Schneider Electric

Schneider Electric LC1DT80A6BNE IEC contactor, TeSys Deca Green, nonreversing, 80A resistive, 4 pole, 4 NO, 24/60VAC/VDC coil, open style

(No reviews yet) Write a Review
SKU:
LC1DT80A6BNE
MPN:
LC1DT80A6BNE
Condition:
New
Eu Rohs Directive:
Compliant with Exemptions
Compatibility Code:
LC1D
Climatic Withstand:
IACS E10 exposure to damp heat || IEC 60947-1 Annex Q category D exposure to damp heat
Non-Overlap Time:
1.5 ms on de-energisation between NC and NO contact || 1.5 ms on energisation between NC and NO contact
Mechanical Durability:
6 Mcycles
[Uimp] Rated Impulse Withstand Voltage:
6 kV IEC 60947
China Rohs Regulation:
Product out of China RoHS scope. Substance declaration for your information.
Contactor Application:
resistive load
Utilisation Category:
AC-1
Weight:
1.290 kg
Standards:
EN/IEC 60947-4-1 || EN/IEC 60947-5-1 || UL 60947-4-1 || CSA C22.2 No 60947-4-1 || IEC 60335-1
Poles Description:
4P
Rohs Exemption Information:
Yes
Hold-In Power Consumption In Va:
1-1 VA 50/60 Hz (at 20°C)
Product Certifications:
CCC || CSA || EAC || UL || KC || DNV-GL || LROS (Lloyds register of shipping) || UKCA
Inrush Power In Va:
15-15 VA 50/60 Hz (at 20°C)
Signaling Circuit Frequency:
25...400 Hz
Fire Resistance:
850°C IEC 60695-2-1
Operating Altitude:
0...9842.52 ft (0...3000 m)
Control Circuit Type:
AC/DC 50/60 Hz AC/DC electronic
Maximum Operating Rate:
3600 cyc/h 60°C
Weee:
The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins.
Auxiliary Contact Composition:
1 NO + 1 NC
Flame Retardance:
V1 conforming to UL 94
Height:
122 mm
[Ue] Rated Operational Voltage:
power circuit <= 690 V AC 25...400 Hz
Pollution Degree:
3
[Ith] Conventional Free Air Thermal Current:
80 A (at 60°C) for power circuit || 10 A (at 60°C) for Signaling circuit
[Uc] Control Circuit Voltage:
24...60 V AC 50/60 Hz || 24...60 V DC
Heat Dissipation:
0.7-0.7 W at 50/60 Hz
Range:
TeSys || TeSys Deca
Tightening Torque:
control circuit 1.7 N.m lugs-ring terminals flat Ø 6 mm M3.5 || control circuit 1.7 N.m lugs-ring terminals Philips No 2 M3.5 || power circuit 6 N.m lugs-ring terminals hexagonal 10 mm M6 || power circuit 6 N.m lugs-ring terminals pozidriv No 2 M4 |
Net Weight:
1.290 kg
Minimum Switching Voltage:
17 V for Signaling circuit
Overvoltage Category:
III
Sustainable Offer Status:
Green Premium product
Connections - Terminals:
power circuit: lugs-ring terminals - external diameter: 16.5 mm || control circuit: lugs-ring terminals - external diameter: 8 mm
Halogen Content Performance:
Halogen free plastic parts & cables product
Power Dissipation Per Pole:
10.2 W AC-1
Irms Rated Making Capacity:
1000 A at 440 V for power circuit conforming to IEC 60947 || 140 A AC for Signaling circuit conforming to IEC 60947-5-1 || 250 A DC for Signaling circuit conforming to IEC 60947-5-1
Depth:
120 mm
Inrush Power In W:
16-16 W 20°C)
Coil Technology:
built-in bidirectional peak limiting
Operating Time:
55...65 ms closing || 20...80 ms opening
Range Of Product:
TeSys Deca
Ip Degree Of Protection:
IP20 front face IEC 60529
Country of Origin:
France
Safety Reliability Level:
B10d = 1369863 cycles contactor with nominal load EN/ISO 13849-1 || B10d = 20000000 cycles contactor with mechanical load EN/ISO 13849-1
Permissible Ambient Air Temperature Around The Device:
-40-60°C || 60-70°C with derating
Control Circuit Voltage Limits:
<= 0.1 Uc -40-70°C drop-out AC/DC || 0.85...1.1 Uc -40-60°C operational AC || 0.8...1.1 Uc -40-60°C operational DC || 1...1.1 Uc 60-70°C operational AC/DC
$642.00

Description

TeSys D Green contactors have been designed for perfect integration into control systems. They can be used to create motor starters for almost any type of application. TeSys D contactors are available in 13 contactor ratings for inductive motor applications up to 150 full-load amps and resistive loads up to 200 amps. This 4 pole IEC contactor can be mounted on DIN rail or mounted directly to a panel. Contactor has four normally open power contacts. Power contacts have a 80A resistive load rating. Equipped with an electronic coil, wide band voltage 24-60V, AC/DC compatible, low consumption. Contactor has one normally open and one normally closed auxiliary contact built-in as standard. The NC contact is mirror certified. Ring-lug screw terminals are used for load and auxiliary connections. An extensive line of accessories makes it easy to meet the requirements of most applications. The contactor is 4.80 inches tall, 2.76 inches wide and 4.72 inches deep. It weighs 2.40 lbs. Contactor is certified to UL, CSA, IEC, CCC, EAC and Marine standards. Contactor also meets the requirements of RoHS/REACh making it a Green Premium product.