Schneider Electric

Schneider Electric LC1F1250M7 contactor, TeSys F, 3P(3NO), AC-1, <=690V 1260 A, coil 220V AC

(No reviews yet) Write a Review
SKU:
LC1F1250M7
MPN:
LC1F1250M7
Condition:
New
[Ie] Rated Operational Current:
1260 A (at <40°C) AC-1
Standards:
EN 60947-4-1 || IEC 60947-4-1 || IEC 60947-1 || EN 60947-1 || JIS C8201-4-1
Reach Regulation:
Reference contains Substances of Very High Concern above the threshold
Operating Time:
40...80 ms closing || 100...200 ms opening
Compatibility Code:
LC1F
Mercury Free:
Yes
Hold-In Power Consumption In Va:
22-22 VA, 40...400 Hz 0.9 20°C)
Circularity Profile:
ENVEOLI1505009EN
Range:
TeSys
Contactor Application:
resistive load
[Ith] Conventional Free Air Thermal Current:
1260 A (at 40°C)
Control Circuit Voltage Limits:
operational 0.85...1.1 Uc 40...400 Hz 55°C) || drop-out 0.25...0.5 Uc 40...400 Hz 55°C)
Power Dissipation Per Pole:
120 W AC-1
[Ue] Rated Operational Voltage:
<= 460 V DC || <= 690 V AC 50/60 Hz
Permissible Ambient Air Temperature Around The Device:
-40-60°C
Weee:
The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins.
Operating Altitude:
9842.52 ft (3000 m) without derating
Country of Origin:
Czechia
Sustainable Offer Status:
Green Premium product
Range Of Product:
TeSys F
Rohs Exemption Information:
Yes
Connections - Terminals:
control circuit screw clamp terminals 1 1-4 mm²flexible without cable end || control circuit screw clamp terminals 2 1-4 mm²flexible without cable end || control circuit screw clamp terminals 1 1-4 mm²flexible with cable end || control circuit scr
Overvoltage Category:
III
Product Certifications:
CB || UL || CSA || CQC || CE || UKCA || CCC
[Uimp] Rated Impulse Withstand Voltage:
8 kV
Ambient Air Temperature For Storage:
-60-80°C
[Ui] Rated Insulation Voltage:
1000 V IEC 60947-4-1 || 1500 V VDE 0110 group C
Warranty:
18 months
Heat Dissipation:
20-20 W
Device Short Name:
LC1F
Associated Fuse Rating:
1000 A gG at <= 440 V
Control Circuit Type:
AC 40...400 Hz
Inrush Power In Va:
1650-1650 VA, 40...400 Hz 0.9 20°C)
Rated Breaking Capacity:
1890 A conforming to IEC 60947-4-1
Net Weight:
19 kg
Protective Treatment:
TH
Tightening Torque:
control circuit 1.2 N.m || power circuit 58 N.m
Depth:
255 mm
Eu Rohs Directive:
Compliant with Exemptions
Average Impedance:
0.12 mOhm - Ith 1260 A 50 Hz
Pole Contact Composition:
3 NO
Utilisation Category:
AC-1
[Icw] Rated Short-Time Withstand Current:
3000 A 40°C - 3 min || 8000 A 40°C - 10 s || 5200 A 40°C - 30 s || 4000 A 40°C - 1 min || 2000 A 40°C - 10 min
Poles Description:
3P
Ambient Air Temperature For Operation:
-5-40°C
California Proposition 65:
WARNING: This product can expose you to chemicals including: Lead and lead compounds, which is known to the State of California to cause cancer and birth defects or other reproductive harm. For more information go to www.P65Warnings.ca.gov
$8,525.00