Schneider Electric LC1DT60A6KUE IEC contactor, TeSys Deca Green, nonreversing, 60A resistive, 4 pole, 4 NO, 100/250VAC/VDC coil, open style

(No reviews yet) Write a Review
SKU:
LC1DT60A6KUE
MPN:
LC1DT60A6KUE
Condition:
New
[Ui] Rated Insulation Voltage:
power circuit 690 V IEC 60947-4-1 || Signaling circuit 690 V IEC 60947-1
Rated Breaking Capacity:
800 A at 440 V for power circuit conforming to IEC 60947
Minimum Switching Current:
5 mA for Signaling circuit
Operating Time:
55...65 ms closing || 20...80 ms opening
Rohs Exemption Information:
Yes
China Rohs Regulation:
Product out of China RoHS scope. Substance declaration for your information.
Ip Degree Of Protection:
IP20 front face IEC 60529
Protective Cover:
with
Power Dissipation Per Pole:
5.8 W AC-1
Height:
122 mm
Depth:
120 mm
Pollution Degree:
3
Climatic Withstand:
IACS E10 exposure to damp heat || IEC 60947-1 Annex Q category D exposure to damp heat
Weight:
1.230 kg
[Ue] Rated Operational Voltage:
power circuit <= 690 V AC 25...400 Hz
[Uimp] Rated Impulse Withstand Voltage:
6 kV IEC 60947
Mercury Free:
Yes
Eu Rohs Directive:
Compliant with Exemptions
Control Circuit Voltage Limits:
<= 0.1 Uc -40-70°C drop-out AC/DC || 0.85...1.1 Uc -40-60°C operational AC/DC || 1...1.1 Uc 60-70°C operational AC/DC
Poles Description:
4P
Inrush Power In Va:
18-18 VA 50/60 Hz (at 20°C)
Control Circuit Type:
AC/DC 50/60 Hz AC/DC electronic
Weee:
The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins.
Range:
TeSys || TeSys Deca
Insulation Resistance:
> 10 MOhm for Signaling circuit
Standards:
EN/IEC 60947-4-1 || EN/IEC 60947-5-1 || UL 60947-4-1 || CSA C22.2 No 60947-4-1 || IEC 60335-1
Inrush Power In W:
14-14 W 20°C)
Width:
70 mm
[Ith] Conventional Free Air Thermal Current:
60 A (at 60°C) for power circuit || 10 A (at 60°C) for Signaling circuit
Overvoltage Category:
III
[Icw] Rated Short-Time Withstand Current:
72 A 40°C - 10 min for power circuit || 165 A 40°C - 1 min for power circuit || 320 A 40°C - 10 s for power circuit || 720 A 40°C - 1 s for power circuit || 100 A - 1 s for Signaling circuit || 120 A - 500 ms for Signaling circuit || 140 A - 100 ms f
Auxiliary Contacts Type:
mechanically linked 1 NO + 1 NC IEC 60947-5-1 || mirror contact 1 NC IEC 60947-4-1
Mechanical Robustness:
vibrations contactor open 2 Gn, 5...300 Hz) || vibrations contactor closed 4 Gn, 5...300 Hz) || shocks contactor open 10 Gn for 11 ms) || shocks contactor closed 15 Gn for 11 ms)
Minimum Switching Voltage:
17 V for Signaling circuit
Warranty:
18 months
Device Short Name:
LC1D
Average Impedance:
1.6 mOhm - Ith 60 A 50 Hz for power circuit
Associated Fuse Rating:
80 A gG at <= 690 V coordination type 1 for power circuit || 80 A gG at <= 690 V coordination type 2 for power circuit || 10 A gG for Signaling circuit conforming to IEC 60947-5-1
Hold-In Power Consumption In Va:
1.8-1.8 VA 50/60 Hz (at 20°C)
Net Weight:
1.230 kg
Utilisation Category:
AC-1
Tightening Torque:
control circuit 1.7 N.m lugs-ring terminals flat Ø 6 mm M3.5 || control circuit 1.7 N.m lugs-ring terminals Philips No 2 M3.5 || power circuit 6 N.m lugs-ring terminals hexagonal 10 mm M6 || power circuit 6 N.m lugs-ring terminals pozidriv No 2 M4 |
Circularity Profile:
ENVEOLI1607010EN
Compatibility Code:
LC1D
Fire Resistance:
850°C IEC 60695-2-1
Signaling Circuit Frequency:
25...400 Hz
Irms Rated Making Capacity:
800 A at 440 V for power circuit conforming to IEC 60947 || 140 A AC for Signaling circuit conforming to IEC 60947-5-1 || 250 A DC for Signaling circuit conforming to IEC 60947-5-1
Environmental Disclosure:
ENVPEP1607010EN
Non-Overlap Time:
1.5 ms on de-energisation between NC and NO contact || 1.5 ms on energisation between NC and NO contact
Product Or Component Type:
contactor
$371.00

Description

TeSys D Green contactors have been designed for perfect integration into control systems. They can be used to create motor starters for almost any type of application. TeSys D contactors are available in 13 contactor ratings for inductive motor applications up to 150 full-load amps and resistive loads up to 200 amps. This 4 pole IEC contactor can be mounted on DIN rail or mounted directly to a panel. Contactor has four normally open power contacts. Power contacts have a 60A resistive load rating. Equipped with an electronic coil, wide band voltage 100-250V, AC/DC compatible, low consumption. Contactor has one normally open and one normally closed auxiliary contact built-in as standard. The NC contact is mirror certified. Ring-lug screw terminals are used for load and auxiliary connections. An extensive line of accessories makes it easy to meet the requirements of most applications. The contactor is 4.80 inches tall, 2.76 inches wide and 4.72 inches deep. It weighs 2.40 lbs. Contactor is certified to UL, CSA, IEC, CCC, EAC and Marine standards. Contactor also meets the requirements of RoHS/REACh making it a Green Premium product.