Schneider Electric LC1DT80A6F7 IEC contactor, TeSys D, nonreversing, 80A resistive, 4 pole, 4 NO, 110VAC 50/60Hz coil, open style
Schneider Electric
$450.80
TeSys D contactors have been designed for perfect integration into control systems. They can be used to create motor starters for almost any type of application. TeSys D contactors are available in 13 contactor ratings for inductive motor applications up to 150 full-load amps and resistive loads up to 200 amps. This 4 pole IEC contactor can be mounted on DIN rail or mounted directly to a panel. Contactor has four normally open power contacts. Power contacts have a 80A resistive load rating. Contactor is supplied with a 110 VAC 50/60 Hz coil. Contactor has one normally open and one normally closed auxiliary contact built-in as standard. The NC contact is mirror certified. Ring-lug screw terminals are used for load and auxiliary connections. An extensive line of accessories makes it easy to meet the requirements of most applications. The contactor is 4.80 inches tall, 2.76 inches wide and 4.72 inches deep. It weighs 2.54 lbs. Contactor is certified to UL, CSA, IEC, CCC, EAC and Marine standards. Contactor also meets the requirements of RoHS/REACh making it a Green Premium product.
- Flame Retardance:
- V1 conforming to UL 94
- Climatic Withstand:
- IACS E10 exposure to damp heat || IEC 60947-1 Annex Q category D exposure to damp heat
- Heat Dissipation:
- 4-5 W at 50/60 Hz
- Ip Degree Of Protection:
- IP20 front face IEC 60529
- Environmental Disclosure:
- ENVPEP1503009EN
- Warranty:
- 18 months
- Mounting Support:
- plate || rail
- Rated Breaking Capacity:
- 1000 A at 440 V for power circuit conforming to IEC 60947
- Device Short Name:
- LC1D
- Signaling Circuit Frequency:
- 25...400 Hz
- Average Impedance:
- 1.6 mOhm - Ith 80 A 50 Hz for power circuit
- Insulation Resistance:
- > 10 MOhm for Signaling circuit
- Protective Treatment:
- THIEC 60068-2-30
- Non-Overlap Time:
- 1.5 ms on de-energisation between NC and NO contact || 1.5 ms on energisation between NC and NO contact
- Product Or Component Type:
- contactor
- Protective Cover:
- with
- Pole Contact Composition:
- 4 NO
- Coil Technology:
- without built-in suppressor module
- Weee:
- The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins.
- Reach Regulation:
- Free of Substances of Very High Concern above the threshold
- Tightening Torque:
- control circuit 1.7 N.m lugs-ring terminals flat Ø 6 mm M3.5 || control circuit 1.7 N.m lugs-ring terminals Philips No 2 M3.5 || power circuit 6 N.m lugs-ring terminals M6 || control circuit 1.7 N.m lugs-ring terminals pozidriv No 2 M3.5
- Mechanical Robustness:
- vibrations contactor open 2 Gn, 5...300 Hz) || vibrations contactor closed 4 Gn, 5...300 Hz) || shocks contactor closed 15 Gn for 11 ms) || shocks contactor open 10 Gn for 11 ms)
- Rohs Exemption Information:
- Yes
- Operating Altitude:
- 0...9842.52 ft (0...3000 m)
- Pvc Free:
- Yes
- Product Certifications:
- DNV || CCC || GL || GOST || LROS (Lloyds register of shipping) || BV || CSA || RINA || UL
- Permissible Ambient Air Temperature Around The Device:
- -40-60°C || 60-70°C with derating
- Depth:
- 120 mm
- Weight:
- 1.15 kg
- [Ue] Rated Operational Voltage:
- power circuit <= 690 V AC 25...400 Hz || power circuit <= 300 V DC
- Mechanical Durability:
- 6 Mcycles
- Compatibility Code:
- LC1D
- Minimum Switching Voltage:
- 17 V for Signaling circuit
- Auxiliary Contacts Type:
- mechanically linked 1 NO + 1 NC IEC 60947-5-1 || mirror contact 1 NC IEC 60947-4-1
- [Icw] Rated Short-Time Withstand Current:
- 640 A 40°C - 10 s for power circuit || 900 A 40°C - 1 s for power circuit || 110 A 40°C - 10 min for power circuit || 260 A 40°C - 1 min for power circuit || 100 A - 1 s for Signaling circuit || 120 A - 500 ms for Signaling circuit || 140 A - 100 ms
- China Rohs Regulation:
- Pro-active China RoHS declaration (out of China RoHS legal scope)
- Height:
- 122 mm
- Sustainable Offer Status:
- Green Premium product
- Connections - Terminals:
- control circuit: lugs-ring terminals - external diameter: 8 mm || power circuit: lugs-ring terminals - external diameter: 16.5 mm
- Electrical Durability:
- 1.4 Mcycles 80 A AC-1 <= 440 V
- Utilisation Category:
- AC-1
- Hold-In Power Consumption In Va:
- 13-13 VA 60 Hz cos phi 0.3 (at 20°C) || 15-15 VA 50 Hz cos phi 0.3 (at 20°C)
- Standards:
- CSA C22.2 No 14 || EN 60947-4-1 || EN 60947-5-1 || IEC 60947-4-1 || IEC 60947-5-1 || UL 508
- Power Dissipation Per Pole:
- 10.2 W AC-1
- Operating Time:
- 4...19 ms opening || 12...26 ms closing
- [Ith] Conventional Free Air Thermal Current:
- 10 A (at 60°C) for Signaling circuit || 80 A (at 60°C) for power circuit
- Control Circuit Type:
- AC 50/60 Hz
- [Ie] Rated Operational Current:
- 80 A (at <60°C) at <= 440 V AC AC-1 for power circuit
- Circularity Profile:
- ENVEOLI1503009EN
- Associated Fuse Rating:
- 10 A gG for Signaling circuit conforming to IEC 60947-5-1 || 125 A gG at <= 690 V coordination type 1 for power circuit || 125 A gG at <= 690 V coordination type 2 for power circuit