Schneider Electric LC1DT80AFD IEC contactor, TeSys Deca, nonreversing, 80A resistive, 4 pole, 4 NO, 110VDC coil, open style
Schneider Electric
$535.00
TeSys D contactors have been designed for perfect integration into control systems. They can be used to create motor starters for almost any type of application. TeSys D contactors are available in 13 contactor ratings for inductive motor applications up to 150 full-load amps and resistive loads up to 200 amps. This 4 pole IEC contactor can be mounted on DIN rail or mounted directly to a panel. Contactor has four normally open power contacts. Power contacts have a 80A resistive load rating. Contactor is supplied with a 110 VDC coil with transient suppressor module. Contactor has one normally open and one normally closed auxiliary contact built-in as standard. The NC contact is mirror certified. Screw clamp terminals are used for load and auxiliary connections. An extensive line of accessories makes it easy to meet the requirements of most applications. The contactor is 4.80 inches tall, 2.76 inches wide and 4.72 inches deep. It weighs 2.70 lbs. Contactor is certified to UL, CSA, IEC, CCC, EAC and Marine standards. Contactor also meets the requirements of RoHS/REACh making it a Green Premium product.
- Net Weight:
- 1.225 kg
- Maximum Operating Rate:
- 3600 cyc/h 60°C
- Pvc Free:
- Yes
- Product Or Component Type:
- contactor
- [Ie] Rated Operational Current:
- 80 A (at <60°C) at <= 440 V AC AC-1 for power circuit
- Sustainable Offer Status:
- Green Premium product
- Insulation Resistance:
- > 10 MOhm for Signaling circuit
- Overvoltage Category:
- III
- Product Certifications:
- RINA || UL || BV || CSA || GOST || LROS (Lloyds register of shipping) || GL || CCC || DNV
- Inrush Power In W:
- 19-19 W 20°C)
- Connections - Terminals:
- control circuit: screw clamp terminals 2 1-2.5 mm² - cable stiffness: flexible with cable end || control circuit: screw clamp terminals 1 1-4 mm² - cable stiffness: flexible without cable end || control circuit: screw clamp terminals 2 1-4 mm² - c
- Device Short Name:
- LC1D
- Contactor Application:
- resistive load
- [Ui] Rated Insulation Voltage:
- power circuit 600 V CSA || power circuit 600 V UL || Signaling circuit 690 V IEC 60947-1 || Signaling circuit 600 V CSA || Signaling circuit 600 V UL || power circuit 690 V IEC 60947-4-1
- Power Dissipation Per Pole:
- 10.2 W AC-1
- Flame Retardance:
- V1 conforming to UL 94
- Environmental Disclosure:
- ENVPEP1503009EN
- Reach Regulation:
- Free of Substances of Very High Concern above the threshold
- Pollution Degree:
- 3
- [Ue] Rated Operational Voltage:
- power circuit <= 690 V AC 25...400 Hz || power circuit <= 300 V DC
- Climatic Withstand:
- IACS E10 exposure to damp heat || IEC 60947-1 Annex Q category D exposure to damp heat
- Height:
- 122 mm
- Rohs Exemption Information:
- Yes
- Operating Time:
- 50±15 % ms closing || 16...24 ms opening
- Mechanical Robustness:
- vibrations contactor open 2 Gn, 5...300 Hz) || vibrations contactor closed 4 Gn, 5...300 Hz) || shocks contactor closed 15 Gn for 11 ms) || shocks contactor open 10 Gn for 11 ms)
- Mercury Free:
- Yes
- Width:
- 70 mm
- Control Circuit Type:
- DC standard
- Safety Reliability Level:
- B10d = 1369863 cycles contactor with nominal load EN/ISO 13849-1 || B10d = 20000000 cycles contactor with mechanical load EN/ISO 13849-1
- Standards:
- CSA C22.2 No 14 || EN 60947-4-1 || EN 60947-5-1 || IEC 60947-4-1 || IEC 60947-5-1 || UL 508 || IEC 60335-1
- Mechanical Durability:
- 10 Mcycles
- Mounting Support:
- plate || rail
- Signaling Circuit Frequency:
- 25...400 Hz
- Associated Fuse Rating:
- 10 A gG for Signaling circuit conforming to IEC 60947-5-1 || 125 A gG at <= 690 V coordination type 1 for power circuit || 125 A gG at <= 690 V coordination type 2 for power circuit
- [Uc] Control Circuit Voltage:
- 110 V DC
- Weight:
- 1.225 kg
- Time Constant:
- 34 ms
- Minimum Switching Voltage:
- 17 V for Signaling circuit
- Auxiliary Contact Composition:
- 1 NO + 1 NC
- Eu Rohs Directive:
- Compliant
- Reach Free Of Svhc:
- Yes
- Pole Contact Composition:
- 4 NO
- Range:
- TeSys || TeSys Deca
- Control Circuit Voltage Limits:
- 0.1...0.3 Uc -40-70°C drop-out DC || 0.75...1.25 Uc -40-60°C operational DC || 1...1.25 Uc 60-70°C operational DC
- Average Impedance:
- 1.6 mOhm - Ith 80 A 50 Hz for power circuit
- [Uimp] Rated Impulse Withstand Voltage:
- 6 kV IEC 60947
- Country of Origin:
- France
- Hold-In Power Consumption In W:
- 7.4-7.4 W 20°C
- Non-Overlap Time:
- 1.5 ms on de-energisation between NC and NO contact || 1.5 ms on energisation between NC and NO contact