Schneider Electric LC1F1250 contactor body withou coil, TeSys F, 3P(3NO), AC-1 <=440V 1260A with coil LX1/ LX9, 110…600V AC 40/400Hz, LX4, 48…250V DC
Schneider Electric
$8,127.00
TeSys F contactor, 3 poles (3NO), 1250A/690V AC-1, for non-inductive load applications. Contactor with no coil to allow a later selection and installation (coil to be ordered separately), it provides bolt terminals for bars or cables with lugs. For high operating rates until 600 cycles/hour and environments until 55°C, it procures high reliability and durability. It makes installation and maintenance easy thanks to a drawer for insertion of the selected coil and a large choice of add-on blocks and accessories (to be ordered separately). Multi standards certified (IEC, UL, CSA, CCC), Green Premium compliant (RoHS/REACh).
- Contactor Application:
- resistive load
- Heat Dissipation:
- 20-20 W
- Ambient Air Temperature For Storage:
- -60-80°C
- Environmental Disclosure:
- ENVPEP1505009EN
- China Rohs Regulation:
- Product out of China RoHS scope. Substance declaration for your information.
- Range:
- TeSys
- Operating Time:
- 40...80 ms closing with LX1/LX9 coil || 100...200 ms opening with LX1/LX9 coil || 60...70 ms closing with LX4 coil || 40...50 ms opening with LX4 coil
- Overvoltage Category:
- III
- Associated Fuse Rating:
- 1400 A gG at <= 440 V for power circuit
- Permissible Ambient Air Temperature Around The Device:
- -40-60°C
- Device Short Name:
- LC1F
- Average Impedance:
- 0.12 mOhm - Ith 1260 A 50 Hz
- Sustainable Offer Status:
- Green Premium product
- Mounting Support:
- plate
- Circularity Profile:
- ENVEOLI1505009EN
- Ambient Air Temperature For Operation:
- -5-40°C
- Weee:
- The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins.
- Net Weight:
- 19 kg
- Control Circuit Voltage Limits:
- operational: 0.85...1.1 Uc AC 40...400 Hz with LX1/LX9 coil || drop-out: 0.25...0.5 Uc AC 40...400 Hz with LX1/LX9 coil || operational: 0.85...1.1 Uc DC with LX4 coil || drop-out: 0.2...0.35 Uc DC with LX4 coil
- [Ith] Conventional Free Air Thermal Current:
- 1260 A (at 40°C)
- Country of Origin:
- Czechia
- Hold-In Power Consumption In Va:
- 20-25 VA, 40...400 Hz cos phi 0.9 (at 20°C)with LX1/LX9 coil || 6.5-12.5 VA (at 20°C)with LX4 coil
- Reach Regulation:
- Reference contains Substances of Very High Concern above the threshold
- Weight:
- 19 kg
- [Ie] Rated Operational Current:
- 1260 A 40°C) <= 440 V AC-1
- Product Or Component Type:
- contactor
- Rated Breaking Capacity:
- 1890 A conforming to IEC 60947-4-1
- Maximum Operating Rate:
- 1200 cyc/h 55°C
- California Proposition 65:
- WARNING: This product can expose you to chemicals including: Lead and lead compounds, which is known to the State of California to cause cancer and birth defects or other reproductive harm. For more information go to www.P65Warnings.ca.gov
- Connections - Terminals:
- power circuit bar 2 || power circuit bolted connection || control circuit screw clamp terminals 1 1-4 mm²flexible without cable end || control circuit screw clamp terminals 2 1-4 mm²flexible with cable end || control circuit screw clamp terminals
- Power Dissipation Per Pole:
- 120 W AC-1
- [Uc] Control Circuit Voltage:
- 110...600 V AC 40...400 Hz with LX1/LX9 coil || 28...250 V DC with LX4 coil
- Poles Description:
- 3P
- Product Certifications:
- CB || UL || CSA || CQC || CE || UKCA || CCC
- [Icw] Rated Short-Time Withstand Current:
- 3000 A 40°C - 3 min || 5200 A 40°C - 30 s || 4000 A 40°C - 1 min || 2000 A 40°C - 10 min || 8000 A 40°C - 10 s
- Pole Contact Composition:
- 3 NO
- Rohs Exemption Information:
- Yes
- Product Name:
- TeSys F
- Mercury Free:
- Yes
- Mechanical Durability:
- 1 Mcycles
- Mechanical Robustness:
- vibrations contactor open2 Gn, 5...300 Hz || vibrations contactor closed4 Gn, 5...300 Hz || shocks contactor open6 Gn for 1/2 sine wave (11 ms) || shocks contactor closed15 Gn for 1/2 sine wave (11 ms)
- Protective Treatment:
- TH
- Warranty:
- 18 months
- Standards:
- IEC 60947-1 || EN 60947-1 || JIS C8201-4-1 || EN 60947-4-1 || IEC 60947-4-1
- Utilisation Category:
- AC-1
- Irms Rated Making Capacity:
- 1890 A conforming to IEC 60947-4-1