inches tall, 1.77 inches wide and 4.21 inches deep. It weighs 0.94 lbs. Contactor is certified to UL, CSA, IEC, CCC, EAC and Marine standards. Contactor also meets the requirements of RoHS/REACh making it a Green Premium product.