Schneider Electric

Schneider Electric LC1DT80ABBE IEC contactor, TeSys Deca Green, nonreversing, 80A resistive, 4 pole, 4 NO, 24VDC coil, open style

(No reviews yet) Write a Review
SKU:
LC1DT80ABBE
MPN:
LC1DT80ABBE
Condition:
New
Standards:
EN/IEC 60947-4-1 || EN/IEC 60947-5-1 || UL 60947-4-1 || CSA C22.2 No 60947-4-1 || IEC 60335-1
Minimum Switching Voltage:
17 V for Signaling circuit
Maximum Operating Rate:
3600 cyc/h 60°C
Pollution Degree:
3
Signaling Circuit Frequency:
25...400 Hz
Weight:
1.290 kg
Ip Degree Of Protection:
IP20 front face IEC 60529
Rated Breaking Capacity:
1000 A at 440 V for power circuit conforming to IEC 60947
Weee:
The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins.
Permissible Ambient Air Temperature Around The Device:
-40-60°C || 60-70°C with derating
Circularity Profile:
ENVEOLI1607010EN
Safety Reliability Level:
B10d = 1369863 cycles contactor with nominal load EN/ISO 13849-1 || B10d = 20000000 cycles contactor with mechanical load EN/ISO 13849-1
Warranty:
18 months
Mechanical Durability:
6 Mcycles
Tightening Torque:
control circuit 1.7 N.m screw clamp terminals flat Ø 6 mm || control circuit 1.7 N.m screw clamp terminals Philips No 2 || power circuit 8 N.m EverLink BTR screw connectors 25-35 mm² hexagonal 4 mm || power circuit 5 N.m EverLink BTR screw connecto
[Ith] Conventional Free Air Thermal Current:
80 A (at 60°C) for power circuit || 10 A (at 60°C) for Signaling circuit
[Icw] Rated Short-Time Withstand Current:
110 A 40°C - 10 min for power circuit || 260 A 40°C - 1 min for power circuit || 520 A 40°C - 10 s for power circuit || 900 A 40°C - 1 s for power circuit || 100 A - 1 s for Signaling circuit || 120 A - 500 ms for Signaling circuit || 140 A - 100 ms
Associated Fuse Rating:
125 A gG at <= 690 V coordination type 1 for power circuit || 125 A gG at <= 690 V coordination type 2 for power circuit || 10 A gG for Signaling circuit conforming to IEC 60947-5-1
Utilisation Category:
AC-1
Reach Regulation:
Reference contains Substances of Very High Concern above the threshold
Halogen Content Performance:
Halogen free plastic parts & cables product
Heat Dissipation:
0.5-0.5 W
[Uc] Control Circuit Voltage:
24 V DC
Operating Time:
55...65 ms closing || 20...80 ms opening
Irms Rated Making Capacity:
1000 A at 440 V for power circuit conforming to IEC 60947 || 140 A AC for Signaling circuit conforming to IEC 60947-5-1 || 250 A DC for Signaling circuit conforming to IEC 60947-5-1
Coil Technology:
built-in bidirectional peak limiting
Insulation Resistance:
> 10 MOhm for Signaling circuit
Non-Overlap Time:
1.5 ms on de-energisation between NC and NO contact || 1.5 ms on energisation between NC and NO contact
Mercury Free:
Yes
Net Weight:
1.290 kg
Country of Origin:
United States
[Ui] Rated Insulation Voltage:
power circuit 690 V IEC 60947-4-1 || Signaling circuit 690 V IEC 60947-1
China Rohs Regulation:
Product out of China RoHS scope. Substance declaration for your information.
[Ue] Rated Operational Voltage:
power circuit <= 690 V AC 25...400 Hz
Pole Contact Composition:
4 NO
Climatic Withstand:
IACS E10 exposure to damp heat || IEC 60947-1 Annex Q category D exposure to damp heat
Depth:
120 mm
Eu Rohs Directive:
Compliant with Exemptions
Power Dissipation Per Pole:
10.2 W AC-1
Overvoltage Category:
III
Auxiliary Contact Composition:
1 NO + 1 NC
Compatibility Code:
LC1D
Rohs Exemption Information:
Yes
Auxiliary Contacts Type:
mechanically linked 1 NO + 1 NC IEC 60947-5-1 || mirror contact 1 NC IEC 60947-4-1
Connections - Terminals:
control circuit: screw clamp terminals 1 1-4 mm² - cable stiffness: flexible without cable end || control circuit: screw clamp terminals 2 1-4 mm² - cable stiffness: flexible without cable end || control circuit: screw clamp terminals 1 1-4 mm² -
Product Certifications:
CCC || CSA || EAC || UL || KC || DNV-GL || LROS (Lloyds register of shipping) || UKCA
$642.00

Description

TeSys D Green contactors have been designed for perfect integration into control systems. They can be used to create motor starters for almost any type of application. TeSys D contactors are available in 13 contactor ratings for inductive motor applications up to 150 full-load amps and resistive loads up to 200 amps. This 4 pole IEC contactor can be mounted on DIN rail or mounted directly to a panel. Contactor has four normally open power contacts. Power contacts have a 80A resistive load rating. Equipped with an electronic 24V DC coil, low consumption, for a direct control by a PLC output 24V DC / 500mA. Contactor has one normally open and one normally closed auxiliary contact built-in as standard. The NC contact is mirror certified. Screw clamp terminals are used for load and auxiliary connections. An extensive line of accessories makes it easy to meet the requirements of most applications. The contactor is 4.80 inches tall, 2.76 inches wide and 4.72 inches deep. It weighs 2.40 lbs. Contactor is certified to UL, CSA, IEC, CCC, EAC and Marine standards. Contactor also meets the requirements of RoHS/REACh making it a Green Premium product.
View AllClose